REGULATIONS

BS 7671 Amendment 3: What Changed and Why It Matters

Amendment 3 (A3:2024) was issued on 31 July 2024 as a free PDF supplement. It introduces two new definitions and Reg 530.3.201 (Chapter 53) — the bidirectional and unidirectional protective device requirement — essential for any installation with solar PV, battery storage, or other embedded generation. This guide explains every detail.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

10 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1BS 7671:2018+A3:2024 was issued on 31 July 2024 as a free PDF supplement — it does not replace the main standard and does not require buying a new book.
  • 2A3:2024 introduces two new definitions ("bidirectional protective device" and "unidirectional protective device") and one new Regulation — Reg 530.3.201 (Chapter 53) — requiring device selection to account for the direction of current flow in installations with embedded generation.
  • 3Reg 530.3.201 also prohibits placing a unidirectional device where bidirectional current flow may occur. Additionally, Reg 551.7.1(d) (introduced in A4:2026) prohibits connecting a source to the load side of an RCD under certain conditions — relevant for any PV or BESS circuit protected by an RCD.
  • 4Electricians working on solar PV, battery storage, EV charger, and generator installations must understand the distinction between bidirectional and unidirectional devices to ensure correct device selection.
  • 5Existing installations that are safe and compliant with BS 7671:2018+A2:2022 do not need to be retrospectively upgraded to meet A3:2024 requirements.
  • 6BS 7671:2018+A4:2026 was issued on 15 April 2026 and may be used immediately. A3:2024 remains current but will be withdrawn on 15 October 2026. A4 introduces Chapter 82 — Prosumer's Electrical Installations — as the comprehensive framework for solar PV and BESS sites.
  • 7Elec-Mate includes updated regulation references for A3:2024 and A4:2026, and the AI circuit designer accounts for bidirectional device requirements when designing solar PV and battery storage circuits.
01 · Regulations

What Is BS 7671 Amendment 3 (A3:2024)?

BS 7671:2018+A3:2024 is the third amendment to the 18th Edition of the IET Wiring Regulations. It was issued by the Institution of Engineering and Technology (IET) on 31 July 2024 as a free PDF supplement. Unlike a new edition of the standard, Amendment 3 is a targeted addition — it does not replace the existing brown book (BS 7671:2018+A2:2022) but adds to it.

The amendment addresses a specific technical gap that became increasingly important as the UK transitioned to renewable energy sources and embedded generation. With more homes and commercial premises installing solar PV arrays, battery energy storage systems (BESS), and other forms of distributed generation, the electrical installation now commonly includes multiple sources of supply. This creates the possibility of current flowing in both directions through protective and switching devices — a scenario that the previous edition of BS 7671 did not explicitly address.

The core of Amendment 3 is a new regulation — Reg 530.3.201 (Chapter 53 of BS 7671) — together with two new definitions: "bidirectional protective device" and "unidirectional protective device". Reg 530.3.201 sets out the requirement to select and install protective devices appropriate to the direction of current flow they will experience. The amendment also includes associated guidance notes to help designers and installers understand the practical implications.

For electricians, the key message is straightforward: if you work on any installation that has, or may have in the future, more than one source of supply (solar PV, battery storage, generator, EV vehicle-to-grid), you need to understand this amendment and ensure the devices you select are suitable for the direction of current flow they will experience.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Regulations

The A3:2024 Requirement: Reg 530.3.201 — Bidirectional Devices

The Amendment 3 addition is Regulation 530.3.201, sitting within Chapter 53 of BS 7671 (Selection and Erection of Equipment). A3:2024 also introduces two new definitions — "bidirectional protective device" and "unidirectional protective device" — to support the regulation's application. Reg 530.3.201 requires that selection and erection of protective equipment shall take account of the appropriate use of either a unidirectional or a bidirectional protective device, depending on whether current can flow in one direction only or in both directions through the device.

  • Identify all sources of supply — the mains DNO supply, any solar PV inverters, battery storage systems, generators, or vehicle-to-grid (V2G) EV chargers. Each source can potentially feed current back into the installation.
  • Determine the direction of current flow — at each protective device in the circuit path, establish whether current can flow in one direction only (from supply to load) or in both directions (supply to load and load to supply).
  • Select suitable devices — if bidirectional current flow is possible, the protective device must be rated for bidirectional operation. If a unidirectional device is used where bidirectional flow can occur, it may fail to interrupt a fault safely.
  • Document the design decision — the choice of bidirectional or unidirectional devices should be recorded in the design documentation. This is particularly important for Electrical Installation Certificates where the design is verified.

The regulation does not mandate that all devices in every installation must be bidirectional. It is targeted: only where the installation topology creates the possibility of reverse current flow does the requirement apply. A standard domestic installation with a single DNO supply and no embedded generation is unaffected.

