LIGHTING CONTROL SYSTEMS

DALI Lighting Control Wiring Guide (BS EN 62386) for UK Electricians

DALI (Digital Addressable Lighting Interface) is the open international standard for lighting control on UK commercial projects. This guide explains BS EN 62386, the differences between DALI-1, DALI-2 and D4i, how to wire the bus correctly under BS 7671:2018+A4:2026 (including Section 528 segregation), the commissioning workflow, and how DALI compares with KNX, 0-10V and DMX.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

16 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

How do you wire a DALI lighting control system?

Run permanent live, neutral and CPC to every driver — there is no switched live. Then run a two-core, polarity-insensitive DALI bus (nominal 16V DC) to every device: up to 64 short addresses, 16 groups and 16 scenes per line, max 300m at 1.5mm². Each line needs one bus PSU. Switching, grouping and scenes are set in software at commissioning, not in copper. Under BS 7671:2018+A4:2026 the bus is a Band I circuit — Section 528 governs sharing cable/trunking with the Band II mains.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1DALI is defined by the BS EN 62386 series — Part 101 covers the physical bus, Part 102 covers control gear, Part 103 covers control devices, and the Part 2xx range covers application extensions such as emergency lighting (Part 202) and colour control (Part 209).
  • 2The DALI bus is a polarity-insensitive two-wire bus, nominal 16V DC, up to 250mA. It supports 64 short addresses, 16 groups and 16 scenes per line, with a maximum cable length of 300 metres at 1.5mm² conductor cross-section.
  • 3DALI-2 introduced certified interoperability between gear and control devices from different manufacturers. D4i extends DALI-2 with intra-luminaire power and data on the same pair for IoT-enabled luminaires.
  • 4Under BS 7671:2018+A4:2026 the DALI bus is a Band I (ELV) signalling circuit. Section 528 governs how it may share trunking, conduit and luminaires with the Band II mains supply powering the drivers.
  • 5A short circuit on the DALI bus disables the whole line — every luminaire on that bus holds at its last-known or fail-safe brightness. Fault isolation and short-circuit-proof bus power supplies are essential.
  • 6Commissioning is where DALI delivers value — addressing, grouping, scene programming and sensor binding are done with vendor software or vendor-neutral DALI-2 tools.
01 · Lighting Control Systems

What DALI Actually Is

DALI stands for Digital Addressable Lighting Interface — the open international standard for digital communication between lighting control gear (drivers, ballasts, emergency converters) and control devices (sensors, push-button panels, scene controllers, BMS). It is published in the BS EN 62386 series and is the dominant protocol for commercial lighting control on UK fit-out, retrofit and new-build projects.

Where 0-10V analogue offers one brightness channel per dimming line, and relay contactors switch only pre-wired groups, a DALI bus addresses up to 64 individual devices per line, commands each independently, queries each for status (lamp failure, energy, hours run), and reorganises groupings in software. For the UK electrician this changes the wiring: permanent live to every driver, plus a two-wire DALI bus to every controllable device. Switching happens in software during commissioning, not in copper at first fix.

DALI is digital signalling, not power

The DALI bus carries data at approximately 1200 baud as a Manchester-encoded signal around a 16V DC nominal level. It does not power the luminaire — every driver still needs its own 230V AC mains supply.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Lighting Control Systems

DALI-1 vs DALI-2 vs D4i

DALI has evolved through three generations, often mixed within the same building. Knowing which generation you have changes the commissioning tools you need and how the bus is powered.

DALI-1

Original — mid-2000s

Defined the bus, the 16V DC physical layer and the 64-address command set. Vendor interoperability was uneven, so commissioning typically required vendor-specific tools.

DALI-2

Certified interoperability — administered by DiiA

Gear (Part 102) and control devices (Part 103) carrying the DALI-2 logo are guaranteed to interoperate at protocol level. DALI-2 also formalised the single bus power supply (one PSU per line).

D4i

DALI-2 extension — IoT-ready

Requires intra-luminaire DALI: the driver can supply bus power, exposes standardised energy and diagnostic data, and accepts IoT sensor nodes plugged directly into the luminaire. The foundation for connected-luminaire IoT in offices and warehouses.

