Regulation 543.1 of BS 7671 sets out the requirements for sizing protective conductors. It states that the cross-sectional area of every protective conductor, other than a protective bonding conductor, shall be calculated by the adiabatic equation or selected in accordance with Table 54.7. The regulation makes it clear that the adiabatic equation is the definitive method — Table 54.7 is a simplified alternative that gives conservative (larger) sizes.
The regulation specifies that the calculated cross-sectional area shall be not less than the value determined by the equation S = √(I²t) / k, where the symbols have the meanings described above. It also notes that the k values are given in Tables 54.2 to 54.6, and that the value of I²t shall not exceed the value given by the manufacturer for the protective device.
In practice, this means that for every circuit in an installation, the designer or verifier must either confirm that the CPC size meets Table 54.7 (the simpler check) or perform the adiabatic calculation to verify that the installed CPC is at least as large as the minimum calculated. The adiabatic method is particularly important for non-standard situations — for example, when the CPC is not the same material as the line conductor, when steel wire armour is used as the CPC, or when the designer wants to use a smaller CPC than Table 54.7 would require to reduce costs.
Amendment 4 to BS 7671 (A4:2026), published 15 April 2026, did not change the fundamental adiabatic equation requirements but added Regulation 530.3.201 covering requirements for bidirectional and unidirectional protective devices. The core CPC sizing requirements in Regulation 543.1 remain as established in the 18th Edition.
Zs and the adiabatic check interact for small cables (GN3 Reg 1.25): For smaller cross-sectional area cables, the earth fault loop impedance (Zs) may be limited by the adiabatic equation as well as by the maximum Zs disconnection requirement. A circuit can pass the Zs limit check — meaning the fault current is high enough to operate the device within the permitted disconnection time — yet still fail the adiabatic check if the fault current is modest and the device is slow. Both checks must always be carried out; satisfying one does not guarantee the other.