BS 7671 HUB

BS 7671: 18th Edition Wiring Regulations Guide

The complete guide to BS 7671:2018+A4:2026 — the 18th Edition of the IET Wiring Regulations. Every part of the standard explained, what each of the four amendments actually changed, and the A4:2026 additions: Chapter 57 for stationary secondary batteries, Section 716 for Power over Ethernet, Section 545 for ICT functional earthing, Chapter 81 for energy efficiency, and the redrafted Regulation 551.7.1 for bidirectional energy flow.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,600+ UK electricians

18 min readUpdated 2026-08-07Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

The short answer

What is the current version of BS 7671?

BS 7671:2018+A4:2026 — the 18th Edition of the IET Wiring Regulations as amended by A1:2020, A2:2022, A3:2024 and A4:2026. Amendment 4 was issued on 15 April 2026 and may be implemented immediately; the previous version is withdrawn on 15 October 2026. BS 7671 is not statutory in itself, but compliance is the accepted way to satisfy the Electricity at Work Regulations 1989 and Part P of the Building Regulations.

1,600+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5

Key takeaways

  1. 01The current standard is BS 7671:2018+A4:2026. Amendment 4 was issued on 15 April 2026 and may be implemented immediately; the previous version (A2:2022 + Corrigendum May 2023 + A3:2024) is withdrawn on 15 October 2026.
  2. 02The 18th Edition has had four amendments: A1:2020 (February 2020, electronic), A2:2022 (March 2022, brown cover), A3:2024 (31 July 2024, electronic) and A4:2026 (April 2026, orange cover). The 31 July 2024 date belongs to Amendment 3, not Amendment 4.
  3. 03Amendment 4 adds a new Chapter 57 (stationary secondary batteries), a new Section 716 (Power over Ethernet), a new Section 545 (functional earthing for ICT), and a new Chapter 81 (energy efficiency, replacing the deleted Appendix 17). It also redrafts Regulation 551.7.1 for bidirectional energy flow.
  4. 04AFDDs are not simply "recommended". Regulation 421.1.7 says AFDDs shall be provided for single-phase AC final circuits supplying socket-outlets rated up to 32 A in high rise residential buildings, HMOs, purpose-built student accommodation and care homes. For all other premises they are recommended.
  5. 05Regulation 411.3.4 has required a 30 mA RCD on AC final circuits supplying luminaires in domestic (household) premises since the 18th Edition was published in 2018 — it is not a new A4:2026 rule.
  6. 06Elec-Mate has every BS 7671 regulation built into the app — tap any certificate field to see the relevant clause, with 70+ calculators based on BS 7671 tables.

01 · BS 7671 Hub

What Is BS 7671?

BS 7671 is the British Standard that sets out the requirements for the design, erection, and verification of electrical installations in the United Kingdom. Published jointly by the British Standards Institution (BSI) and the Institution of Engineering and Technology (IET), it is the single most important document for every working electrician in the UK. The current version is BS 7671:2018+A4:2026 — the 18th Edition, as amended by A1:2020, A2:2022, A3:2024 and A4:2026.

BS 7671 at a glance
QuestionAnswer
Current versionBS 7671:2018+A4:2026
Amendment 4 issued15 April 2026 — may be implemented immediately
Previous version withdrawn15 October 2026 (A2:2022 + Corrigendum May 2023 + A3:2024)
18th Edition issued1 July 2018; in effect for designs after 31 December 2018
Voltage scopeUp to and including 1000 V AC or 1500 V DC
StructureParts 1 to 7, plus Part 8 (functional requirements)
Legal statusNot law itself — the accepted route to satisfying the Electricity at Work Regulations 1989 and Part P

The standard applies to circuits supplied at nominal voltages up to and including 1000 V AC or 1500 V DC. That covers virtually every domestic, commercial, and light industrial installation in the country — from a single socket-outlet in a flat to a complete rewire of a hospital. It does not cover certain specialist installations such as mines, quarries, explosive atmospheres, or high-voltage distribution systems, which are covered by separate regulations.

BS 7671 is not a textbook or a how-to guide. It is a set of requirements — minimum standards that must be met for an installation to be considered safe. The companion documents — the IET Guidance Notes (GN1 through GN8), the On-Site Guide, and the Electrician's Guide — provide the practical interpretation and worked examples that help electricians apply the regulations on site. The most commonly referenced companion is Guidance Note 3 (GN3): Inspection and Testing, now in its 9th Edition.

Which amendment changed what — the short version

Amendments to the 18th Edition
AmendmentIssuedHeadline changes
A1:2020February 2020 (electronic)Section 722 (EV charging) amended and rebased on HD 60364-7-722:2018
A2:202228 March 2022 (brown cover)AFDDs became a requirement in four premises types (421.1.7); new Chapter 82 (prosumer's installations); 443.5 risk-assessment method deleted; Appendix 3 Table 3A deleted and RCD testing changed
A3:202431 July 2024 (electronic)Two new definitions and one new regulation on bidirectional and unidirectional devices (530.3.201)
A4:202615 April 2026 (orange cover)New Chapter 57 (stationary secondary batteries), new Section 716 (Power over Ethernet), new Section 545 (functional earthing for ICT), new Chapter 81 (energy efficiency); 551.7.1 redrafted for bidirectional energy flow

In the app

Every BS 7671 regulation in your pocket

Elec-Mate has auto BS 7671 regs built into every certificate. Tap any field and see the relevant regulation — clause number, full text…

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · BS 7671 Hub

The Parts of BS 7671

BS 7671 is built from seven numbered parts covering design and installation, plus Part 8, which carries the functional requirements added by later amendments. Knowing the structure is what makes the book quick to use — whether you are looking up a regulation, studying for the 2382 exam, or checking compliance on site.

Part 1: Scope, Object, and Fundamental Principles

Defines the scope of the standard — what types of installations it covers and what it does not. Sets out the fundamental principles of electrical safety: protection against electric shock, protection against thermal effects, protection against overcurrent, protection against fault current, and protection against overvoltage. Regulation 133.1.3 also sits here: where equipment is not to an applicable standard, or is used outside the scope of its standard, the designer must confirm it gives at least the same degree of safety and record it as a departure on the Part 6 certification.

Part 2: Definitions

Contains all the defined terms used throughout the standard. Understanding these definitions is critical because many terms have specific technical meanings that differ from everyday usage. For example, "extraneous-conductive-part" has a precise definition that determines whether bonding is required. "Skilled person," "instructed person," and "ordinary person" have specific meanings that affect the level of protection required. Part 2 is frequently tested in the 2382 exam.

Part 3: Assessment of General Characteristics

Requires the designer to assess the characteristics of the installation before starting the design: the purpose of the installation, the supply characteristics (earthing system, supply voltage, prospective fault current), the nature of the demand, the environmental conditions, and compatibility with other systems. You cannot size cables, select protective devices, or design earthing arrangements without first assessing the general characteristics. A4:2026 added a protective neutral bonding (PNB) figure and requirements to Regulation 312.2.1.1.

Part 4: Protection for Safety

The largest and most frequently referenced part. Covers protection against electric shock (Chapter 41), protection against thermal effects (Chapter 42), protection against overcurrent (Chapter 43), protection against voltage disturbances and electromagnetic disturbances (Chapter 44), and isolation and switching (Chapter 46). Chapter 41 holds the automatic disconnection of supply (ADS) requirements — Table 41.1 maximum disconnection times and Tables 41.2 to 41.6 for maximum earth fault loop impedance — which are the tables electricians reach for most often on site.

Part 5: Selection and Erection of Equipment

Covers the practical selection and installation of equipment — wiring systems (Chapter 52), protection, isolation, switching, control and monitoring (Chapter 53), earthing arrangements and protective conductors (Chapter 54), other equipment (Chapter 55), safety services (Chapter 56) and, new at A4:2026, stationary secondary batteries (Chapter 57). This is where you find cable selection, installation methods, minimum conductor sizes, and equipment ratings. Regulation 530.3.201 on unidirectional and bidirectional protective devices sits here, as does the redrafted Regulation 551.7.1 for generating sets in parallel with another source.

Part 6: Inspection and Testing

Sets out the requirements for initial verification (Chapter 64) and periodic inspection and testing (Chapter 65). It specifies which tests must be carried out and what the pass criteria are. Table 64 — minimum values of insulation resistance and the DC test voltages, applied by Regulation 643.3.2 — is in this part. The maximum earth fault loop impedance tables are not: they are Tables 41.2 to 41.6 in Chapter 41, with the supporting loop-impedance material in Appendix 3. Part 6 is the basis for every electrical certificate issued in the UK.

Part 7: Special Installations or Locations

Contains additional or modified requirements where the risk of electric shock or fire is increased. Sections include locations containing a bath or shower (701), swimming pools and other basins (702), saunas (703), construction and demolition sites (704), agricultural and horticultural premises (705), conducting locations with restricted movement (706), marinas (709), exhibitions, shows and stands (711), solar PV (712), Power over Ethernet (716, new at A4:2026), and EV charging (722). Where a Part 7 section applies, its requirements supplement or modify the general requirements in Parts 1 to 6 and Part 8. Part 7 is heavily tested in the 2382 exam because it is full of specific, memorable requirements.

Part 8: Functional Requirements

Part 8 did not exist in the 2018 book — energy efficiency was informative guidance in Appendix 17. Amendment 2:2022 added Chapter 82, Prosumer's low-voltage electrical installations, which sets requirements for installations with local generation and storage (Sections 821 to 826). Amendment 4:2026 added Chapter 81, an informative chapter on energy efficiency that points the reader to the Building Regulations and to BS HD 60364-8-1:2019, and deleted Appendix 17.

In the app

Practice questions covering every part of BS 7671

Elec-Mate's 18th Edition course works through the whole standard with questions mapped to the City and Guilds 2382-22 exam syllabus.

03 · BS 7671 Hub

Key Changes from the 17th Edition

BS 7671:2018 was issued on 1 July 2018 and came into effect on 1 January 2019, replacing the 17th Edition (BS 7671:2008+A3:2015). Installations designed after 31 December 2018 are to comply with the 18th Edition, so the overlap was six months rather than a year. These are the 2018 changes that still shape day-to-day practice.

30 mA RCD on domestic lighting — Regulation 411.3.4

Regulation 411.3.4, "Additional requirements for circuits with luminaires", states: within domestic (household) premises, additional protection by an RCD with a rated residual operating current not exceeding 30 mA shall be provided for AC final circuits supplying luminaires. It uses "shall", so it is a requirement, not a recommendation — and it has been in force since the 18th Edition was published in 2018. It is often reported as a new Amendment 4 rule; it is not. On new work and rewires, lighting circuits are protected by a 30 mA RCD or RCBO.

Arc fault detection devices — Regulation 421.1.7

This is the most widely misquoted regulation in the book, in both directions. The 18th Edition introduced 421.1.7 in 2018 as a recommendation. Amendment 2:2022 redrafted it into a requirement for four premises types, and Amendment 4:2026 reworded the first of them. As it now stands, AFDDs conforming to BS EN 62606 shall be provided for single-phase AC final circuits supplying socket-outlets with a rated current not exceeding 32 A in (a) high rise residential buildings (HRRBs), (b) houses in multiple occupation (HMOs), (c) purpose-built student accommodation, and (d) care homes. A note assumes an HRRB to be a residential building over 18 m in height or in excess of six storeys, whichever is met first. For all other premises, AFDDs are recommended for single-phase AC final circuits supplying socket-outlets not exceeding 32 A. Where used, they go at the origin of the circuit to be protected, and Regulation 532.6 confirms they are installed at the origin of the final circuits to be protected and in AC single-phase circuits not exceeding 230 V. Using an AFDD does not remove the need to apply the other measures in the standard.

Surge protection — Section 443 and Section 534

The two sections do different jobs, and they are routinely confused. Section 443 decides whether you need protection against transient overvoltages; Section 534 governs the selection and erection of the SPDs themselves. Section 534 was completely revised in 2018, the most significant technical change being the selection requirements for the voltage protection level (Up). Amendment 2:2022 then redrafted Section 443: Regulation 443.4.1 requires protection where the consequence of an overvoltage could cause serious injury or loss of human life, or significant financial or data loss — and for all other cases protection shall be provided unless the owner declares it is not required and accepts the risk. The old risk-assessment method in Regulation 443.5, and Annex A443, were deleted. In practice SPDs are now the default on most new installations.

EV charging installations — Section 722

Section 722 was not new in 2018 — the 18th Edition made significant changes to Regulation 722.411.4.1 on the use of a PME supply, deleting the "reasonably practicable" exception, and revised the requirements for external influences, RCDs, socket-outlets and connectors. Amendment 1:2020 then rewrote the section on the basis of HD 60364-7-722:2018, and Amendment 2:2022 folded that in alongside further changes, including prosumer's installations (722.826.3.201). Section 722 does not apply to wireless (inductive) charging.

RCD types — Regulation 531.3.3

Regulation 531.3.3 sets out the RCD types — AC, A, F and B — by how they behave in the presence of DC components and frequencies. Amendment 2:2022 added the sentence that changed specification in practice: RCD Type AC shall only be used to serve fixed equipment where it is known that the load current contains no DC components, with electric heating and simple filament lighting given as examples. Anything with electronics in it — washing machines, dishwashers, EV chargers, LED drivers — needs Type A or better. Most manufacturers now supply Type A as standard for domestic work.

Cable support, fire and escape routes — Regulation 521.10.202

Regulation 521.10.202 replaced 521.11.201 and requires cables to be adequately supported against premature collapse in the event of a fire throughout the installation, not just in escape routes as previously. This is the reason plastic clips alone are no longer acceptable for supporting cables on a ceiling. Amendment 4:2026 added a note explaining the intent of the regulation, and redrafted Regulation 422.2 and 422.2.1 so that 422.2.1 now lists the cables permitted in protected escape routes.

04 · BS 7671 Hub

Amendment 2 (2022)

BS 7671:2018+A2:2022 was issued on 28 March 2022 and could be implemented immediately; BS 7671:2018+A1:2020 remained current until it was withdrawn on 27 September 2022. A2 was a printed reprint of the whole standard — the brown cover — and it is still the version most often quoted second-hand, which is why several A2 changes get misattributed to Amendment 4.

The substantive A2:2022 changes that still matter on site are these. Regulation 411.3.1.2 was redrafted, so main protective bonding applies to extraneous-conductive-parts liable to introduce a dangerous potential difference, with a note clarifying that metallic pipework fed by non-metallic pipes entering the building is not normally an extraneous-conductive-part. Regulation 421.1.7 became a requirement for AFDDs in high rise residential buildings, HMOs, purpose-built student accommodation and care homes. A new Chapter 82 introduced prosumer's low-voltage electrical installations. Regulation 531.3.3 restricted Type AC RCDs to fixed equipment with no DC component in the load current. Appendix 11 (warning and user instruction labels) and a rewritten Appendix 13 on protected escape routes were added.

The two testing changes A2:2022 made — still catching people out

Regulation group 643.3 was redrafted. Where connected equipment is likely to influence the measurement or be damaged, the Table 64 test is applied before the equipment is connected; then, following connection, a test at 250 V DC is applied between live conductors and the protective conductor, with a minimum acceptable value of 1 MΩ (Regulation 643.3.3).

RCD testing changed at the same time, and Table 3A in Appendix 3 was deleted. Regulation 643.8 now requires the effectiveness of automatic disconnection by RCDs to be verified using test equipment to BS EN 61557-6, and its note says that regardless of RCD type, effectiveness is deemed verified where the RCD disconnects within the stated time on an alternating current test at rated residual operating current (I∆n) — for a general non-delay type, 300 ms maximum. The old half-rated and five-times tests are product-standard tests, not an installation verification requirement in BS 7671.

For the consumer unit itself, A2:2022 is also where Regulation 531.3.2 indent (b) began highlighting the use of RCBOs on individual final circuits in residential premises to minimise unwanted tripping — the practical reason most new consumer units are now fully populated with RCBOs rather than split-load RCDs.

In the app

Try Elec-Mate free for 7 days

19 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

05 · BS 7671 Hub

Amendment 4 (2026) — What Actually Changed

BS 7671:2018+A4:2026 was issued on 15 April 2026 and may be implemented immediately. The previous version — BS 7671:2018+A2:2022+Corrigendum (May 2023)+A3:2024 — remains current but is withdrawn on 15 October 2026. Amendment 4 is a substantive amendment: it adds whole chapters and sections, so an older book cannot simply be annotated to match it.

A point of frequent confusion: the electronic amendment issued on 31 July 2024 was Amendment 3 (A3:2024), not Amendment 4. A3 was a very small amendment — two new definitions and one new regulation, 530.3.201, on the use of bidirectional and unidirectional devices.

Amendment 4:2026 changes at a glance

Main changes introduced by Amendment 4:2026
Regulation or sectionWhat changed
312.2.1.1Now includes a protective neutral bonding (PNB) figure and requirements
421.1.7(a)Reworded to read "high rise residential buildings"
422.2 and 422.2.1Protected escape routes modified; 422.2.1 now lists the cables permitted in a protected escape route, and cables in a fire-resisting enclosure are deemed outside it
434.2.1 and 434.3(a)"Inherently short-circuit and earth fault proof" introduced for conductor selection and erection
Annex B443Deleted
Table 51Revised to identify combined protective and functional earthing conductors, combined protective and functional bonding conductors, and functional bonding conductors
Table 52.1Now carries the requirements for cables in a wall or partition
537.4.2Firefighter's switches now required in locations specified by the fire engineer to support the building's fire strategy; 537.4.2.1 deleted
Section 545 (new)Functional earthing and functional equipotential bonding for ICT equipment and systems
551.7.1 and 551.7.2Redrafted for generating sets in parallel — see the panel below
Chapter 57 (new)Stationary secondary batteries; the old Regulation 551.8 requirements moved here
653.1 and 653.2Condition reports must take account of the Appendix 6 notes for the person producing the report and include guidance for the recipient
Section 716 (new)Power over Ethernet — distribution of ELV DC power over data cabling
Chapter 81 (new)Energy efficiency, referring to the Building Regulations and BS HD 60364-8-1:2019; Appendix 17 deleted
Appendix 4Buried cables now have distinct reference methods and current-carrying capacities depending on whether the cable is in direct contact with soil or in a conduit or duct; Tables 4A2, 4D4A, 4E4A, 4H4A and 4J4A revised
Appendix 6Condition report notes redrafted and items rearranged; code FI no longer needs to be marked as unsatisfactory

Bidirectional energy flow — Regulation 530.3.201 and 551.7.1

Standard MCBs, RCDs and RCBOs are built to interrupt fault current flowing one way — from the supply, through the device, to the load. Where a battery or PV inverter can export, fault current can flow the other way. Regulation 530.3.201 requires the selection and erection of equipment for protection to take account of the appropriate use of either a unidirectional or a bidirectional protective device; its note points out that product standards require RCCBs, RCBOs, circuit-breakers and AFDDs to be marked to show which they are — "in" and "out", "line" and "load", or arrows. Amendment 4 then redrafted Regulation 551.7.1, which applies where a generating set runs in parallel with another source:

  • Indent (c) — protective devices shall be selected in accordance with Regulation 530.3.201.
  • Indent (d) — except where the RCD disconnects all live conductors including the neutral, a source of supply shall not be connected to the load side of any RCD providing additional protection that is shared with other circuits.
  • Regulation 551.7.2.1 — the generating set shall be installed on the supply side of all the protective devices for the final circuits of a distribution board, and stationary secondary batteries to Chapter 57 are to be treated as a generating set, not a load.

If you install solar PV, battery storage or EV chargers, that combination — 530.3.201, 551.7.1, 551.7.2 and the new Chapter 57 — is the part of Amendment 4 that will change how you specify a job. It affects device selection, where the storage system lands relative to the RCD, and what you record on the certificate.

In the app

70+ calculators built to BS 7671:2018+A4:2026

Cable sizing, voltage drop, Zs verification, maximum demand, adiabatic equation…

06 · BS 7671 Hub

How BS 7671 Applies to Your Daily Work

For a working electrician, BS 7671 is not an abstract academic document — it is the reference you use every day when designing circuits, selecting cables, choosing protective devices, carrying out tests, and completing certificates. Here is how the key parts of the standard map to common on-site activities.

Cable sizing and circuit design

Appendix 4 contains the current-carrying capacity tables for each cable type and reference method, together with the rating factors for grouping, ambient temperature and thermal insulation. Every reference method has its own tabulated capacity — you read the column for the method you are actually using rather than applying a multiplier on top. For voltage drop, Section 525 sets the requirement and Regulation 525.202 points you to Appendix 4, Section 6.4 for the permitted limits. Note that A4:2026 changed the buried-cable methods: direct in soil and in a conduit or duct now have distinct reference methods and distinct capacities.

Testing and certification

Part 6 specifies the testing sequence, the tests required, and the acceptance criteria. Every test value you record on an EIC or EICR is compared against the BS 7671 limits. The model forms are in Appendix 6, which since A2:2022 carries separate pages for the schedule of circuit details and the schedule of test results, plus fields for recording SPD and AFDD details.

Protection and device selection

Chapters 41, 43 and 53 govern how you select protective devices — MCBs, RCDs, RCBOs, fuses — for protection against electric shock, overload and fault current. Regulation 411.3.2.2 sets which final circuits the Table 41.1 maximum disconnection times apply to: circuits rated up to 63 A with one or more socket-outlets, and circuits rated up to 32 A supplying only fixed connected current-using equipment. Tables 41.2 to 41.6 tell you whether the device will disconnect in time at the measured Zs; the adiabatic equation tells you whether the conductor survives the fault for that duration.

Observation codes and condition reporting

When carrying out a periodic inspection you assess the installation against the current edition of BS 7671, recording every departure, defect and deterioration as an observation with a classification code (C1, C2, C3 or FI). A4:2026 touched this directly: Regulation 653.1 requires the Appendix 6 notes for the person producing the report to be taken into account, Regulation 653.2 requires guidance for the recipient to be included, and Appendix 6 now states that code FI no longer needs to be marked as unsatisfactory.

In the app

Tap any certificate field, see the BS 7671 regulation

Elec-Mate links every certificate field to its relevant BS 7671 clause. When you are on site and need to check a regulation, the answer is one tap away.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-day free trial

Every BS 7671 regulation, always in your pocket

Join 1,600+ UK electricians using Elec-Mate for on-site regulation references, 70+ calculators, and 19 certificate types — all built to BS 7671:2018+A4:2026. 7-day free trial, cancel anytime.

Start your free trial

From £6.99/mo after the trial — no charge until day 8.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in one tap — no calls, no hassle
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play
Certificate types
19Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists

1,600+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy