Trunking fill refers to the proportion of a cable trunking's internal cross-sectional area that is occupied by cables. BS 7671:2018+A4:2026 and the IET Guidance Note 1 state that the total cross-sectional area of all cables installed in trunking must not exceed 45% of the trunking's internal cross-sectional area. This is known as the 45% fill rule, and it applies to all types of cable trunking — PVC, galvanised steel, stainless steel, aluminium, dado, skirting, and mini-trunking.
Why 45% and not more? The 45% limit exists for three reasons. First, heat dissipation: when current flows through cables, the conductors generate heat. The air space inside the trunking acts as a cooling medium, allowing heat to transfer from the cable surface to the trunking walls and then to the surrounding environment. If the trunking is packed too tightly, the temperature inside rises, potentially exceeding the cable insulation's rated temperature and causing degradation or failure.
Second, installation practicality: cables need to be laid into the trunking without excessive bending or forcing. They must be arranged neatly to avoid crossing over each other, which creates pressure points that can damage insulation over time. A 45% fill leaves enough space for cables to be routed neatly with gentle bends at fittings and junctions.
Third, future capacity: good design practice — and many specifications — require spare capacity for additional circuits. Building use changes over time, and new circuits are frequently needed for additional power points, data outlets, or replacement of existing services. A trunking system designed to 45% fill on day one has no spare capacity; designing to 30 to 35% fill on day one leaves room for growth. When planning containment, use the cable sizing calculator to determine the required cable cross-section before checking trunking fill, and the voltage drop calculator to verify the circuit meets BS 7671 limits.
Total cable CSA ≤ 45% of trunking internal CSA
The fundamental trunking fill rule from BS 7671