The UK EICR market has grown significantly since the Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020 made periodic inspections a legal requirement for all privately rented properties. The mandatory interval is every 5 years for private rented properties in England. For owner-occupied domestic properties, BS 7671 and GN3 recommend a maximum interval of 10 years (or on change of occupancy). Commercial premises are typically inspected every 5 years or sooner based on risk assessment. With approximately 4.4 million private rented households in England alone, the demand for EICR certificates is substantial and recurring.
This demand has created both opportunity and pressure. Electricians who price their EICRs correctly can build a profitable, predictable revenue stream. Those who undercharge — either to win work or because they do not account for the full cost of their time — risk burning out on high-volume, low-margin work.
The prices below are based on 2026 market rates across the UK. London and South East prices are typically 10 to 25% higher. Rural areas and Scotland tend to be at the lower end. These figures are for the inspection and report only — remedial work is additional.
Before you set a price, it helps to be clear about what a compliant EICR actually involves. A periodic inspection (BS 7671 Chapter 65) applies the test methods of Chapter 64, carried out circuit by circuit in the prescribed sequence — and these are the reason a thorough inspection takes hours, not minutes:
Continuity of conductors
Reg 643.2Protective conductors, ring final circuit continuity (R1 + R2), and bonding.
Insulation resistance
Reg 643.3Between live conductors and between live conductors and earth.
Polarity
Reg 643.6Confirming correct connection at the origin and throughout the installation.
Earth fault loop impedance (Zs)
Reg 643.7.3Measured and checked against the disconnection-time limits in Chapter 41.
Prospective fault current
Reg 643.7.3.201Determined at the origin and other relevant points in the installation.
Functional testing
Reg 643.10Operation of main switches, RCDs and AFDDs proven to work.
An electrician quoting £60 to £80 cannot do all of this on every circuit and still make a living — the cheapest quote almost always means corners are cut. Pricing your EICR fairly is about being paid for the work the standard actually requires.