Part of 70 Electrical Calculators

Conduit Fill CalculatorCable Factor Method to BS 7671

Calculate conduit fill using the cable factor method. Instantly determine the right conduit size for any combination of cables, with bend adjustments and trunking fill mode included.

Conduit Fill Calculator

Calculate fill percentage with BS EN 61386-1 compliance

Fill % = (Total Cable Area ÷ Conduit Area) × 100. Lower fill = easier installation.

What Is Conduit Fill and Why Does It Matter?

Conduit fill refers to the proportion of a conduit's internal space that is occupied by cables. Getting this right is critical for three reasons: heat dissipation, pulling tension during installation, and future capacity for additional cables.

Heat dissipation: When current flows through a cable, the conductor generates heat due to its resistance. This heat must be dissipated through the cable insulation, through the air space inside the conduit, through the conduit wall, and finally to the surrounding environment. If the conduit is packed too tightly with cables, the air space is insufficient, and the cables overheat. Overheating degrades the insulation over time, reducing the cable's lifespan and eventually causing insulation failure, short circuits, and potentially fire. The cable factor tables account for this by limiting the fill to approximately 40% of the conduit's internal cross-sectional area.

Pulling tension: Cables must be drawn through conduit during installation. The friction between the cable sheaths and the conduit wall, and between adjacent cables, determines how much force is needed to pull them through. If the conduit is overfilled, the pulling tension becomes excessive, risking damage to the cable insulation — particularly at bends where the cables are pressed against the conduit wall. Damaged insulation can lead to earth faults, short circuits, and reduced insulation resistance readings during testing.

Future capacity: Good installation practice and BS 7671 encourage leaving spare capacity in conduit systems to accommodate future circuit additions. An installation that is filled to maximum capacity on day one leaves no room for the additional circuits that building alterations, extensions, or technology upgrades may require. Many specifications call for conduit to be no more than 30 to 35% full to allow for future growth.

For these reasons, conduit fill calculations are a fundamental part of electrical design. They should be performed before any conduit is installed, and the results documented as part of the design records. Guessing conduit sizes based on experience alone often leads to under-sized conduit that causes problems during cable pulling, or over-sized conduit that wastes material and installation time. Pair conduit fill checks with the cable derating calculator to account for grouping factors, and the cable sizing calculator to confirm your conductor sizes before pulling.

The Cable Factor Method Explained

The cable factor method is the standard approach in the UK for calculating conduit fill. It uses a system of dimensionless "factors" — one for each cable size and one for each conduit size — that make the calculation simple without needing to work with actual cross-sectional areas in square millimetres.

The principle is straightforward: each cable has a cable factor that represents the space it occupies. Each conduit has a conduit factor that represents the space available. If the sum of all cable factors is less than or equal to the conduit factor, the cables will fit with adequate clearance for heat dissipation and pulling.

Sum of cable factors ≤ Conduit factor

If this condition is met, the cables fit. If not, use a larger conduit.

The cable factors are derived from the overall diameter of each cable (including insulation), and the conduit factors are derived from the usable internal cross-sectional area of each conduit size, reduced to approximately 40% to allow for air space and pulling clearance. This means the factor system already has the safety margin built in — you do not need to apply an additional reduction.

Cable Factor Tables

The table below shows the cable factors for the most common sizes of single-core PVC insulated cables (to BS 6004) used in conduit installations. These are the "singles" — individual conductors with PVC insulation but no sheath — that are drawn into conduit for wiring circuits.

Conductor CSA
Cable Factor
Typical Use
1.0 mm²
22
Lighting circuits
1.5 mm²
22
Lighting circuits
2.5 mm²
30
Socket outlets, radials
4.0 mm²
43
High-power radials
6.0 mm²
58
Cooker, shower circuits
10 mm²
105
Sub-mains, large loads
16 mm²
145
Sub-mains, distribution

Note that 1.0 mm² and 1.5 mm² cables have the same cable factor (22) because their overall diameters (including insulation) are very similar. The difference in conductor cross-section is small at these sizes, and the insulation thickness is the dominant dimension.

Conduit Factor Tables

The conduit factors below are for standard round PVC conduit (heavy gauge, to BS EN 61386). The factor depends on the conduit size and the length and complexity of the run. Straight runs and runs with gentle bends have higher factors (more capacity), while runs with multiple tight bends have lower factors.

Conduit Size
Straight Run
With Bends
Internal Diameter
16 mm
290
200
15.2 mm
20 mm
460
320
19.1 mm
25 mm
800
560
24.1 mm
32 mm
1400
980
30.8 mm
40 mm
2100
1500
38.4 mm
50 mm
3500
2450
48.4 mm

The "With Bends" column shows a reduced conduit factor for runs containing two or more bends. For runs with a single bend, use a value between the straight and bends columns. The Elec-Mate calculator adjusts the factor automatically based on the number of bends you specify.

Worked Examples

Example 1: Singles in 20 mm Conduit (Straight Run)

A conduit run carries two lighting circuits. Each circuit requires one 1.5 mm² line conductor and one 1.5 mm² neutral conductor, plus a shared 1.5 mm² CPC. Total conductors: 5 singles of 1.5 mm².

Total cable factor = 5 x 22 = 110

Conduit factor for 20 mm (straight run) = 460

Result: 110 ≤ 460 — PASS. Plenty of room. You could fit up to 20 conductors of 1.5 mm² in a 20 mm straight run (20 x 22 = 440 ≤ 460).

Example 2: Mixed Sizes in 25 mm Conduit (With Bends)

A conduit run with two 90-degree bends carries one 2.5 mm² radial circuit (line, neutral, CPC = three 2.5 mm² singles) and two 1.5 mm² lighting circuits (line, neutral each = four 1.5 mm² singles, plus one shared 1.5 mm² CPC = five 1.5 mm² singles).

Cable factor for 2.5 mm² singles: 3 x 30 = 90

Cable factor for 1.5 mm² singles: 5 x 22 = 110

Total cable factor = 90 + 110 = 200

Conduit factor for 25 mm (with bends) = 560

Result: 200 ≤ 560 — PASS. A 25 mm conduit is adequate. A 20 mm conduit with bends (factor 320) would also work: 200 ≤ 320.

Band I / Band II Segregation (OSG 7.4.1)

When planning to mix circuits in the same conduit or trunking, check whether any circuit is Band I (extra-low voltage, e.g. SELV, data, fire, security) alongside Band II (low voltage, 230 V). OSG Reg 7.4.1 prohibits Band I and Band II circuits in the same wiring system part unless one of these five conditions is satisfied:

  • (a) Every cable is insulated for the highest voltage present.
  • (b) Each conductor of a multicore cable is insulated for the highest voltage present.
  • (c) Cables are installed in separate compartments within the same trunking/conduit.
  • (d) Cables on cable tray are separated by a partition.
  • (e) Band I and Band II conductors in a multicore cable are separated by an earthed metal screen of equivalent current-carrying capacity to the largest Band II circuit.

Source: IET On-Site Guide 9th Ed (A4:2026), Reg 7.4.1; BS 7671 Reg 528.1.

Example 3: Heavy Run — Checking a 20 mm Conduit

An electrician wants to run three 2.5 mm² radial circuits and one 4 mm² cooker circuit through a single 20 mm conduit with three bends. Each 2.5 mm² circuit has 3 conductors; the 4 mm² circuit has 3 conductors.

Cable factor for 2.5 mm² singles: 9 x 30 = 270

Cable factor for 4.0 mm² singles: 3 x 43 = 129

Total cable factor = 270 + 129 = 399

Conduit factor for 20 mm with bends = 320

Result: 399 > 320 — FAIL. The 20 mm conduit is too small. Upgrading to 25 mm conduit with bends (factor 560) solves the problem: 399 ≤ 560. Alternatively, install a draw-in box to split the run and use the straight-run factor for 20 mm (460), which also works: 399 ≤ 460.

Bends, Long Runs, and Difficulty Factors

The number of bends in a conduit run has a significant impact on cable pulling difficulty. Each bend increases friction between the cables and the conduit wall, and the cables press against each other at bend points, increasing the pulling tension required. Excessive pulling tension can stretch conductors, damage insulation, and even pull cables off their terminations.

As a general rule, a conduit run should not contain more than two 90-degree bends (or the equivalent) between draw-in points. If the run requires more bends, a draw-in box or inspection tee should be installed to break the run into manageable sections. Each section is then treated as an independent run for the purposes of conduit fill calculations.

Long straight runs also present challenges. Friction accumulates over length, and a 15-metre straight run requires more pulling force than a 5-metre run. For runs exceeding 10 metres without a bend, some specifications recommend reducing the conduit factor by 10% to account for the additional friction. The Elec-Mate calculator allows you to input the run length and automatically flags long runs that may benefit from intermediate draw-in points.

Cable lubricant (sometimes called "cable wax" or "pulling compound") can significantly reduce friction during installation and is recommended for any run that is near the conduit factor limit or contains multiple bends. This does not change the conduit factor calculation, but it makes the practical installation easier and reduces the risk of cable damage.

Reg 522.8.2 — buried conduit: Where a conduit system is buried in the structure, cables shall not be drawn in until the conduit is completely erected between access points. This is a frequently overlooked site-sequencing requirement: all joints, bends and boxes must be in place before pulling commences. Pre-wired conduit assemblies specifically designed for the installation are exempt.

Trunking Fill — The 45% Rule

While conduit fill uses the cable factor method, trunking fill uses a direct cross-sectional area calculation. The IET On-Site Guide and Guidance Note 1 recommend that the total cross-sectional area of all cables installed in trunking must not exceed 45% of the internal cross-sectional area of the trunking. BS 7671 does not state this percentage limit in normative regulation text, but the guidance is universally applied in UK practice.

To perform a trunking fill calculation, you need the overall diameter of each cable (including insulation and sheath for multicore cables, or insulation only for singles). The cross-sectional area of each cable is calculated as pi times the radius squared. Sum the areas of all cables, then compare against 45% of the trunking's internal cross-sectional area (width x height for rectangular trunking).

For example, consider a 100 mm x 50 mm trunking. The internal cross-sectional area is 100 x 50 = 5000 mm². 45% of 5000 = 2250 mm². If the total cross-sectional area of all cables is 2000 mm², the trunking is adequate: 2000 ≤ 2250.

The 45% limit is more generous than the approximately 40% limit for conduit because trunking has a removable lid — cables are laid in from the top rather than pulled through, so the friction and pulling tension constraints are less severe. However, the heat dissipation requirement still applies, which is why the fill is limited to less than half.

The Elec-Mate calculator includes a trunking fill mode alongside the conduit fill mode. Select the trunking dimensions, add the cables, and the calculator shows the fill percentage with a pass/fail indication against the 45% limit.

Note also that BS 7671 Reg 530.4.3 requires any trunking system used to carry electrical equipment (such as switches or socket-outlets) to comply with the BS EN 50085 series. Always verify that the trunking product is BS EN 50085-certified before mounting equipment within it.

How to Calculate Conduit Fill — Step by Step

1

Identify all cables to be installed

List every cable that will be drawn into the conduit. For each circuit, count the individual conductors — for example, a single-phase circuit in singles requires a line conductor and a neutral conductor (and a CPC if required). Note the cross-sectional area of each conductor (1.0 mm², 1.5 mm², 2.5 mm², 4 mm², etc.).

2

Look up the cable factor for each conductor

From the cable factor table, find the factor for each conductor size. Common values are: 1.0 mm² = 22, 1.5 mm² = 22, 2.5 mm² = 30, 4 mm² = 43, 6 mm² = 58, 10 mm² = 105, 16 mm² = 145. These factors apply to single-core PVC insulated cables (BS 6004 singles).

3

Calculate the total cable factor

Multiply the cable factor for each size by the number of conductors of that size, then sum all the results. For example, if you have 4 conductors of 2.5 mm² and 2 conductors of 1.5 mm²: total = (4 x 30) + (2 x 22) = 120 + 44 = 164.

4

Determine the conduit factor

Look up the conduit factor for the conduit size you plan to use. Standard conduit factors for straight runs are: 16 mm = 290, 20 mm = 460, 25 mm = 800, 32 mm = 1400, 40 mm = 2100, 50 mm = 3500. If the conduit run includes bends, reduce the factor according to the difficulty — typically 10% per bend or use the reduced factors from the tables.

5

Compare and select the conduit size

If the total cable factor is less than or equal to the conduit factor, the cables will fit. If not, try the next larger conduit size. For the example above (total factor 164), a 16 mm conduit (factor 290) is sufficient. Always leave some spare capacity for future cables if the installation design permits it.

Why Use the Elec-Mate Conduit Fill Calculator?

Purpose-built for UK electricians working to BS 7671. Eliminates guesswork and ensures your conduit is correctly sized every time.

Instant Conduit Size Selection

Enter the number and size of cables, and the calculator recommends the minimum conduit size. Supports 16 mm to 50 mm conduit and all standard cable sizes.

Mixed Cable Sizes

Handles any combination of cable sizes in the same conduit. Add 1.0 mm² through to 16 mm² singles in any quantity…

Bend Adjustment

Specify the number of bends in the conduit run, and the calculator reduces the conduit factor accordingly.

Fill Percentage Display

Shows the fill percentage as a visual gauge. Colour-coded: green for comfortable fill, amber for approaching the limit…

Trunking Fill Mode

Switch between conduit fill (cable factor method) and trunking fill (45% area method). Calculate trunking fill for all standard trunking sizes.

BS 7671 Compliant

All cable factors and conduit factors verified against BS 7671:2018+A4:2026 and the IET On-Site Guide. Values match the published tables.

Conduit Fill Calculator UK: Cable Capacity (BS 7671)

Free conduit fill calculator: check how many cables fit your conduit using the space-factor method. Sizes for PVC and steel conduit to BS 7671.

Try Elec-Mate free
Download on the App StoreGet it on Google Play

Frequently Asked Questions

What is the cable factor method for conduit fill?
The cable factor method is the standard BS 7671 approach for determining whether a given number of cables will fit inside a conduit of a specific size. Each cable size has a "cable factor" — a dimensionless number that represents the relative space the cable occupies. Each conduit size has a "conduit factor" that represents the available space inside the conduit. To check whether the cables fit, you multiply the cable factor for each cable by the number of cables of that size, sum all the results, and compare the total against the conduit factor. If the sum of cable factors is less than or equal to the conduit factor, the cables will fit. If it exceeds the conduit factor, you need a larger conduit.
What is the maximum fill ratio for conduit?
BS 7671 does not state an explicit percentage fill limit for conduit in the same way it does for trunking. Instead, the cable factor method inherently limits the fill to approximately 40% of the internal cross-sectional area of the conduit. This 40% figure accounts for the space needed to physically draw the cables through the conduit without damaging them, the air gaps required for heat dissipation, and the fact that cables do not pack perfectly due to their circular cross-section. The conduit factors published in the tables are calculated on this basis. For trunking, the rule is more explicit: the total cross-sectional area of all cables must not exceed 45% of the internal cross-sectional area of the trunking.
How do bends affect conduit fill calculations?
Bends in a conduit run increase the friction when pulling cables through, making it harder to install them without damage. BS 7671 and the IET On-Site Guide recommend that the conduit factor should be reduced when the run includes bends. A straight run with no bends can use the full conduit factor. For runs with one or two bends (up to 90 degrees each), a reduction of approximately 10 to 15% is recommended. For runs with three or more bends, or runs longer than 10 metres, the conduit factor should be reduced by 20 to 30%, or a draw-in box should be installed to break the run into shorter, straighter sections. The Elec-Mate calculator allows you to specify the number of bends and automatically adjusts the conduit factor accordingly.
What is the difference between conduit fill and trunking fill?
Conduit fill uses the cable factor method — a dimensionless number system where you compare the sum of cable factors against the conduit factor. Trunking fill uses the cross-sectional area method — you calculate the actual cross-sectional area of each cable in square millimetres, sum them, and check that the total does not exceed 45% of the internal cross-sectional area of the trunking. The IET On-Site Guide and Guidance Note 1 recommend a maximum fill of 45% for trunking; BS 7671 itself does not state a percentage fill limit in normative text. For conduit, the approximately 40% limit is built into the cable factor tables. The two methods exist because conduit and trunking have different installation challenges: conduit requires cables to be pulled through a tube (friction is the main constraint), while trunking has a removable lid allowing cables to be laid in (packing density is the main constraint).
Can I mix different cable sizes in the same conduit?
Yes, you can install different cable sizes in the same conduit, and the cable factor method is specifically designed to handle this. Simply add the cable factor for each individual cable (not per circuit — per conductor). For example, if you have three 2.5 mm² singles (cable factor 30 each) and two 1.5 mm² singles (cable factor 22 each), the total cable factor is (3 x 30) + (2 x 22) = 90 + 44 = 134. You then check this against the conduit factor for your chosen conduit size. A 20 mm conduit (straight run) has a conduit factor of 460, so 134 is well within capacity. Remember that grouping correction factors for current-carrying capacity must also be applied when multiple circuits share a conduit.
Why must I apply grouping correction factors when cables share a conduit?
When multiple current-carrying conductors are enclosed together in a conduit, they each generate heat and cannot dissipate it as effectively as a cable installed in free air. This thermal grouping effect reduces the current-carrying capacity of every cable in the conduit. BS 7671 Appendix 4 provides correction factors (Cg) that account for the number of circuits or multi-core cables grouped together. For example, two circuits in a conduit require a grouping factor of 0.80, reducing the rated current capacity to 80% of the single-cable value. Failing to apply the grouping factor means you may select a cable that is undersized for the actual heat conditions inside the conduit, creating a risk of overheating and insulation damage.

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR
7-Day Free Trial — Cancel Anytime, No Hassle

Size Conduit Correctly Every Time

Join 1,000+ UK electricians using Elec-Mate for on-site calculations. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

Cookie Preferences

Manage your privacy settings

We use cookies to enhance your experience and analyse platform usage. Cookie Policy