Specify DALI-2 throughout where possible

New specifications almost universally call for DALI-2 gear, frequently with D4i where future IoT sensors are anticipated. Retrofits often splice into DALI-1 — interoperable in principle but proprietary extensions and older firmware can create commissioning issues. Where mixing, allow contingency for vendor-specific troubleshooting.

03 · Lighting Control Systems

DALI Bus Topology and Limits

The DALI bus is exceptionally permissive about topology. There is no required daisy-chain, no terminating resistor, no trunk-and-spur layout. The standard calls this "free topology" — branches, stars, trees and mixed arrangements are all permitted, provided cumulative cable length and electrical loading stay within limits.

Per-line limits (one DALI bus)

Devices (short addresses)64 (0–63)
Groups16 (0–15)
Scenes16 (0–15)
Nominal bus voltage16V DC
Max bus supply current250mA
Max cable length (1.5mm²)300 m
Max bus voltage drop2V at full load
Topology / terminationFree / none

A multi-channel driver (e.g. 4-channel RGBW) consumes one address per channel. Typical control gear draws around 2mA from the bus, so a fully populated line of 64 devices sits well under the 250mA budget — but sensors and control panels also draw bus current, so count the load in design.

Plan addresses before you wire

A common first-fix mistake is to wire more than 64 controllable devices onto a single bus. Multi-channel drivers, emergency converters, sensors and panels all consume addresses. Count the address budget in design — not at commissioning when re-pulling cable is expensive.

04 · Lighting Control Systems

Bus Power Supply

Every DALI line needs a bus power supply — a small DIN-rail or surface unit providing 16V DC nominal and current for the bus. Without it, no signalling occurs, although every driver still receives mains and delivers light at its last-known level.

Bus PSU specification

Nominal bus voltage16V DC
Permitted bus range9.5V – 22.5V
Max bus current250mA per line
Short-circuit protectionRequired (DALI-2)
PSUs per lineExactly one (DALI-2)
D4i in-luminaire PSUDriver-sourced

DALI-2 mandates exactly one bus PSU per line. Legacy DALI-1 installations with parallel PSUs should be corrected during refurbishment. D4i drivers can supply bus power on the same pair within the luminaire boundary, useful for modular ceiling tiles where the driver and sensor share a connector.

Sizing the PSU is not optional

A common commissioning fault is an under-rated bus PSU. The bus works at first fix and during initial addressing — then drops devices intermittently once all 64 are powered up. Sum the maximum bus current from datasheets and size with at least 20% margin.

05 · Lighting Control Systems

Cable Selection for the DALI Bus

The DALI bus is intentionally tolerant of cable choice — no impedance spec, no shielding or twisted-pair requirement, no polarity. The two conductors are interchangeable: connecting them the wrong way causes no damage and does not stop the bus working. A deliberate decision to make DALI installable by general electricians.

Conductor cross-section vs maximum line length

1.5mm²~300 m
0.75mm²~150 m
0.5mm²~100 m

The limiting factor is voltage drop on the bus (2V at full load), not current rating. Smaller conductors de-rate the maximum length roughly linearly.

What the bus needs

  • Cable: standard mains cable, commonly 1.5mm² twin LSZH or two cores of a 5-core mains cable.
  • Polarity: insensitive — the two cores terminate either way at every device.
  • Shielding: not required; useful only on noisy industrial sites near motors or VSDs.

Combined mains + DALI cable

Using 5-core mains cable for L, N, CPC and the DALI pair together is permitted under BS 7671:2018+A4:2026 Section 528 provided every core carries insulation rated for the highest voltage present.

Standardise on 5-core for clean installation

On any DALI fit-out larger than a single room, standardising on a 5-core 1.5mm² mains-rated cable between luminaires is the cleanest approach. One cable per drop, no segregation problem inside the cable, every conductor rated for full mains insulation. Mark the DALI cores at every termination.

06 · Lighting Control Systems

Section 528 — Segregation Under BS 7671:2018+A4:2026

Section 528 of BS 7671:2018+A4:2026 governs the proximity of wiring systems of different voltage bands. The DALI bus is a Band I (ELV) signalling circuit — Band I explicitly covers signalling and control installations — and the mains supply to the drivers is Band II. Regulation 528.1 sets out when these may share a wiring system.

Reg 528.1 — permitted methods to combine Band I and Band II

A Band I circuit shall not share a wiring system with a Band II circuit unless one of these methods is used:

528.1 (a)/(b)

Every cable (or every core of a multicore cable) is insulated for the highest voltage present. This is the basis for the 5-core mains-rated cable approach.

528.1 (c)

Cables are installed in a separate compartment of a cable ducting or trunking system.

528.1 (d)/(e)

A cable tray with a physical partition, or a separate conduit, trunking or ducting system for the DALI bus.

528.1 (f)

For a multicore cable, the Band I cores are separated from the Band II cores by an earthed metal screen of equivalent current-carrying capacity to the largest Band II core.

Within the luminaire, the requirements of Section 559 (luminaires and lighting installations) apply alongside Section 528 — the DALI bus terminals and the mains terminals must be appropriately separated within the gear tray, or the bus cable must carry mains-rated insulation up to the driver. Where the bus serves Part 202 emergency converters, BS 5266 and BS 8519 may impose fire-rated cable requirements on that segment; 528.1 itself references BS 5266, BS 5839 and BS 8519 for safety-service separation. Check the project fire engineering brief.

Section 715 ELV lighting interaction

Where the lighting itself is extra-low voltage (e.g. SELV LED strip on a 24V output), Section 715 of BS 7671:2018+A4:2026 governs the SELV output side. The DALI bus controlling the SELV driver remains a Band I signalling circuit subject to Section 528. See the Section 715 ELV lighting under A4:2026 guide.

07 · Lighting Control Systems

Practical Wiring on Site

First-fix follows a consistent pattern, and doing it the same way every time pays off at commissioning.

  1. Run permanent live, neutral and CPC to every driver from the lighting MCB or RCBO — as you would for an uncontrolled mains-switched luminaire. There is no switched live in a DALI installation.
  2. Run the DALI bus pair (two cores, polarity-insensitive) to every device — every driver, every sensor, every control panel, every emergency converter. Free topology: branch, star or daisy-chain as suits.
  3. Terminate the bus pair at the driver's DA / DA terminals (sometimes labelled D+ / D-, but polarity-insensitive). Tighten to the driver's specified torque.
  4. Run the DALI bus back to the lighting control panel where the bus PSU sits. Terminate on the PSU output and power up.
  5. For multi-line systems, each line has its own PSU and bus pair. Lines may share trunking but must not share bus cores — each line is a separate two-wire pair with independent address space.
  6. Document the bus topology on the as-installed drawing — every drop, every drive, every sensor. Commissioning relies on knowing which physical luminaire corresponds to which discovered short address.

Permanent live to every driver

The single most common DALI first-fix mistake is wiring one core as a switched live. Every driver receives permanent mains 24/7. If you wire a switched live from a wall plate, DALI commands cannot wake the driver because it is unpowered. The wall plate is itself a DALI control device on the bus — not a mains switch.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
08 · Lighting Control Systems

Commissioning — Addressing, Grouping, Scenes

Commissioning is where DALI delivers its value. Out of the box, every driver responds to the broadcast address — every luminaire reacts identically until commissioning gives each its own identity.

  1. Power up the bus and confirm every driver is alive — broadcast a fade-to-100% command and walk the building. If a luminaire does not respond, it is unpowered, unwired, or faulty.
  2. Run automatic short address assignment from the commissioning tool. The tool assigns addresses 0 to (N-1) to every device. The assignment is effectively random, so identification comes next.
  3. Identify each address against the physical luminaire — by flashing each address in turn and walking the space. Record the mapping on the as-installed drawing.
  4. Assign devices to groups (e.g. Group 0 = perimeter, Group 1 = central, Group 2 = corridor). A device may belong to multiple groups; commands target groups efficiently.
  5. Program scenes (Scene 0 = Meeting, Scene 1 = Presentation, Scene 2 = Cleaning, Scene 15 = Off). Each device stores its own brightness for each scene.
  6. Bind control devices to groups or addresses — push-buttons and PIR sensors get their group and scene mappings here. This is where DALI replaces traditional wired switching entirely in software.

Tridonic masterCONFIGURATOR, Helvar Designer and Lunatone DALI Cockpit are common manufacturer tools. DALI-2 certified components also work with vendor-neutral tools such as DALI Cockpit. A USB-to-DALI interface (typically £100–£300) connects the laptop to the bus.

Hand the commissioning file to the client

The commissioning file (a backup of every address, group, scene and binding on the bus) is the most valuable handover document on a DALI project. Save to project records, email a copy to the client, and store a backup off-site.

09 · Lighting Control Systems

Emergency Lighting Integration (BS EN 62386-202)

BS EN 62386-202 defines the DALI command set for self-contained emergency lighting. Under BS 5266, self-contained luminaires must be tested at defined intervals: a short functional test (typically monthly) and a full-rated-duration discharge test (annually). DALI Part 202 automates this.

  • Addressing: each emergency converter takes a DALI short address on the bus, consuming one of the 64 addresses.
  • Functional test: triggered on any addressed converter at any time, individually or in groups.
  • Discharge test: scheduled outside occupation hours, with results (pass / fail / battery duration) logged automatically.
  • Audit trail: test logs pushed to the BMS over a BACnet or Modbus gateway, aligned to the BS 5266 logbook requirement.
  • Self-reporting: failed converters or batteries report over the bus — facilities get an automatic alert rather than waiting for the next walk-test.

DALI-driven emergency testing is one of the strongest commercial arguments for the protocol on buildings larger than a small office — labour saving on monthly and annual testing repays the system cost within a few maintenance cycles. See the BS 5266 emergency lighting standard guide.

Emergency cabling still follows BS 5266 / BS 8519

The DALI bus delivers test commands and collects results, but the emergency luminaire itself is still subject to BS 5266 maintained / non-maintained classification, three-hour duration, and any fire-rated cabling required by the building's fire strategy.

10 · Lighting Control Systems

Master/Slave Architecture vs Broadcast Mode

A DALI line can operate in three architectural modes, which determine commissioning effort and flexibility.

Broadcast

Every device listens to every command. No addressing, groups or scenes — the whole bus dims and switches as one. The factory default, occasionally specified for very simple applications.

Master/slave

A single master control device (a DALI-2 wall panel, sensor or application controller) issues commands to a defined set of addressed slaves. Common for small commercial spaces — meeting rooms, retail bays.

Managed (controller-based)

A central application controller or routing gateway orchestrates groups, scenes, schedules and sensor logic — often a node on a higher-level BACnet / Modbus / KNX network. Typical for whole-building lighting management.

The managed architecture is dominant on commercial fit-outs: a line controller sits on each line, runs schedules and scene logic, and connects to the BMS over BACnet/IP. See the commercial lighting guide for whole-building integration.

11 · Lighting Control Systems

Fault Isolation on the Bus

A short circuit on the DALI bus disables the entire line. Every device drops to its configured bus-failure state — typically last-scene, sometimes a fail-safe level. The fault-finding sequence is different from a conventional lighting circuit.

  1. Confirm the bus PSU is delivering 16V DC across the PSU output terminals with the bus disconnected. If the PSU is dead, the line is unpowered.
  2. Reconnect the bus and re-measure. If voltage reads near 0V with the PSU trying to source, there is a short somewhere on the line. The PSU's current-limiter is preventing damage but no signalling can occur.
  3. Bisect the bus — disconnect at a known midpoint and measure each half independently. The half that still reads low contains the short.
  4. Repeat the bisection until the short is localised. Common causes: a bus core touching a mains core or CPC inside a driver, a damaged cable at a containment penetration, a failed driver with internally shorted DA terminals.
  5. For repeated bus failures, fit a short-circuit-proof bus PSU (most DALI-2 PSUs are) and surge protection on the bus side of the PSU — particularly on outdoor or industrial sites with heavy switching.

Lights still work without bus signalling

With the bus disabled, every driver still has mains and outputs light at its last-known level. The system has lost control but not power. The failure mode is lit, not dark — a feature, but it can mask a bus fault for days until someone notices the controls have stopped working.

12 · Lighting Control Systems

DALI vs KNX vs 0-10V Analogue vs DMX

DALI is not the only lighting control protocol. The most common alternatives are KNX, 0-10V analogue, DMX, and increasingly Power over Ethernet (PoE) lighting.

ProtocolAddressingStatus feedbackTypical use
DALI64 per line, groups + scenesYes (lamp fail, energy, hours)General commercial lighting
KNXBuilding-wide, multi-serviceYesWhole-building backbone
0-10VNone (single analogue channel)NoSimple zoned dimming
DMX512Channel-based, broadcastNoTheatre, studio, feature lighting
PoE lightingIP address per luminaireYesData-centre / high-density office
  • DALI vs KNX — many projects use DALI for lighting and KNX as the building backbone, bridged by DALI/KNX gateways. See the KNX wiring installation guide.
  • DALI vs 0-10V — DALI replaces 0-10V where individual control, energy reporting, or future reconfigurability matters.
  • DALI vs DMX — DMX is faster and broadcast-only; it dominates entertainment, DALI dominates general commercial.
  • DALI vs PoE — PoE delivers power and Ethernet data on Cat6 to each luminaire as an IP device. See the PoE lighting vs traditional LED wiring guide.
  • DALI vs wireless — for residential use, Zigbee and Matter often replace DALI. See the smart home lighting installation guide.
13 · Lighting Control Systems

Certification and Handover

A DALI installation must be certified to BS 7671:2018+A4:2026 like any other. The mains side — permanent live feeds, the bus PSU mains feed, and the lighting MCB/RCBO — is recorded on the EIC or Minor Works Certificate, with test results in the schedule of test results.

BS 7671 documentation

EIC or Minor Works Certificate for the mains side under BS 7671:2018+A4:2026, with the schedule of test results. Emergency lighting is separately recorded under BS 5266 with first test results as the logbook baseline.

DALI-specific records

A commissioning report (every short address, its physical luminaire, programmed groups and scenes, control device bindings), the software configuration backup file, and as-installed drawings with every luminaire numbered against its DALI short address.

On the Elec-Mate platform, the EIC tool covers the mains-side certification, and lighting commissioning record templates cover the DALI handover — both produced as PDFs aligned to BS 7671:2018+A4:2026.

Hand over the bus, not just the lights

A handover that consists only of "the lights work" is incomplete. Include the commissioning backup file, the address-to-luminaire mapping, the group and scene programming, and the emergency lighting test schedule.

Certify the mains side of your DALI install

Produce the EIC, EICR and Minor Works Certificate for the mains side of a DALI lighting installation — aligned to BS 7671:2018+A4:2026, with the schedule of test results built in.

Try it free for 7 days
Download on the App StoreGet it on Google Play

How to Install and Commission a DALI Lighting System

The end-to-end workflow from first-fix wiring to client handover for a DALI-2 lighting control system on a UK commercial fit-out, aligned to BS EN 62386 and BS 7671:2018+A4:2026.

1

Plan the bus topology and address budget

Count every controllable device — drivers (one address per dimmable channel), emergency converters, sensors and control panels. Stay within 64 addresses per line and split into multiple lines if needed. Confirm cable lengths are within 300m at 1.5mm². Mark the topology on the lighting drawing before first fix.

2

First-fix wiring

Run permanent live, neutral and CPC to every driver from the lighting MCB or RCBO. Run a two-core polarity-insensitive DALI bus pair to every controllable device. Standardise on a 5-core 1.5mm² mains-rated cable carrying mains and bus together to satisfy Section 528 of BS 7671:2018+A4:2026 in a single cable.

3

Install the bus power supply

Mount the DALI bus PSU in the lighting distribution panel or local control panel. Feed from a Band II mains supply. Connect the PSU output to the bus pair returning from the luminaires. Power up and confirm 16V DC on the bus.

4

Address every device on the bus

Connect a USB-to-DALI interface to the bus. Open the commissioning software (vendor-specific or DALI-2 vendor-neutral). Run automatic addressing to assign short addresses 0 to N-1. Walk the building flashing each address and record the mapping to physical luminaires on the as-installed drawing.

5

Configure groups, scenes and control devices

Assign devices to groups based on the zoning plan. Program scenes (Meeting, Presentation, Cleaning, etc) with the required brightness per device. Bind push-button panels and PIR sensors to the appropriate groups and scenes. Test every control path from operator action to luminaire response.

6

Commission emergency lighting and hand over

Run the first BS 5266 functional and discharge tests on Part 202 emergency converters via the DALI bus. Save the commissioning backup file. Produce the EIC under BS 7671:2018+A4:2026, the DALI commissioning report, and the as-installed drawing. Hand all three to the client along with the backup file.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Certify your DALI install to BS 7671:2018+A4:2026

The Elec-Mate platform produces the EIC, EICR, Minor Works Certificate and emergency lighting commissioning documentation that sit alongside a DALI installation — aligned to BS 7671:2018+A4:2026, BS EN 62386 and BS 5266. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy