Earth fault loop impedance is the total impedance of the fault current path: the source, the line conductor up to the point of the fault, and the protective conductor between the fault and the source. A lower Zs means more fault current, and more fault current means faster disconnection.
The formula is the same, the regulation number is not
For a TN system, Reg 411.4.4 requires Zs x Ia ≤ Uo x Cmin. For a TT system protected by an overcurrent device, Reg 411.5.4 states the same requirement. Uo is the nominal line to earth voltage and Cmin is the minimum voltage factor, given the value 0.95 for a low voltage supply provided in accordance with the ESQCR. Ia is the current causing automatic operation of the device within the time required by Reg 411.3.2.2 or 411.3.2.3.
Worked through for a 32A Type B MCB, that gives a maximum Zs of 1.37Ω — the figure printed in Table 41.3. A TN-C-S installation with a Ze of 0.30Ω leaves ample headroom for the circuit conductors. A TT installation with a Ze of 50Ω is nowhere near it, which is why fault protection on TT is provided by an RCD reading against Table 41.5 instead.
Disconnection times differ by system, not just by device
Table 41.1 gives 0.4s for a 230V AC final circuit on a TN system and 0.2s for the same circuit on TT. For distribution circuits and circuits outside the scope of Reg 411.3.2.2, Reg 411.3.2.3 permits up to 5s on TN and Reg 411.3.2.4 permits up to 1s on TT. Quoting the TN figure on a TT installation is a common slip on certificates and in exams.