A complete practical guide to fused connection units (FCUs): types, correct fuse ratings, when to use a spur instead of a socket, BS 7671 requirements, and step-by-step wiring instructions.
Run a 2.5 mm² twin-and-earth spur from a socket on the ring final circuit (or a junction box in the ring cable) to the supply/IN terminals of the FCU. Connect the appliance flex — line, neutral and green/yellow earth — to the load/OUT terminals. Fit a BS 1362 cartridge fuse rated to the appliance flex (3 A, 5 A or 13 A), not 13 A by default. Then test polarity, earth continuity and insulation resistance before energising.
A switched FCU gives local double-pole isolation of all live conductors (Regulation 462.2). Where the spur supplies socket-outlets up to 32 A, the circuit needs 30 mA RCD protection (Regulation 411.3.3).
1,000+
UK electricians
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer — DP Electrical
Key Takeaways
1A fused connection unit (FCU) is a fused spur outlet that provides a permanent, non-socket connection to a fixed appliance. It contains a cartridge fuse (typically 3A, 5A, or 13A) and can be switched or unswitched, with or without a flex outlet and indicator neon.
2FCUs are required where an appliance needs a permanent connection that cannot be unplugged — for example a dishwasher, washing machine, extractor fan, or immersion heater. They must not be positioned so the appliance blocks access for switching off.
3The fuse rating inside the FCU must match the rating of the appliance flex, not the ring main. A 3A fuse is appropriate for lighting loads and appliances up to 720W. A 5A fuse suits appliances up to 1,150W. A 13A fuse suits loads up to 3,000W.
4Under BS 7671 Regulation 462.2, every circuit must be provided with a means of isolation of all live conductors. A switched FCU (double-pole) provides local isolation of both line and neutral plus overcurrent protection for the appliance flex in a single unit.
5A spur from a ring final circuit must be taken from a socket-outlet on the ring, or from a junction box connected into the ring cable — not from another spur. Per Appendix 15, an unfused spur should feed only one single or one twin socket-outlet.
01 · Wiring Guide
What is a Fused Connection Unit (FCU)?
A fused connection unit (FCU) — commonly called a fused spur — is a wiring accessory that provides a permanent, fused connection to a fixed electrical appliance. Unlike a standard socket outlet, the FCU does not have a removable plug — the appliance is hardwired to the load side of the FCU or connected via a short flex to a flex outlet plate on the FCU face.
The FCU contains a cartridge fuse (BS 1362 type, identical to those used in 13A plugs) sized to protect the appliance flex rather than the circuit cable. This means the fuse provides an additional level of overcurrent protection downstream of the ring main protection — protecting the flex and the appliance rather than the supply cable.
FCU vs fused spur outlet — these terms are often used interchangeably. Strictly, an FCU is the wiring accessory (the plate with terminals), while a fused spur describes the circuit arrangement (spur from a ring main via a fuse). Both terms refer to the same physical accessory in common usage.
Not a replacement for a socket outlet — an FCU is for permanently connected appliances only. If the appliance will occasionally be moved or requires a removable connection, a standard 13A socket is more appropriate.
Free download
Get the BS 7671 A4:2026 Cheat Sheet — free
Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.
Every regulation change summarised
New model forms (EIC + MEIWC)
Free PDF — no subscription
02 · Wiring Guide
Types of Fused Connection Unit
FCUs are available in several configurations. Choosing the right type for the application is important for compliance, safety, and usability.
Switched FCU
Incorporates a double-pole rocker switch that disconnects both line and neutral simultaneously, giving a local means of isolation (Regulation 462.2). The default choice for dishwashers, washing machines, extractor fans, heated towel rails and most kitchen appliances.
Unswitched FCU
Fuse only, no switch. Used where the appliance has its own integral switch or where isolation is provided by a separate DP switch. Less common in practice since switched FCUs cost little more.
FCU with neon indicator
Includes an LED or neon lamp that illuminates when the switch is on. Useful for appliances in concealed positions where it matters that you can see the supply is live (e.g. immersion heater, frost-protection heater).
FCU with flex outlet
Has a small aperture in the face plate through which the appliance flex emerges, connected to the load terminals inside the back box. Common for cooker-hood extractors and where the flex routing is tight.
20 A DP switch / connection unit
For higher-current fixed loads such as immersion heaters and some fixed heaters. Not a standard FCU — it has no cartridge fuse — but a double-pole switch for fixed equipment. Circuit protection is provided by the MCB at the consumer unit, so the load is run as its own dedicated radial rather than a spur.
03 · Wiring Guide
When to Use a Fused Spur Instead of a Socket
The decision between a socket outlet and an FCU is not always obvious. These are the situations where an FCU is the appropriate choice:
Built-in dishwashers & washing machines
Not moved in normal use. An FCU inside the adjacent cupboard gives an accessible isolation point without pulling the appliance out to reach a socket. A 13 A fuse matches the appliance flex rating.
Extractor fans (kitchen & bathroom)
Wired as a 3 A or 5 A fused spur from the lighting circuit or ring final circuit. The FCU protects the fan flex and provides isolation without going to the consumer unit.
Fixed electric heaters & towel rails
Panel heaters and heated towel rails installed as fixed equipment need a means of isolation. A switched FCU provides local double-pole isolation plus flex protection.
Outdoor socket spurs
Where a weatherproof garden socket is spurred from an indoor ring final circuit, an FCU gives the fused connection point. The garden socket (IP44 minimum) connects as the load and must have 30 mA RCD protection.
Underfloor heating thermostats
Electric underfloor heating mats are commonly fed via a 13 A FCU spurred from the ring final circuit, with the thermostat wired between the FCU and the heating mat. See the for related circuit and RCD considerations.
04 · Wiring Guide
Correct Fuse Ratings for FCUs
One of the most common mistakes with FCUs is fitting the wrong fuse rating. The fuse in an FCU protects the appliance flex — it should be rated as close as possible to (but above) the rated current of the appliance, not automatically set to 13A because that is the maximum.
BS 1362 Fuse Rating Quick Reference
Approximate wattage limits at 230 V. Always confirm against the appliance rating plate — the fuse protects the flex, not the ring.
Larger fans with integral lighting, small fridges, low-wattage panel heaters
13 A (brown)
up to 3,000 W
Dishwashers, washing machines, tumble dryers, electric heaters, microwave ovens
Always check the rating plate — do not assume a 13A fuse is correct for all appliances. A kitchen extractor fan with a 13A fuse has effectively no overcurrent protection for its flex (a 1A motor on a 13A fuse means the fuse will not operate until the current is 13 times higher than normal — well above the point at which the flex would be damaged).
Try Elec-Mate free for 7 days
16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.
Fused connection units are covered by BS 7671:2018+A4:2026 and the relevant British Standard for the accessory itself (BS 1363-4 for FCUs to BS 1363). Key regulatory requirements include:
Regulation
Requirement and what it means for an FCU
462.2
Every circuit must be provided with isolation means for all live conductors. The double-pole switch of a switched FCU disconnects both line and neutral, providing local isolation adjacent to the appliance.
464.1
Means for switching off must be provided where mechanical maintenance may involve a risk of physical injury — relevant for fans, pumps and motorised appliances. A switched FCU provides this off-switch with disconnection of all live conductors.
411.3.3
Socket-outlets rated up to 32 A require 30 mA RCD additional protection (subject to the permitted exceptions). An FCU spur taken from a ring final circuit must be RCD-protected at the consumer unit or by an inline 30 mA RCD.
433.1.204
Ring final circuit rule: accessories to BS 1363 may be supplied through a ring final circuit (with or without unfused spurs) protected by a 30 A or 32 A device, wired in copper with line and neutral of at least 2.5 mm² (1.5 mm² for two-core MICC).
App 15
Ring and radial arrangements (informative). An unfused spur should feed only one single or one twin socket-outlet; the number of socket-outlets fed from an FCU depends on the load, having taken diversity into account.
514.4.2
The green-and-yellow combination is used exclusively for protective conductors. Earth cores must be sleeved green/yellow at terminations; old red/black cable reused in a modification must have line and neutral re-identified with brown and blue.
See the for common FCU-related C2 findings that arise during inspection.
06 · Wiring Guide
For Electricians — Certifying FCU Work
Adding an FCU as a spur from an existing ring main requires a Minor Works Certificate. If new cabling is installed that creates a new circuit, an Electrical Installation Certificate is required. Use Elec-Mate to generate compliant certificates on-site.
— record any existing installation deficiencies found during the work.
How to Wire a Fused Spur — Step by Step
Follow these steps to install a switched fused connection unit as a spur from a ring main circuit.
1
Identify the correct spur point on the ring main
Switch off the circuit at the consumer unit and prove dead with an approved voltage indicator. Identify a suitable socket on the ring main (confirm it is on the ring, not already a spur) or install a 30A junction box in the ring cable at a convenient point. Do not use a non-standard junction — use a properly enclosed JB.
2
Run the spur cable
Use 2.5mm² twin and earth cable for standard FCU spurs. Route concealed cable in accordance with BS 7671 Section 522 and Table 52.1 — within a prescribed zone (within 150mm of the top of the wall or of an angle between walls, or running horizontally/vertically from the accessory), or provide additional protection by a 30mA RCD, or use a cable with an earthed metallic covering. Leave sufficient tail length at each end.
3
Connect the supply side of the FCU
At the spur origin (socket or junction box), connect the spur cable using the appropriate terminals. At the FCU back box, connect line (brown) to the "Line In" or "Supply L" terminal, neutral (blue) to "Neutral In" or "Supply N", and earth (green/yellow) to the earth terminal. Ensure cores are sleeved correctly — earth in green/yellow.
4
Connect the load side of the FCU
Connect the appliance flex or a short length of flex (for a flex outlet plate) to the "Load" or "Out" terminals: line to "Load L", neutral to "Load N", earth to the earth terminal or the metal earth clip. Verify that the flex current rating is adequate for the appliance load.
5
Fit the correct fuse
Insert the correct BS 1362 cartridge fuse in the FCU fuse carrier: 3A (red) for loads up to 720W, 5A for loads up to 1,150W, 13A for loads up to 3,000W. Confirm the fuse rating against the appliance rating plate. Replace the fuse carrier and secure the FCU face plate.
6
Test and certify
With the circuit off, test insulation resistance between line/neutral/earth, verify polarity, and measure earth continuity from the FCU earth terminal back to the main earth terminal. Reconnect the circuit and verify correct operation of the switched FCU and the appliance. Issue a Minor Works Certificate (or EIC if the circuit is new) using the Elec-Mate app.
Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.
Fantastic app for electricians
I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.
Absolutely amazing
I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.
Trusted by electricians across the UK
Real feedback from real sparks
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer
Sole Trader · DP Electrical
“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”
Nathan Perry
Electrician · NP Electrical Services
“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”
Jake Pizey
3rd Year Apprentice · Apprentice
7-Day Free Trial — Cancel Anytime, No Hassle
Issue Minor Works Certificates instantly
Generate compliant MWCs and EICs for FCU installations on your phone with Elec-Mate.
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer, DP Electrical
From £6.99/mo after trial — less than a coffee a week
or download the app
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents
1,000+ electricians · From £6.99/mo after trial
We use cookies to improve the app and measure what works. Cookie Policy