Residual current devices (RCDs) operate on a fundamentally different principle from overcurrent devices. An RCD detects an imbalance between the current flowing in the line conductor and the current returning through the neutral. When some current leaks to earth through a fault (or through a person), the RCD senses the difference and disconnects the supply — typically within 30 to 40 milliseconds for a 30 mA device.
Because the RCD operates on differential current rather than magnitude of fault current, it does not require a high fault current to trip. The maximum earth fault loop impedance for an RCD-protected circuit is calculated from the formula:
Zs = 50 / Idelta n
50 = maximum touch voltage in volts (from BS 7671 Regulation 411.3.2.1)
Idelta n = rated residual operating current of the RCD in amperes
For a 30 mA (0.03 A) RCD: Zs = 50 / 0.03 = 1667 ohms. For a 100 mA (0.10 A) RCD: Zs = 50 / 0.10 = 500 ohms. For a 300 mA (0.30 A) RCD: Zs = 50 / 0.30 = 167 ohms.
The 1667 ohm limit for 30 mA RCDs is so generous that virtually any circuit within a building will meet it. This is why RCD protection is so valuable on TT installations (where Ze can be very high due to the earth electrode resistance) and as a solution for circuits where the Zs is too high for the OCPD alone to disconnect within time.
However, it is important to note that even on RCD-protected circuits, you should still verify that the overcurrent protective device can disconnect a line-to-earth fault. If the RCD fails (sticks), the OCPD is the backup. BS 7671 recommends (but does not require for all cases) that the Zs still permits the OCPD to operate within 5 seconds as a secondary measure. The Elec-Mate calculator checks both the RCD limit and the OCPD limit, flagging any discrepancies.
TT Systems — Earth Electrode Resistance (Ra)
On TT installations, the return path from the installation earth back to the supply transformer is through the general mass of earth rather than a metallic conductor. The resistance of this path — the earth electrode resistance, Ra — can be 20 ohms or more, making Zs far too high for any overcurrent protective device to clear a fault within the required disconnection time. This is why BS 7671 Regulation 411.5 requires TT installations to use RCD protection: Regulation 411.6.5(b) states that the condition Ra × I ≤ 50 V must be satisfied (where Ra is the sum of the resistances of the earth electrode and the protective conductor, and I is the current causing automatic disconnection). Because RCDs operate on differential current rather than fault-current magnitude, even a very high Ra will not prevent disconnection — the 1667 ohm limit for a 30 mA RCD easily encompasses any practical TT Ze value.
Ra is measured on site using a proprietary earth electrode resistance tester (or the 3-terminal fall-of-potential method). BS 7671 Regulation 643.7.3 requires that where the earthing system incorporates an earth electrode, the electrode resistance to earth (Ra) shall be measured and recorded. Typical TT Ze values obtained from the distributor or measured on site should be used for design verification; on-site measurement is required if the distributed value is unavailable or suspect (OSG Reg 1.3).