A residual current device compares the current flowing out along the line conductor with the current returning along the neutral. If they differ, current is escaping somewhere it should not — through a damaged cable, a wet connection, or a person — and the RCD disconnects. A 30 mA device is the rating BS 7671 recognises for additional protection against electric shock. Under Reg 643.8, a general non-delay RCD is deemed effective where it disconnects within 300 ms on an alternating current test at its rated residual operating current.
What Regulation 411.3.3 actually requires
Amendment 4 redrafted Reg 411.3.3 into three indents. In AC systems, additional protection by an RCD rated not more than 30 mA shall be provided for:
| Indent | Applies to | Risk-assessment exception? |
|---|
| 411.3.3(a) | Socket-outlets rated up to 32 A in locations where they are liable to be used by ordinary persons (BA1) or children (BA2) | No |
| 411.3.3(b) | Socket-outlets rated up to 32 A in other locations | Yes — only on a suitably documented risk assessment undertaken with the involvement of a skilled person (electrically), supplied with the certificate |
| 411.3.3(c) | Mobile equipment rated up to 32 A for use outdoors — power tools, mowers, hedge trimmers | No |
Two things follow. A home is a location liable to be used by ordinary persons and children, so indent (a) applies and there is no exception to fall back on. And anything portable you take outside falls under indent (c) in its own right — so a mower or a drill used in the garden needs 30 mA RCD protection whether or not the socket it is fed from happens to have it.
That protection can come from the RCD or RCBO in the consumer unit, from an RCD built into the lead, or from a plug-in RCD adaptor that sits between the plug and the socket. All three work; the point is that one of them is present.
Why an RCD lead trips constantly
Persistent tripping is normally leakage, not a defective device. Every healthy appliance leaks a small current to earth, and Reg 531.3.2(c) expects the accumulated protective conductor and earth leakage currents downstream of an RCD to be no more than 30% of its rated residual operating current — 9 mA on a 30 mA RCD. Put several tools, a jet washer and a site radio on one lead and they can pass that between them with nothing actually faulty.
- Split the load. Reg 531.3.2(a) and (b), and Reg 314.1(d), address exactly this: subdivide circuits so that normal leakage does not trip the device. Practically, run high-leakage tools off their own lead rather than ganging everything onto one.
- Dry the connections. Water in a plug, a socket or a nicked cable is a leakage path. Damp is the single most common cause of an outdoor lead tripping in the rain.
- Find the appliance. Unplug everything, reset, then add items back one at a time. The one that trips it is the one to have looked at.
- Never work around it. Do not fit a higher-rated RCD, bypass the device or hold the test button. A device that keeps operating is reporting something.