03 · Regulations

Bidirectional Devices: What They Are and When You Need Them

A bidirectional protective device can safely interrupt fault current flowing in either direction through the device. Most miniature circuit breakers (MCBs) conforming to BS EN 60898-1 are inherently bidirectional — they use a thermal-magnetic trip mechanism that responds to overcurrent regardless of the direction of flow.

You need bidirectional devices in the following scenarios:

  • Solar PV installations — the PV inverter feeds current back through the consumer unit into the grid. Any MCB, RCBO, or switching device in the path between the inverter connection point and the meter must be bidirectional.
  • Battery energy storage systems (BESS) — the battery charges from the supply (current flowing in) and discharges to the installation (current flowing out). The protective devices must handle both directions.
  • Vehicle-to-grid (V2G) EV chargers — these chargers can both draw power from the grid to charge the vehicle and feed power from the vehicle battery back into the installation. The protective devices must be bidirectional.
  • Generator installations with grid paralleling — where a standby generator operates in parallel with the mains supply, current can flow in both directions at the point of connection.

The good news is that most standard MCBs used in UK consumer units are already bidirectional. The issue arises more commonly with moulded case circuit breakers (MCCBs), isolators, and certain specialist switching devices that may only be rated for unidirectional operation.

04 · Regulations

Unidirectional Devices: The Risk of Getting It Wrong

A unidirectional protective device is designed to interrupt current flowing in one direction only — typically from the supply (line) terminal to the load terminal. If fault current flows in the reverse direction through a unidirectional device, it may not trip correctly. In the worst case, the device could fail to disconnect the fault at all, leading to:

  • Sustained fault current — the device does not trip, so the fault current continues to flow. This can cause overheating, cable damage, and fire.
  • Damage to the protective device — a unidirectional device subjected to reverse current may suffer internal arcing, contact welding, or mechanical failure.
  • Loss of supply isolation — if the device cannot open under reverse current, it becomes impossible to safely isolate the circuit for maintenance or emergency disconnection.
  • Invalidation of the installation certificate — using a unidirectional device where bidirectional operation is required is a design deficiency that would be recorded as a C2 (Potentially Dangerous) observation on an EICR.

The practical lesson is simple: before installing any protective or switching device in a circuit that includes embedded generation, check the manufacturer documentation to confirm whether the device is bidirectional or unidirectional. If the datasheet does not explicitly state bidirectional capability, assume it is unidirectional and either choose a different device or contact the manufacturer for clarification.

05 · Regulations

Practical Impact for Working Electricians

For the majority of day-to-day domestic electrical work — socket additions, lighting circuits, consumer unit changes on single-supply installations — Amendment 3 does not change your working practices. The requirement is specifically triggered by installations with multiple sources of supply.

However, the proportion of installations with embedded generation is growing rapidly. The UK government's net zero targets, the Smart Export Guarantee (SEG), and falling solar PV prices mean that more domestic and commercial properties are adding solar, battery storage, and V2G EV charging every year. As an electrician, you will increasingly encounter these installations, and you need to be prepared.

  • During design — when designing an installation with embedded generation, identify every protective device in the circuit path and confirm it is suitable for the direction(s) of current flow. Record your design decisions.
  • During installation — verify that the devices supplied match the design specification. Check product markings and datasheets. Do not substitute a device without confirming its directional rating.
  • During inspection and testing — when carrying out an EICR or verifying a new installation, check that the devices installed are appropriate for any embedded generation present. A unidirectional device in a bidirectional circuit path should be recorded as a defect.
  • During certification — the Electrical Installation Certificate should record that the design accounts for bidirectional current flow where applicable. Reference the Reg 530.3.201 (A3:2024) bidirectional device requirement in the observations if relevant.

If you are studying for your C&G 2391 inspection and testing qualification, expect questions on Amendment 3 to appear in exam papers. The examiners will be looking for your understanding of when bidirectional devices are required and how to identify installations that are affected.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · Regulations

Solar PV and Battery Storage: The Primary Use Case

The driving force behind Amendment 3 is the rapid growth of solar PV and battery storage installations in the UK. When a solar PV system is connected to a domestic consumer unit via an AC-coupled inverter, the inverter generates AC current that flows back through the consumer unit and into the grid. This reverse current flow passes through the main switch, the meter tails, and potentially through other protective devices depending on the connection arrangement.

Battery energy storage systems add another layer of complexity. A BESS can charge from the grid (drawing current from the supply), charge from solar PV (drawing current from the inverter), and discharge to the installation (supplying current to loads). The direction of current flow through the protective devices changes dynamically depending on whether the battery is charging, discharging, or idle.

Key Design Considerations

  • The main switch (isolator) at the consumer unit must be bidirectional if the installation exports to the grid.
  • Any MCB or RCBO protecting the circuit that connects the inverter or BESS to the consumer unit must be confirmed as bidirectional.
  • RCDs in the circuit path must detect earth leakage current regardless of the direction of current flow — most standard RCDs do, but always verify.
  • The DNO may have additional requirements for the type and rating of protective devices at the point of connection. Check the G98/G99 application requirements.

Reg 551.7.1(d) — RCD Load-Side Prohibition (A4:2026)

BS 7671:2018+A4:2026 redrafts Reg 551.7.1 and adds indent (d), which prohibits the connection of a source (for example a PV inverter, BESS, or generator) to the load side of an RCD under certain conditions. This is directly relevant to any installation where solar PV or battery storage is connected downstream of an RCD-protected circuit. Combined with Reg 530.3.201 (A3:2024), these two requirements form the core regulatory framework for multi-source installations. A4:2026 was issued on 15 April 2026 and may be used immediately; A3:2024 is withdrawn on 15 October 2026. See the BS 7671 Amendment 4 guide for the full A4 framework, including the new Chapter 82 — Prosumer's Electrical Installations.

AI circuit designer for solar PV installations

Elec-Mate's AI circuit designer handles bidirectional device selection automatically. Describe the installation — solar PV capacity, battery storage…

Try it free for 7 days
Download on the App StoreGet it on Google Play
07 · Regulations

Certification and Compliance Implications

Amendment 3 has direct implications for how you complete electrical certificates. When issuing an Electrical Installation Certificate (EIC) for a new installation or alteration that includes embedded generation, you must confirm that the design complies with Reg 530.3.201 (A3:2024) — the bidirectional device selection requirement.

On the EIC, the design section should note that bidirectional current flow has been considered and that all protective and switching devices in the circuit path are suitable. If you are using Elec-Mate to produce the certificate, the app prompts you to record embedded generation details and flags any device compatibility issues.

When carrying out periodic inspection and testing (EICR), you should check whether the existing installation includes any embedded generation. If it does, verify that the protective devices are suitable for bidirectional operation. If a unidirectional device is found in a bidirectional circuit path, record it as a C2 (Potentially Dangerous) observation referencing Reg 530.3.201 (A3:2024).

  • New installations with solar PV/BESS — the EIC must confirm compliance with the Reg 530.3.201 (A3:2024) bidirectional device requirement. Record the inverter model, battery system model, and confirm bidirectional device suitability.
  • Alterations adding embedded generation — if you are adding solar PV or battery storage to an existing installation, check that the existing consumer unit devices are bidirectional. If not, they must be replaced as part of the alteration.
  • EICR on existing installations — if the installation has embedded generation that was installed before A3:2024, check device suitability during the periodic inspection. Record any non-compliant devices in the observations.

Remember that Amendment 3 is not retrospective. An installation that was compliant with BS 7671:2018+A2:2022 at the time of installation is still compliant. However, if you identify a genuine safety issue (a unidirectional device in a bidirectional circuit path that could fail to disconnect a fault), that should be recorded as a defect regardless of the regulation edition in force at the time of installation.

08 · Regulations

How Elec-Mate Keeps You Up to Date

Keeping track of regulation changes is one of the biggest challenges for working electricians. Amendment 3 is a relatively small change, but it is easy to miss — and getting it wrong on a solar PV or battery storage installation could result in a serious safety issue and a defective certificate.

AI Circuit Designer

Describe the installation and the AI designs the circuit with A3:2024 compliance. It automatically selects bidirectional devices where required and flags any incompatibilities in the design.

AI Board Scanner

Scan an existing consumer unit with your phone camera. The AI identifies the installed devices and can flag potential unidirectional devices in installations with embedded generation — helping you catch issues during an EICR.

46+ Training Courses

The Elec-Mate training library includes modules on BS 7671 amendments, solar PV installation, battery storage, and EV charging. Stay current with regulation changes through structured CPD content, flashcards, and mock exams.

50+ Calculators

Cable sizing, voltage drop, earth fault loop impedance, prospective fault current, maximum demand — all the calculations you need for solar PV and battery storage design, with BS 7671 compliance built in.

Stay ahead of regulation changes

Elec-Mate updates its regulation references, AI agents, and training content with every BS 7671 amendment.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions About BS 7671 Amendment 3

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Design Solar PV Circuits with A3:2024 Compliance

Elec-Mate's AI circuit designer selects bidirectional devices automatically. Plus 70+ calculators, AI board scanner, voice test entry, and 46+ training courses. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy