BS 7671:2018+A4:2026 Compliant

Cable Sizing Calculator to BS 7671

Size cables correctly to the 18th Edition IET Wiring Regulations. Automatic correction factors, voltage drop calculation, fault current verification, and all Appendix 4 tables built in.

Cable Sizing Calculator

Professional cable sizing with BS 7671 compliance validation

Current Specification

Cable sizing parameters
Installation method (BS 7671)
Selected method
Clipped direct to surface (Method C)
Cable type
Environmental conditions

Standard: 30°C

Affects current rating

Lighting: 3%, Power: 5%

Load characteristics

1.0 = 100% simultaneous load

System parameters

For voltage drop calculation. Typical: 0.8-0.9

Cable selection factors

Cable sizing depends on multiple factors beyond current rating alone:

  • Current-carrying capacity
  • Voltage drop over distance
  • Installation method & ambient temperature
  • Grouping factors when multiple cables run together
  • Short circuit protection requirements

Always consult relevant electrical codes and standards for your specific application.

What Is Cable Sizing and Why Does It Matter?

Cable sizing is the process of selecting the correct cross-sectional area (CSA) of conductor for an electrical circuit. It is one of the most fundamental design decisions in any electrical installation. Get it wrong, and the consequences range from nuisance tripping and poor equipment performance to cable overheating, insulation failure, and fire.

BS 7671:2018 (the IET Wiring Regulations, 18th Edition) sets out the methodology for cable sizing in Section 523, with the current carrying capacity tables in Appendix 4 and the voltage drop data in Appendix 4, Section 6.4. The process involves calculating the design current, selecting a protective device, determining the installation method, applying correction factors for environmental conditions, selecting a cable with sufficient current carrying capacity, and then verifying voltage drop and fault current withstand.

The cable must be large enough to carry the full load current without its temperature exceeding the rated value for its insulation (70 degrees C for thermoplastic/PVC, 90 degrees C for thermosetting/XLPE). It must also limit voltage drop to within the permitted values, and it must be able to survive the thermal effects of a short circuit for the time it takes the protective device to disconnect.

For working electricians, cable sizing calculations are a daily requirement. Whether you are wiring a domestic kitchen circuit, running a submain to an outbuilding, or designing a three-phase distribution board for a commercial fit-out, you need to verify the cable size against BS 7671 before you install it. The Elec-Mate cable sizing calculator does this in seconds, right on your phone. Use it alongside the voltage drop calculator and the cable derating calculator for a complete circuit design check.

The Five Factors in Cable Sizing

BS 7671 requires you to consider five key factors when selecting a cable size. Each factor can independently determine the minimum cable CSA, so all five must be checked. The governing factor (the one that requires the largest cable) determines the final cable size.

1

Design Current (Ib)

The maximum sustained current the circuit will carry in normal service. This is your starting point. For simple resistive loads, Ib = P / V. For motor loads, use the full load current. For discharge lighting, multiply lamp watts by 1.8. The protective device rating (In) must be equal to or greater than Ib.

2

Current Carrying Capacity (Iz)

The cable must have a tabulated current carrying capacity (Iz) that, after correction factors are applied, is at least equal to the protective device rating (In). The required tabulated value is calculated as It = In / (Ca x Cg x Ci x Cf). You then select the smallest cable from the Appendix 4 tables with Iz greater than or equal to It.

3

Voltage Drop

Regulation 525.202 requires that the voltage drop from the origin of the installation to any socket-outlet or fixed equipment terminal does not exceed the values in Appendix 4, Section 6.4. The standard limits are 3% for lighting circuits (6.9V on a 230V supply) and 5% for other circuits (11.5V on a 230V supply). Voltage drop is calculated using the mV/A/m values from Appendix 4, Section 6.4, multiplied by the design current and cable length.

4

Fault Current Withstand

Under short circuit conditions, the cable must be able to withstand the heat generated by the fault current for the duration it takes the protective device to disconnect. This is checked using the adiabatic equation from Regulation 434.5.1 (for live conductors) and 543.1 (for protective conductors): minimum CSA = square root of (I squared t) / k, where I squared t is the energy let-through of the device and k is a constant for the conductor and insulation type (115 for copper/PVC, 143 for copper/XLPE).

5

Earth Fault Loop Impedance

The total earth fault loop impedance (Zs) must be low enough for the protective device to operate within the required disconnection time (0.4 seconds for final circuits, 5 seconds for distribution circuits). A longer cable run increases the circuit impedance, so in some cases you may need to increase the cable size (or the CPC size) to achieve an acceptable Zs value. Note: the tabulated maximum Zs values in BS 7671 assume conductors at maximum operating temperature. On-site measured Zs values (taken at ambient) must be multiplied by the 0.8 factor from GN3 Appendix 3 before comparing to the tabulated limits — an installation signed off without this correction may fail when conductors reach full operating temperature.

Understanding Correction Factors

The tabulated current carrying capacities in Appendix 4 of BS 7671 assume a set of reference conditions: an ambient temperature of 30 degrees C (for cables in air), a single circuit with no grouping, and no thermal insulation in contact with the cable. When real-world conditions differ from these reference conditions, correction factors must be applied.

Ca — Ambient Temperature

If the ambient temperature is above 30 degrees C, the cable can carry less current. Tables 4B1 and 4B2 provide the correction factors. For example, at 40 degrees C with 70 degree C thermoplastic insulation, Ca = 0.87. At 35 degrees C, Ca = 0.94. For installations below 30 degrees C (e.g., underground at 20 degrees C), Ca is greater than 1, slightly increasing the permitted capacity.

Cg — Grouping

When multiple circuits are grouped together (e.g., in trunking, conduit, or on a cable tray), they share heat and each cable can carry less current. Tables 4C1 through 4C5 provide grouping factors based on the number of circuits and the arrangement. For example, 3 circuits in a single layer on a tray gives Cg = 0.79, while 6 circuits in conduit gives Cg = 0.57.

Ci — Thermal Insulation

Cables surrounded by thermal insulation cannot dissipate heat effectively. If a cable is totally surrounded by thermally insulating material for more than 0.5 metres, a derating factor of 0.5 applies (Regulation 523.9). For cables touching insulation on one side, reference method 100 (formerly 101/102) applies, which is built into the table values. The calculator selects the correct approach based on your input.

Cf — Semi-Enclosed Fuse Factor

When the protective device is a BS 3036 semi-enclosed (rewirable) fuse, an additional factor of 0.725 must be applied. This is because rewirable fuses have a fusing factor of approximately 2 (they may not blow until the current reaches twice their rated value), so the cable must be rated higher to allow for this. This factor is not applied for MCBs, RCBOs, or cartridge fuses, which have tighter operating characteristics.

Reference Methods Explained

The way a cable is installed has a significant effect on its ability to dissipate heat, and therefore on its current carrying capacity. BS 7671 Table 4A2 defines a series of reference methods that cover the most common installation arrangements. When you use the cable sizing tables in Appendix 4, you must select the column that corresponds to your reference method.

The most common reference methods encountered in UK domestic and commercial installations are:

  • Method A: Enclosed in conduit in a thermally insulated wall. The most restrictive common method, giving the lowest current carrying capacities.
  • Method B: Enclosed in conduit on a wall, or in trunking on a wall. Slightly better than Method A as heat can escape more easily.
  • Method C: Clipped direct to a surface (e.g., flat twin and earth cable clipped to joists). A common domestic method with good heat dissipation.
  • Method D: Cables in ducts in the ground. Used for underground supply cables, with different ambient temperature assumptions (20 degrees C reference).
  • Methods E/F/G: Free air methods — cable tray (touching), cable tray (spaced), and cable ladder. These give the highest current carrying capacities as the cable can radiate heat freely.
  • Reference Method 100: Enclosed in a building void where thermal insulation is in contact with one side. Increasingly common with modern energy-efficient building standards.

Choosing the wrong reference method is one of the most common cable sizing errors. The Elec-Mate calculator presents the reference methods with clear descriptions and illustrations, so you select the right one every time.

What the Elec-Mate Cable Sizing Calculator Includes

Everything you need to size cables to BS 7671 on your phone or tablet, with no internet connection required.

BS 7671 Tables Built In

All current carrying capacity tables from Appendix 4 and voltage drop data from Appendix 4, Section 6.4 are embedded in the calculator. No need to carry the book.

Automatic Correction Factors

Enter the ambient temperature, grouping arrangement, and insulation conditions. The calculator applies Ca, Cg, Ci, and Cf automatically.

Voltage Drop Calculation

Calculates voltage drop for your route length and design current. Flags results that exceed the 3% lighting or 5% general limit.

Fault Current Check

Verifies the selected cable can withstand the prospective fault current using the adiabatic equation from BS 7671 Regulation 434.5.1.

All Reference Methods

Supports all standard reference methods from Table 4A2 including clipped direct, conduit, trunking, cable tray, and underground ducts.

Multiple Cable Types

Covers thermoplastic (PVC) and thermosetting (XLPE/LSF) cables, singles, flat twin and earth, SWA, and flexible cables.

70 Calculators Included

Cable sizing is just one of 70 electrical calculators. Also includes voltage drop, max demand, diversity, conduit fill, earth rod, and more.

Works Offline

All calculations run locally on your device. Size cables on site with no internet connection. Results sync when you reconnect.

Save and Compare

Save cable sizing calculations and compare different options side by side. Attach results to job records and certificates.

How to Size a Cable to BS 7671

Follow these seven steps to select the correct cable size for any circuit, using the methodology set out in BS 7671:2018. The Elec-Mate calculator handles steps 2 through 7 automatically once you enter the circuit parameters.

1

Determine the design current

Calculate the design current (Ib) of the circuit. For resistive loads, divide the power in watts by the supply voltage (Ib = P/V). For motor loads, use the full load current from the manufacturer. For discharge lighting, multiply the lamp wattage by 1.8 to account for control gear losses and harmonic currents.

2

Select the protective device

Choose a protective device with a nominal rating (In) equal to or greater than the design current. The device must also be appropriate for the type of circuit — for example, a Type B MCB for resistive loads, Type C for motor or transformer inrush, or Type D for very high inrush currents.

3

Identify the installation method

Determine the reference method from BS 7671 Table 4A2 that matches how the cable will be installed. Common methods include Method A (conduit in insulated wall), Method B (conduit on wall), Method C (clipped direct), and Reference Method 100 for thermally insulating material on one side. The method determines which column of the current carrying capacity tables to use.

4

Apply correction factors

Apply all relevant correction factors. Ca for ambient temperature (from Table 4B1/4B2), Cg for grouping (from Table 4C1 to 4C5), Ci for thermal insulation (from Regulation 523.9), and Cf for semi-enclosed fuses (0.725). Calculate the required tabulated current carrying capacity: It = In / (Ca x Cg x Ci x Cf).

5

Select the cable from the tables

Look up the appropriate Appendix 4 table for your cable type (e.g., Table 4D5 for 70 degree C thermoplastic flat cable, or Table 4E2A for 90 degree C thermosetting singles). Find the smallest cable size with a tabulated Iz value equal to or greater than your calculated It value.

6

Check voltage drop

Calculate the voltage drop using the mV/A/m values from Appendix 4, Section 6.4 for your selected cable size and installation method. Multiply by design current and route length, then divide by 1000. Ensure the result does not exceed 3% for lighting or 5% for other circuits, as required by Regulation 525.202. If it exceeds the limit, increase the cable size and re-check.

7

Verify fault current withstand

Confirm the selected cable can withstand the let-through energy of the protective device under fault conditions. The adiabatic equation is: S = square root of (I squared t) / k, where S is the minimum conductor cross-sectional area in mm squared, I squared t is the energy let-through of the protective device, and k is a constant for the conductor and insulation type (from BS 7671 Regulation 434.5.1 for live conductors and Regulation 543.1 for protective conductors). The cable CSA must be at least equal to S.

Practical Cable Sizing Examples

To illustrate the cable sizing process, consider a common domestic scenario: a ring final circuit supplying socket outlets in a kitchen, protected by a 32A Type B MCB, installed as flat twin and earth cable clipped to joists (Reference Method C), with an ambient temperature of 30 degrees C and no grouping.

Since the ambient temperature is at the reference value (30 degrees C), Ca = 1.0. There is no grouping, so Cg = 1.0. No thermal insulation contact, so Ci = 1.0. The protective device is an MCB, so Cf does not apply. The required tabulated current carrying capacity is It = 32 / (1.0 x 1.0 x 1.0) = 32A. From Table 4D5, column 6 (Reference Method C), a 2.5mm squared cable has Iz = 27A, which is less than 32A. However, for a ring final circuit, the cable is effectively in parallel, so 2.5mm squared is the standard and accepted cable size for a domestic ring final circuit — the ring configuration means each conductor only carries approximately half the total current.

Now consider a more challenging scenario: a 3-phase submain to a workshop 45 metres from the main distribution board, carrying a design current of 80A, installed as SWA cable clipped direct (Method C), at 35 degrees C ambient, with 2 other circuits grouped on the same tray. The correction factors would be Ca = 0.94, Cg = 0.79, giving It = 80 / (0.94 x 0.79) = 107.7A. You would then select from the appropriate SWA table and verify voltage drop over the 45-metre run does not exceed 5%.

The Elec-Mate calculator performs these calculations instantly. Enter the circuit parameters, and the app shows the recommended cable size, the voltage drop as both a value in volts and a percentage, and whether the fault current withstand is acceptable.

Cable Sizing Calculator (BS 7671) - Free Online Tool

Free BS 7671 cable sizing calculator: enter load, length and installation method to get the cable size, volt drop and current rating. Works on any phone.

Try Elec-Mate free
Download on the App StoreGet it on Google Play

Frequently Asked Questions About Cable Sizing

What factors affect cable sizing to BS 7671?+
There are five primary factors that determine the minimum cable size for any circuit to BS 7671. First, the design current (Ib) of the circuit — the maximum current the load will draw in normal service. Second, the rating of the protective device (In), which must be equal to or greater than the design current. Third, the current carrying capacity (Iz) of the cable, which must be equal to or greater than the protective device rating after applying correction factors. Fourth, the voltage drop in the cable, which must not exceed the limits set by BS 7671 Regulation 525.202 (typically 3% for lighting circuits and 5% for other circuits, as detailed in Appendix 4, Section 6.4). Fifth, the cable must be able to withstand the let-through energy (I squared t) of the protective device under fault conditions without its insulation being damaged.
What are the BS 7671 correction factors for cable sizing?+
BS 7671 requires several correction factors to be applied to the tabulated current carrying capacity of a cable. Ca is the ambient temperature correction factor — if the ambient temperature is above the reference temperature (30 degrees C for most cable types), the cable can carry less current, so you apply a factor less than 1. Cg is the grouping correction factor — when cables are installed together, they heat each other up, reducing the capacity of each cable. Ci is the thermal insulation correction factor — if a cable passes through or is surrounded by thermal insulation, it cannot dissipate heat effectively. Cf is the semi-enclosed fuse factor (0.725) — applied when the protective device is a BS 3036 semi-enclosed (rewirable) fuse. The effective current carrying capacity required is calculated as It = In / (Ca x Cg x Ci x Cf), and the selected cable must have a tabulated Iz equal to or greater than It.
What reference methods does BS 7671 define for cable installation?+
BS 7671 defines a series of standard reference methods in Table 4A2 that describe how a cable is installed, as this affects its ability to dissipate heat. The main reference methods are: A — enclosed in conduit in a thermally insulated wall; B — enclosed in conduit on a wall or in trunking; C — clipped direct to a surface; D — in ducts in the ground; E — free air (on a cable tray, touching); F — free air (on a cable tray, spaced); G — free air (on a cable ladder, touching). The installation method determines which column of the current carrying capacity tables (Appendix 4) you use. For example, a 2.5mm squared twin and earth cable has a different current carrying capacity when clipped direct (Method C) compared to when it is enclosed in conduit in an insulated wall (Method A).
How do I check voltage drop for a cable to BS 7671?+
BS 7671 Regulation 525.202 requires that the voltage drop between the origin of the installation and any socket-outlet or fixed equipment terminals does not exceed the values stated in Appendix 4, Section 6.4. The mV/A/m values for each cable type and installation method are given in Appendix 4, Section 6.4. To calculate the voltage drop, multiply the mV/A/m value from the tables by the design current (Ib) in amps and the route length (L) in metres, then divide by 1000 to get the result in volts. For a 230V single-phase supply, the maximum voltage drop to the furthest point is typically 3% for lighting (6.9V) and 5% for other uses (11.5V). For three-phase circuits, a 5% limit gives 20V on a 400V supply. If the voltage drop exceeds the limit, you need to increase the cable size until the drop is within tolerance.
What changed in BS 7671 Amendment 4 (2026) that affects cable sizing?+
The 18th Edition Amendment 4:2026 introduced two changes that directly affect protective device selection and, in turn, cable sizing. First, Regulation 411.3.4 now requires that all AC final circuits supplying luminaires within domestic (household) premises are protected by a 30 mA RCD. This affects Zs calculations for those lighting circuits because the required disconnection time is now governed by the RCD rather than the overcurrent device, and the maximum Zs for a 30 mA RCD is 1667 Ω under BS 7671. Second, Regulation 421.1.7 recommends the installation of an Arc Fault Detection Device (AFDD) on AC final circuits to mitigate fire risk from series arcing faults. Where an AFDD is specified, the combined AFDD/RCBO protective device must be co-ordinated with the cable size to ensure discrimination and correct operation. These changes do not alter the fundamental cable sizing methodology in Appendix 4, but they do change which protective devices you are sizing against on domestic lighting and general circuits.
Does the Elec-Mate cable sizing calculator work offline?+
Yes. The Elec-Mate cable sizing calculator is built into the mobile app and works fully offline. All the BS 7671 tabulated data, correction factors, reference methods, and voltage drop values are stored locally on your device. You can size cables on site with no internet connection. Results sync to the cloud when you reconnect, and the calculator can be used alongside the EICR, EIC, and Minor Works certificate forms to cross-check cable sizes against recorded test results.
What is the minimum cable size for a ring final circuit in a UK home?+
A standard domestic ring final circuit protected by a 32A Type B or C MCB (or 30A fuse) requires 2.5mm² copper twin-and-earth cable (6242Y) when clipped direct to a surface. The conductor must have a current-carrying capacity (It) of at least 20A per Regulation 433.1.1 — 2.5mm² copper clipped direct in reference method C gives 27A, which satisfies this requirement with an appropriate grouping factor. If the ring is installed in thermal insulation (for example, in a loft) the cable must be derated using the Ci correction factor. Regulation 523.9 requires that a cable totally surrounded by thermally insulating material over 0.5 m or more is taken as having only 0.5 times the clipped-direct (Method C) current-carrying capacity; for shorter enclosed runs the derating is derived from Appendix 4, Section 2.6. This may require uprating to 4mm². The earth conductor in 6242Y (1.0mm²) is adequate for a 32A circuit when protected by an MCB, verified by the adiabatic equation in BS 7671.

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR
7-Day Free Trial — Cancel Anytime, No Hassle

Stop flipping through cable sizing tables

Join 1,000+ UK electricians using Elec-Mate to size cables in seconds. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy