BS 7671:2018+A4:2026 was issued on 15 April 2026 and may be implemented immediately. The previous version — BS 7671:2018+A2:2022+Corrigendum (May 2023)+A3:2024 — remains current but is withdrawn on 15 October 2026. Amendment 4 is a substantive amendment: it adds whole chapters and sections, so an older book cannot simply be annotated to match it.
A point of frequent confusion: the electronic amendment issued on 31 July 2024 was Amendment 3 (A3:2024), not Amendment 4. A3 was a very small amendment — two new definitions and one new regulation, 530.3.201, on the use of bidirectional and unidirectional devices.
Amendment 4:2026 changes at a glance
Main changes introduced by Amendment 4:2026| Regulation or section | What changed |
|---|
| 312.2.1.1 | Now includes a protective neutral bonding (PNB) figure and requirements |
| 421.1.7(a) | Reworded to read "high rise residential buildings" |
| 422.2 and 422.2.1 | Protected escape routes modified; 422.2.1 now lists the cables permitted in a protected escape route, and cables in a fire-resisting enclosure are deemed outside it |
| 434.2.1 and 434.3(a) | "Inherently short-circuit and earth fault proof" introduced for conductor selection and erection |
| Annex B443 | Deleted |
| Table 51 | Revised to identify combined protective and functional earthing conductors, combined protective and functional bonding conductors, and functional bonding conductors |
| Table 52.1 | Now carries the requirements for cables in a wall or partition |
| 537.4.2 | Firefighter's switches now required in locations specified by the fire engineer to support the building's fire strategy; 537.4.2.1 deleted |
| Section 545 (new) | Functional earthing and functional equipotential bonding for ICT equipment and systems |
| 551.7.1 and 551.7.2 | Redrafted for generating sets in parallel — see the panel below |
| Chapter 57 (new) | Stationary secondary batteries; the old Regulation 551.8 requirements moved here |
| 653.1 and 653.2 | Condition reports must take account of the Appendix 6 notes for the person producing the report and include guidance for the recipient |
| Section 716 (new) | Power over Ethernet — distribution of ELV DC power over data cabling |
| Chapter 81 (new) | Energy efficiency, referring to the Building Regulations and BS HD 60364-8-1:2019; Appendix 17 deleted |
| Appendix 4 | Buried cables now have distinct reference methods and current-carrying capacities depending on whether the cable is in direct contact with soil or in a conduit or duct; Tables 4A2, 4D4A, 4E4A, 4H4A and 4J4A revised |
| Appendix 6 | Condition report notes redrafted and items rearranged; code FI no longer needs to be marked as unsatisfactory |
Bidirectional energy flow — Regulation 530.3.201 and 551.7.1
Standard MCBs, RCDs and RCBOs are built to interrupt fault current flowing one way — from the supply, through the device, to the load. Where a battery or PV inverter can export, fault current can flow the other way. Regulation 530.3.201 requires the selection and erection of equipment for protection to take account of the appropriate use of either a unidirectional or a bidirectional protective device; its note points out that product standards require RCCBs, RCBOs, circuit-breakers and AFDDs to be marked to show which they are — "in" and "out", "line" and "load", or arrows. Amendment 4 then redrafted Regulation 551.7.1, which applies where a generating set runs in parallel with another source:
- Indent (c) — protective devices shall be selected in accordance with Regulation 530.3.201.
- Indent (d) — except where the RCD disconnects all live conductors including the neutral, a source of supply shall not be connected to the load side of any RCD providing additional protection that is shared with other circuits.
- Regulation 551.7.2.1 — the generating set shall be installed on the supply side of all the protective devices for the final circuits of a distribution board, and stationary secondary batteries to Chapter 57 are to be treated as a generating set, not a load.
If you install solar PV, battery storage or EV chargers, that combination — 530.3.201, 551.7.1, 551.7.2 and the new Chapter 57 — is the part of Amendment 4 that will change how you specify a job. It affects device selection, where the storage system lands relative to the RCD, and what you record on the certificate.
In the app
70+ calculators built to BS 7671:2018+A4:2026
Cable sizing, voltage drop, Zs verification, maximum demand, adiabatic equation…