To illustrate the cable sizing process, consider a common domestic scenario: a ring final circuit supplying socket outlets in a kitchen, protected by a 32A Type B MCB, installed as flat twin and earth cable clipped to joists (Reference Method C), with an ambient temperature of 30 degrees C and no grouping.
Since the ambient temperature is at the reference value (30 degrees C), Ca = 1.0. There is no grouping, so Cg = 1.0. No thermal insulation contact, so Ci = 1.0. The protective device is an MCB, so Cf does not apply. The required tabulated current carrying capacity is It = 32 / (1.0 x 1.0 x 1.0) = 32A. From Table 4D5, column 6 (Reference Method C), a 2.5mm squared cable has Iz = 27A, which is less than 32A. However, for a ring final circuit, the cable is effectively in parallel, so 2.5mm squared is the standard and accepted cable size for a domestic ring final circuit — the ring configuration means each conductor only carries approximately half the total current.
Now consider a more challenging scenario: a 3-phase submain to a workshop 45 metres from the main distribution board, carrying a design current of 80A, installed as SWA cable clipped direct (Method C), at 35 degrees C ambient, with 2 other circuits grouped on the same tray. The correction factors would be Ca = 0.94, Cg = 0.79, giving It = 80 / (0.94 x 0.79) = 107.7A. You would then select from the appropriate SWA table and verify voltage drop over the 45-metre run does not exceed 5%.
The Elec-Mate calculator performs these calculations instantly. Enter the circuit parameters, and the app shows the recommended cable size, the voltage drop as both a value in volts and a percentage, and whether the fault current withstand is acceptable.