BS 7671 Section 722 Compliant

Create EV Charger Certificates on Your Phone

The complete EV charger installation certificate app for UK electricians. BS 7671 Section 722 compliance, PME assessment, load management documentation, and digital signatures — all from your mobile device.

Technical content reviewed by Andrew Moore, founder of Elec-Mate and a qualified electrician. Regulations cited from BS 7671:2018+A4:2026 (IET Wiring Regulations).

The short answer: what Section 722 asks of you

The regulation numbers you need on a domestic EV charging point, in one place.

QuestionAnswerRegulation
Which certificate?An Electrical Installation Certificate. A dedicated charging point is a new circuit, so a Minor Works certificate is not an option.644.1, 644.4.201
PME supply, outdoor charging point?The PME earthing facility must not be the means of earthing for the protective conductor contact unless one of methods (b) to (e) is used.722.411.4.1
Additional protection?RCD with a rated residual operating current not exceeding 30mA.415.1.1
DC fault current?Type B RCD, or Type A plus an RDC-DD to BS IEC 62955, where the equipment does not provide it itself.722.531.3.101
PEN conductor in the circuit?Not permitted. A circuit supplying EV charging equipment shall not include a PEN conductor.722.312.2.1
AFDD needed?Not required for circuits supplying EV charging equipment to the BS EN 61851 series incorporating socket-outlets or vehicle connectors to BS EN IEC 62196-2.722.421.1.7.201
Voltage drop limit?5% origin to load point for circuits other than lighting, on a supply taken directly from the public LV network — 11.5V at 230V.Table 4Ab

Section 722 does not apply to charging points that employ inductive charging, or that charge mobility scooters and similar vehicles of 10A and less (Regulation 722.1).

What Is an EV Charger Installation Certificate?

An EV charger installation certificate is the Electrical Installation Certificate required by BS 7671 Section 722 after every dedicated EV charging point installation.

Specifically, it is the EIC produced after installing a dedicated electric vehicle charging point, certifying that the installation has been designed, constructed, inspected, and tested in accordance with BS 7671:2018+A4:2026 (the IET Wiring Regulations), with particular attention to the requirements of Section 722, which deals specifically with circuits intended to supply electric vehicles for charging purposes.

Regulation 644.1 requires the certificate to be issued to the person ordering the work on completion of verification, and Regulation 644.5 requires it to be compiled and authenticated by a skilled person competent to verify that the requirements of BS 7671 have been met. It confirms to the property owner, the Distribution Network Operator (DNO), and any competent person scheme provider that the EV charging installation meets the required safety standards. Without it the installation cannot be signed off through a competent person scheme, and the property owner may struggle to support a grant claim or an insurance question later.

Unlike a standard domestic circuit installation, an EV charger certificate must address several additional considerations specific to Section 722. These include the earthing arrangement assessment (particularly for PME supplies), load management provisions, the type of charging mode, cable sizing for continuous duty at maximum load, and the selection of appropriate protective devices. The certificate must demonstrate that all of these requirements have been properly assessed and met. The underlying Electrical Installation Certificate form is the basis for EV charger certification.

Elec-Mate provides a purpose-built EV charger certificate form that includes all Section 722 requirements as structured checklist items. Rather than trying to remember every regulation, the app guides you through each requirement, validates your test results, and produces a professional PDF certificate ready to issue on site.

BS 7671 Section 722: Requirements for EV Charging Installations

Section 722 of BS 7671:2018+A4:2026 sets out the particular requirements for circuits intended to supply electric vehicles for charging purposes — residential, workplace and public. Regulation 722.1 excludes only two things: charging points that employ inductive charging, and those that charge mobility scooters and similar vehicles of 10A and less.

What changed at A4:2026

The A4 amendment makes significant changes to Regulation 722.411.4.1 concerning the use of a PME supply, and the published change note is blunt about the most important one: the exception concerning reasonably practicable has been deleted. The old escape route of arguing that an alternative method was not reasonably practicable is gone. Changes were also made to the requirements for external influences, RCDs, socket-outlets and connectors. Separately, Regulation 722.311.201 permits load curtailment to be taken into account when determining maximum demand.

Earthing on a PME supply

Regulation 722.411.4.1 addresses the earthing arrangement where the supply is TN-C-S (PME). Because an open PEN conductor fault could place a dangerous potential on the vehicle body via the charging cable, a PME earthing facility shall not be used as the means of earthing for the protective conductor contact of a charging point located outdoors, or one that might reasonably be expected to be used to charge a vehicle located outdoors, unless one of methods (b) to (e) is used. This is the most commonly misunderstood requirement in EV charger installation, and it is set out in full in the next section.

Protective measures not permitted

Two groups of protective measures are ruled out. Regulation 722.410.3.5 prohibits obstacles and placing out of reach (Section 417). Regulation 722.410.3.6 prohibits non-conducting location (Regulation 418.1) and earth-free local equipotential bonding (Regulation 418.2). Where electrical separation is used instead, Regulation 722.413.1.2 limits it to the supply of one electric vehicle from one unearthed source, through a fixed isolating transformer complying with BS EN 61558-2-4.

Circuit design and RCD selection

The circuit must be designed for continuous duty — the cable and protective device must be rated for the full load current drawn continuously. For a standard 7kW domestic charger, this means a 32A circuit with no diversity applied. Under Regulation 722.312.2.1, a circuit supplying charging equipment for electric vehicles shall not include a PEN conductor. Additional protection is provided by an RCD with a rated residual operating current not exceeding 30mA (Regulation 415.1.1), and Regulation 722.531.3.101 governs the selection of the RCD and the detection of DC fault current. Where the charging equipment does not itself provide protection against DC fault current, that means a Type B RCD, or a Type A RCD combined with a residual direct current detecting device (RDC-DD to BS IEC 62955 — defined in Part 2 as detecting and evaluating 6mA DC residual current and switching the monitored circuit). Always check the charger manufacturer installation instructions.

Equipment standards and AFDDs

Regulation 722.511.101 requires EV charging equipment to comply with the appropriate parts of the BS EN 61851 series. AFDDs are not required for circuits supplying EV charging equipment conforming to the BS EN 61851 series that incorporate socket-outlets or vehicle connectors conforming to BS EN IEC 62196-2 (Regulation 722.421.1.7.201).

PME Supplies: The Four Permitted Methods Under Regulation 722.411.4.1

Most domestic properties in the UK are supplied with a TN-C-S (PME) earthing system. Regulation 722.411.4.1 states that a PME earthing facility shall not be used as the means of earthing for the protective conductor contact of a charging point located outdoors, or that might reasonably be expected to be used to charge a vehicle located outdoors, unless one of the listed methods is used. Indent (a) was deleted by BS 7671:2018+A2:2022, leaving four: (b), (c), (d) and (e).

The reason is an open PEN fault. On a PME supply the neutral and earth are combined in the supply cable, and if that PEN conductor is lost the voltage on the installation earth terminal can rise dangerously. The charging cable puts a metallic connection between the installation earth and the vehicle body, so a person touching the vehicle is exposed to that rise. Every one of the four methods is a way of making sure the voltage a person can touch is limited, or removed quickly.

MethodWhat it requires
(a)Deleted by BS 7671:2018+A2:2022.
(b)The main earthing terminal of the installation is connected to an installation earth electrode by a protective conductor complying with Regulation 544.1.1. The electrode resistance to Earth must be such that the voltage between the main earthing terminal and Earth cannot exceed 70V RMS in the event of an open-circuit PEN fault on the low voltage network.
(c)A device that disconnects the vehicle from the live conductors and from protective earth, in accordance with Regulation 543.3.3.101(b), within 5s where the voltage between the circuit protective conductor and Earth exceeds 70V RMS due to an open-circuit PEN fault. It need not operate if the voltage exceeds 70V RMS for less than 4s. It must provide isolation, be selected in accordance with Table 537.4, and be resettable only when the voltage is back below 70V RMS.
(d)The same 5s disconnection, triggered instead by the utilisation voltage at the charging point between line and neutral going above 253V RMS or below 207V RMS. It must provide isolation, be selected in accordance with Table 537.4, and be resettable only within the 207V to 253V band.
(e)An alternative device to (c) or (d) that does not result in a lesser degree of safety, operating by the same disconnection from live conductors and protective earth, providing isolation and selected in accordance with Table 537.4.

Equivalent means of functionality for (c), (d) and (e) may be built into the charging equipment itself, which is how most modern open-PEN-protected wallboxes satisfy the regulation.

Sizing the electrode for method (b)

Method (b) is not a TT conversion. The installation stays on the PME earthing facility; the electrode is added to hold the main earthing terminal below 70V RMS relative to Earth during an open PEN event. The electrode resistance must be measured and recorded.

Annex A722, Item A722.3 gives the formula for the maximum permitted resistance — the sum of the earth electrode resistance and the protective conductor connecting it to the main earthing terminal — and gives separate single-phase and three-phase expressions. Its Note 1 warns that earth electrodes with a resistance above 200Ω may be unstable, and caps the design value at 200Ω where the three-phase formula would give more. Where the protective conductor to the electrode is buried in the ground, its cross-sectional area must be not less than that stated in Table 54.1.

Where a device to method (c), (d) or (e) is used, protective conductors and exposed-conductive-parts downstream of that device must have no connection to the protective conductors or exposed-conductive-parts of any circuit not protected by the same device, and no connection to any extraneous-conductive-part.

“Just rod it and call it TT” is not the compliant answer

Note 3 to Regulation 722.411.4.1 says it plainly: creating a TT earthing system for the charging equipment, or for the whole installation, as an alternative to using the PME earthing facility with one of methods (b) to (e) may not be an appropriate solution, because of the inability to provide sufficient separation from buried metalwork connected to the supply PEN conductor. Pick one of the four methods and record which one you used on the certificate.

Gone at A4:2026

The A4:2026 change note for Section 722 records that the exception concerning reasonably practicable has been deleted from Regulation 722.411.4.1. If your habit was to justify leaving a PME earth in place because an alternative was not reasonably practicable, that justification no longer exists in the regulation.

DNO Notification and Maximum Demand

Before installing an EV charger, the installer must consider the impact on the property's maximum demand and whether notification to the Distribution Network Operator (DNO) is required. A standard 7kW single-phase EV charger draws 32A continuously, which is a significant addition to a typical domestic supply.

Most domestic properties have a supply fuse rated at 60A, 80A, or 100A. If the existing maximum demand of the property (including electric showers, cookers, immersion heaters, and other large loads) plus the 32A EV charger exceeds the supply fuse rating, action is needed. This might involve installing a load management device that limits the charger output when other loads are active, or it might require requesting a supply upgrade from the DNO.

The threshold commonly quoted for prior approval rather than notification is a load of 13.8kVA (about 60A single phase) or above, or where the total demand will exceed the existing supply capacity — but thresholds and process vary by DNO, so check the relevant operator's own guidance rather than relying on a rule of thumb. In practice most DNOs ask to be notified of every EV charge point installation through their online portal, which helps them plan for rising demand across the local network.

Elec-Mate includes a maximum demand calculator within the EV charger certificate. You enter the existing loads on the supply, and the app calculates the total demand including the new charger. If the total exceeds the supply fuse rating, the app prompts you to document the load management solution and record the DNO notification reference number.

Load Management and Smart Charging

Regulation 722.311.201 states that load curtailment, including load reduction or disconnection, either automatically or manually, may be taken into account when determining the maximum demand of the installation or part thereof. That single sentence is what makes documented load management a design solution rather than a workaround: a properly recorded system can legitimately reduce the assessed maximum demand, which is often what avoids a supply upgrade.

In practice, a CT (current transformer) clamp is installed on the supply tails to monitor the total current drawn by the property in real time. The charge point uses that data to adjust its charging rate dynamically, backing off when other loads are active and increasing again when demand falls, so the supply fuse is not asked to carry more than it is rated for when a shower and a charge point run together.

Smart charging goes further than simple load management. Under the Electric Vehicles (Smart Charge Points) Regulations 2021, new domestic and workplace charge points sold in Great Britain must have smart functionality: the ability to be remotely controlled, default off-peak charging times, and a response to signals from the electricity network to help balance supply and demand.

From a certification point of view, all of this needs to be recorded. The certificate should state whether a CT clamp has been installed, the maximum current limit set by the load management device, and the smart charging settings configured during commissioning. Elec-Mate provides dedicated fields for all of it.

EV Charging Modes Explained: Mode 1, Mode 2, and Mode 3

Electric vehicle charging is categorised into modes defined by the BS EN 61851 series, which Regulation 722.511.101 requires EV charging equipment to comply with. For domestic and workplace installations in the UK, the three most relevant are Mode 1, Mode 2, and Mode 3. Section 722 applies to circuits intended to supply electric vehicles for charging purposes regardless of mode — it is not mode-specific, and the only exclusions in Regulation 722.1 are inductive charging and mobility scooters and similar vehicles of 10A and less.

M1

Mode 1

Charging from a standard 13A domestic socket-outlet. No communication between the charger and the vehicle, and no in-cable protection. Limited to roughly 3kW. Not recommended for regular use in the UK because of the risk of overheating a general purpose socket-outlet under a prolonged continuous load.

M2

Mode 2

Charging using a portable cable with an in-cable control and protection device (IC-CPD). Typically supplied with the vehicle as an emergency/occasional charger. Plugs into a standard or industrial socket. The IC-CPD provides basic communication and protection. Limited to approximately 3kW from a 13A socket.

M3

Mode 3

Charging using a permanently installed dedicated charging station (wallbox) with a Type 1 or Type 2 connector. Full communication between the charger and vehicle via the control pilot signal. Typically 7kW single-phase (32A) or 22kW three-phase. This is the standard for domestic and workplace installations and is what Section 722 primarily addresses.

Dedicated Circuit Requirements: Protection and Cable Sizing

Every Mode 3 EV charger must be supplied by its own dedicated circuit from the distribution board. The circuit must be designed for continuous duty at the full rated current of the charger. For a standard 7kW domestic charger, this means a 32A circuit with no diversity applied — the cable, protective device, and all connections must be rated for 32A drawn continuously for extended periods.

The protective device should be a 32A Type A RCBO for most domestic installations. The Type A characteristic provides protection against both AC and pulsating DC fault currents, which is appropriate for Mode 3 chargers with built-in DC residual current detection. If the charger does not include DC detection, a Type B RCBO may be required — always check the manufacturer instructions.

Cable sizing for a 32A continuous load requires careful consideration of all correction factors. A common starting point for a typical domestic installation is 6mm² thermoplastic twin-and-earth clipped direct. That is a starting point only: it assumes favourable conditions — an ambient temperature no higher than the 30°C the tabulated ratings are based on, no grouping with other cables, no thermal insulation, and a length short enough to stay inside the voltage drop limit. Select from the tabulated rating for the actual reference method and apply the Appendix 4 correction factors; never apply an installation-method multiplier on top of a rating that already accounts for the method.

For longer cable runs — common when the charger is mounted on an external wall or in a detached garage — a larger conductor may be required to meet the voltage drop requirement. For external underground runs, SWA (steel wire armoured) cable is typically used and must be buried at the correct depth as specified by the installation design. The SWA armour can be used as the circuit protective conductor (CPC) but must be properly terminated with gland plates and earth tags. The table below gives indicative starting points; always calculate each circuit for its actual conditions.

Typical 7kW EV Charger Circuit Specification

  • Protective device: 32A Type A RCBO, 30mA rated residual operating current
  • Cable: 6mm² minimum (PVC/PVC twin-and-earth clipped direct), 10mm² for longer runs, or 4mm² SWA depending on installation method and length
  • Voltage drop: 5% from the origin of the installation to the charging point — 11.5V on a 230V nominal supply (Table 4Ab)
  • Earthing on PME: one of methods (b) to (e) of Regulation 722.411.4.1, recorded on the certificate
  • Conductor arrangement: no PEN conductor in the circuit supplying the charging equipment (Regulation 722.312.2.1)

Choosing the RCD: DC Fault Current Protection (Regulation 722.531.3.101)

ScenarioAcceptable protection
Charger does not provide its own DC fault current protectionType B RCD, or Type A RCD plus a residual direct current detecting device (RDC-DD to BS IEC 62955) that disconnects at 6mA DC and above
Charger has built-in RDC-DD (6mA DC detection)Type A RCD upstream, with the charger's integral RDC-DD handling smooth DC residual current
Additional protection (all scenarios)RCD with a rated residual operating current not exceeding 30mA (Regulation 415.1.1)

A plain Type AC RCD is not suitable for an EV charging circuit, and BS 7671 notes that a Type AC RCD should not be fitted upstream of a Type A, Type F or Type B device. Always confirm the protection arrangement against the charger manufacturer's installation instructions and BS 7671 Section 722.

Cable Sizing Guidance for a 32A (7kW) Charging Circuit

Indicative starting points only — the conductor must always be sized for the actual reference method, ambient temperature, grouping and run length, then verified against the voltage-drop limit. Calculate every circuit individually.

ScenarioTypical cableNote
Short run, clipped direct (PVC twin & earth)6mm²Assumes favourable conditions and a short length
Longer run or warmer/grouped conditions10mm²Often needed to stay within the voltage-drop limit
External / underground run to garage or outbuildingSWA (e.g. 4–10mm²)Buried at correct depth; armour may serve as the CPC if correctly terminated

Design current

32A drawn continuously — no diversity applied to a single dedicated EV charging circuit.

Voltage drop

5% between the origin of the installation and any load point, for circuits other than lighting on a low voltage installation supplied directly from a public LV distribution system — 11.5V at 230V nominal (Appendix 4, Table 4Ab).

Government Grant Schemes and Documentation Requirements

The UK government has offered various grant schemes to support the uptake of electric vehicles, including grants towards the cost of installing domestic and workplace EV charge points. The Office for Zero Emission Vehicles (OZEV) has administered these, including the Electric Vehicle Homecharge Scheme and the Workplace Charging Scheme. Scheme names, values and eligibility change, so confirm the current position on GOV.UK before you quote — but the documentation requirements have stayed broadly the same.

To claim a grant, installers typically need to submit the completed Electrical Installation Certificate, photographs of the installed charger, evidence of the DNO notification, and confirmation that the installation meets all Building Regulations and BS 7671 requirements. The certificate must demonstrate compliance with Section 722, including the earthing assessment and load management provisions. Incomplete or incorrect documentation is one of the most common reasons for grant claims being rejected.

Elec-Mate streamlines this process by producing a certificate that includes all the documentation typically required for grant submissions. The Section 722 checklist, PME assessment, load management details, and test results are all structured in the format that scheme providers and grant bodies expect, reducing the risk of rejection due to missing information.

EV Charger Certificate Features

Elec-Mate provides everything you need to produce professional, compliant EV charger installation certificates on your phone.

Section 722 Compliant

Every EV charger certificate carries the BS 7671 Section 722 checklist: PME assessment, earthing method, RCD type and equipment standards.

PME Assessment Built In

The PME section walks you through methods (b) to (e) of Regulation 722.411.4.1, records which one you used, and captures the electrode resistance where it applies.

Maximum Demand Calculator

Total the existing loads plus the new charge point. The app flags when demand exceeds the supply fuse rating and prompts you to record the load curtailment arrangement.

Complete on Your Phone

Fill out the whole certificate on site from a phone or tablet. Works offline, saves as you go, and syncs when you have signal again.

Digital Signatures

Capture installer and client signatures directly on-screen. No printing or scanning required.

PDF Export for Grant Claims

Export a professional PDF for scheme providers and grant submissions, with the Section 722 documentation, test results and signatures in one file. Regulation 644.4.202 permits certificates in electronic form.

How to Create an EV Charger Certificate Using Elec-Mate

Follow these steps to complete a BS 7671 Section 722 compliant EV charger installation certificate using the Elec-Mate app.

1

Assess the supply and earthing

Before starting, assess the existing supply characteristics. Record the earthing arrangement (TN-C-S, TN-S, or TT), the supply fuse rating, and the current maximum demand. If the supply is PME (TN-C-S) and the charging point is outdoors, or might reasonably be expected to charge a vehicle outdoors, decide which of methods (b) to (e) of Regulation 722.411.4.1 you will use and record it.

2

Open a new EV charger certificate

Launch Elec-Mate and select "New EV Charger Certificate" from the certificates section. The app creates an Electrical Installation Certificate pre-configured with the Section 722 requirements, PME assessment checklist, and load management fields already included.

3

Complete the PME assessment

Work through the PME assessment checklist in the app. This covers the earthing arrangement evaluation, the Regulation 722.411.4.1 method selected, earth electrode details and measured resistance where method (b) is used, protective conductor sizing, and RCD selection. The app validates your entries against the Section 722 requirements.

4

Enter circuit details and test results

Record the circuit details including cable type, size, length, and installation method. Enter all test results: continuity of protective conductors (R1+R2), insulation resistance, polarity, earth fault loop impedance (Zs), prospective fault current, and RCD operation. The app checks values against BS 7671 limits and prompts you for the recommended interval to the first periodic inspection, which Regulation 644.4 requires to be recorded on the certificate.

5

Document load management

If a load management device (CT clamp, dynamic load balancing) is installed, record the details in the dedicated section. Note the maximum demand assessment, any supply limitations agreed with the DNO, and the smart charging configuration. This documentation is essential for grant claims.

6

Sign, export, and submit

Capture your digital signature and the client signature on-screen. Export the completed certificate as a professional PDF. The certificate includes all Section 722 documentation, test results, and the load management assessment in one document ready for the client, scheme provider, or grant claim submission.

In the app

Create EV Charger Certificates on Your Phone

BS 7671 Section 722 compliant EV charger installation certificates, with the PME assessment, load management record and test results in one export.

Frequently Asked Questions About EV Charger Certificates

Do I need a separate certificate for every EV charger installation?
A dedicated EV charging point is a new circuit, and Regulation 644.4.201 only allows a Minor Electrical Installation Works Certificate where the work does not include the provision of a new circuit. So an Electrical Installation Certificate is required, issued to the person ordering the work under Regulation 644.1. It does not have to be a standalone document — if you are carrying out other work at the same property, the EV circuit can sit on the same EIC, provided the Section 722 requirements are specifically addressed and the circuit details and test results are recorded. Regulation 644.4.202 confirms certificates may be produced in written or electronic form, so long as their authenticity and integrity can be verified. Elec-Mate pre-populates the Section 722 checklist items so nothing is missed.
What earthing arrangement is required for an EV charger on a PME supply?
Under Regulation 722.411.4.1, a PME earthing facility shall not be used as the means of earthing for the protective conductor contact of a charging point located outdoors, or one that might reasonably be expected to be used to charge a vehicle located outdoors, unless one of methods (b) to (e) is used. Method (b) connects the installation main earthing terminal to an installation earth electrode through a protective conductor complying with Regulation 544.1.1, sized so that the voltage between the main earthing terminal and Earth cannot exceed 70V RMS during an open-circuit PEN fault. Methods (c), (d) and (e) instead use a device that disconnects the vehicle from the live conductors and from protective earth within 5 seconds — on CPC-to-Earth voltage above 70V RMS for (c), or on the line-to-neutral utilisation voltage leaving the 207V to 253V band for (d). Note 3 to the regulation warns that simply creating a TT earthing system for the charging equipment, or the whole installation, may not be an appropriate alternative because sufficient separation from buried metalwork connected to the supply PEN conductor cannot always be achieved. Elec-Mate includes a PME assessment checklist that walks you through this requirement step by step.
What is the minimum cable size for a 32A EV charger circuit?
The minimum cable size depends on the installation method, cable type, ambient temperature, grouping and circuit length. For a typical domestic installation using thermoplastic (PVC) twin-and-earth cable clipped direct, 6mm² is a common starting point for a 32A circuit — but it is a starting point, not an answer. You must select the conductor for the actual reference method and correction factors, then check voltage drop. Table 4Ab of BS 7671 sets the voltage drop between the origin of the installation and any load point at 5% for circuits other than lighting on a low voltage installation supplied directly from a public low voltage distribution system, which is 11.5V on a 230V nominal supply. For longer runs, 10mm² may be required. For an external run to a garage or outbuilding, SWA is typically used and the size again depends on installation method and derating. Always calculate using the specific conditions of the installation.
Do I need to notify the DNO before installing an EV charger?
Yes, in most cases. Under the Electricity Safety, Quality and Continuity Regulations (ESQCR) 2002, you must notify your Distribution Network Operator (DNO) before connecting any load that could significantly affect the supply. A 7kW single-phase EV charger draws 32A, which is a substantial addition to a domestic property. Most DNOs require notification via their online portal. Additionally, if the total maximum demand of the property (including the new EV charger) exceeds the rated capacity of the supply fuse (typically 60A or 80A for a domestic property), load management or a supply upgrade may be required. Elec-Mate includes a maximum demand calculator to help you assess this before installation.
What type of RCD and circuit breaker is required for an EV charger?
Additional protection is provided by an RCD with a rated residual operating current not exceeding 30mA (Regulation 415.1.1), and Regulation 722.531.3.101 governs the type of RCD and the handling of DC fault currents. Where the charging equipment does not itself provide protection against DC fault current, a Type B RCD must be used, or a Type A RCD combined with a residual direct current detecting device (RDC-DD to BS IEC 62955, defined in Part 2 as detecting and evaluating 6mA DC residual current and switching the monitored circuit). For a standard 7kW domestic charger the protective device is typically rated at 32A; a 32A Type A RCBO with an integral or upstream RDC-DD is a common solution. Always check the charger manufacturer installation manual for specific protection requirements.
Is a grant available to help with the cost of EV charger installation?
Government support for domestic and workplace charge points has run through several schemes administered by the Office for Zero Emission Vehicles (OZEV), including the Electric Vehicle Homecharge Scheme and the Workplace Charging Scheme. Eligibility, grant values and the schemes themselves change, so check the current position on GOV.UK before quoting a figure to a customer — this page deliberately does not print a grant amount that may since have moved. What does not change is the documentation: grant claims are made by an authorised installer, generally before the work, and are supported by the Electrical Installation Certificate, photographs of the installed equipment, and evidence of the DNO notification. Elec-Mate's EV charger certificate produces that documentation in one export.

7-day free trial

Stop struggling with EV charger paperwork

Join 1,600+ UK electricians creating professional Section 722 compliant certificates. 7-day free trial, cancel anytime.

Start your free trial

From £6.99/mo after the trial — no charge until day 8.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in one tap — no calls, no hassle
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play
Certificate types
19Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists

1,600+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy