BS 7671:2018+A4:202670 Calculators Included

How to Size Cables to BS 7671

The complete step-by-step guide to cable sizing using BS 7671:2018+A4:2026 Appendix 4 tables. Current carrying capacity, correction factors, voltage drop verification, and fault current withstand — with worked examples.

The 6-Step Cable Sizing Process

1

Determine the Design Current (Ib)

The design current is the current the cable must carry in normal service. Calculate it from the load:

Single-phase: Ib = P ÷ (V × cosφ)

Three-phase: Ib = P ÷ (√3 × VL × cosφ)

For a 7.4kW electric shower on a 230V single-phase supply (power factor 1.0): Ib = 7,400 ÷ (230 × 1.0) = 32.2A

2

Select the Protective Device (In)

Choose a protective device with rated current In ≥ Ib. Standard MCB ratings: 6, 10, 16, 20, 25, 32, 40, 50, 63A.

For our 32.2A shower: the next standard rating up is 40A Type B MCB.

Tip: Select the MCB type based on the load. Type B for general circuits (trips at 3-5× rated current). Type C for motors (5-10×). Type D for transformers and high inrush loads (10-20×).

3

Apply Correction Factors & Calculate It

This is where most mistakes happen. You must account for conditions that reduce the cable's ability to dissipate heat:

It = In ÷ (Ca × Cg × Ci × Cc)

Ca — Ambient Temperature (Table 4B1): At 30°C = 1.0. At 35°C = 0.94. At 40°C = 0.87. At 45°C = 0.79.

Cg — Grouping (Table 4C1): 2 circuits = 0.80. 3 circuits = 0.70. 4 circuits = 0.65. 6 circuits = 0.57. 9 circuits = 0.50.

Ci — Thermal Insulation: Cable touching insulation on one side = 0.89. Fully enclosed in insulation (over 0.5m) = 0.50.

Cc — Semi-enclosed Fuses: 0.725 for BS 3036 fuses. 1.0 for MCBs and RCBOs (no correction needed).

For our shower: installed alone (Cg = 1.0), in a 35°C loft (Ca = 0.94), touching insulation one side (Ci = 0.89), MCB protection (Cc = 1.0):

It = 40 ÷ (0.94 × 1.0 × 0.89 × 1.0) = 40 ÷ 0.8366 = 47.8A

4

Select Cable from Appendix 4

Find a cable with current-carrying capacity Iz ≥ It (47.8A) from the correct table for your installation method and cable type.

For twin and earth in an enclosed space (Reference Method A), from Table 4D5A column 6:

Cable SizeIz (Method A)Suitable?
6mm²32ANo (32 < 47.8)
10mm²43ANo (43 < 47.8)
16mm²57AYes (57 ≥ 47.8)

Result: 16mm² twin and earth for this installation. However, if using Reference Method C (clipped direct), 10mm² may suffice as Iz = 52A for that method.

Common Mistake: Using the wrong installation method. Reference Method A (enclosed in insulated wall) has much lower ratings than Method C (clipped direct). Check the actual route the cable will take — use the worst-case method for any portion of the run.

5

Verify Voltage Drop

Check the cable selection meets BS 7671 voltage drop limits: 3% for lighting (6.9V from 230V) and 5% for power (11.5V from 230V). Use the cable sizing calculator to automate these checks.

VD = mV/A/m × Ib × L ÷ 1000

For 10mm² T&E (clipped direct), the mV/A/m value from Appendix 4 is 4.4. With Ib = 32.2A and a 12m cable run:

VD = 4.4 × 32.2 × 12 ÷ 1000 = 1.7V (0.74% of 230V)

1.7V is well within the 5% power limit (11.5V). Compliant.

6

Verify Fault Current Withstand

The final check ensures the cable can withstand a short circuit without damage. Use the adiabatic equation:

k²S² ≥ I²t

k = 115 (PVC/copper line conductor) | S = cable CSA in mm² | I = prospective fault current | t = disconnection time

For 10mm² cable, fault current 3kA, 40A MCB disconnecting in 0.1s:

k²S² = 115² × 10² = 13,225 × 100 = 1,322,500

I²t = 3,000² × 0.1 = 9,000,000 × 0.1 = 900,000

1,322,500 ≥ 900,000 Compliant

Worked Example Summary

Load: 7.4kW electric shower

Design current (Ib): 32.2A

Protective device: 40A Type B MCB

Conditions: 35°C loft, touching insulation one side

Required It: 47.8A

Cable selected: 10mm² T&E (clipped direct, Iz = 52A)

Voltage drop: 1.7V (0.74%) — compliant

Fault withstand: k²S² > I²t — compliant

Skip the Manual Calculations

Elec-Mate's cable sizing calculator does all 6 steps in seconds. Every BS 7671 table is built in — just enter your load, conditions, and cable run length.

All BS 7671 Tables Built In

Appendix 4 current-carrying capacity tables, correction factor tables, and mV/A/m values — no flipping through the brown book.

Automatic Derating

Enter ambient temperature, grouping, and insulation conditions. The calculator applies Ca, Cg, Ci, and Cc automatically.

Voltage Drop Verification

Checks your cable selection against BS 7671 voltage drop limits: 3% for lighting (6.9V) and 5% for power (11.5V) from a 230V supply.

Fault Current Check

Verifies the cable can withstand fault current using the adiabatic equation (k²S² ≥ I²t) so your design is fully compliant.

Every Cable Type

Twin and earth, singles in conduit, SWA, MICC, fire-resistant, flexible — all installation methods from Reference A to G covered.

Complete Circuit Schedule

Generates a full circuit schedule with cable size, protection device, voltage drop, and Zs values for your certificates.

Inside the App

What You Get Inside Elec-Mate

The cable sizing calculator is one of 70+ calculators inside the complete platform. Here's what else is waiting for you:

70 Electrical Calculators

Cable sizing is one of 70+ calculators. Also includes voltage drop, Zs lookup, diversity, max demand, conduit fill, and 64 more.

AI Circuit Designer

Describe your job and the AI designs the complete circuit — cable sizes, protection devices, voltage drop, and Zs verification. All BS 7671 compliant.

16 Certificate Types

EICR, EIC, Minor Works, EV Charger, Emergency Lighting, Fire Alarm, Solar PV, and PAT — auto-filled, digitally signed, PDF exported.

36+ Training Courses

18th Edition, Level 2, Level 3, AM2, EPA, Inspection & Testing, plus 16 H&S courses. All with mock exams and AI study tools.

BS 7671:2018+A4:2026

Every calculator, every AI agent, every course — updated to the latest Amendment 4 (issued July 2024). No outdated references.

8 Elec-AI Specialists

Circuit Designer, Cost Engineer, Health & Safety, Installation Guide, Commissioning, Board Reader, Portfolio Analyser, and AI Assistant.

Why Elec-Mate, Not YouTube or Google?

Free resources are great for learning. But when you're on site, quoting a job, or filling in a certificate, you need tools that work \u2014 not a 45-minute video.

AI Trained for UK Electrical

Not a generic chatbot. AI specialists trained specifically on BS 7671:2018+A3:2024, GN3, CDM 2015, and thousands of real UK electrical scenarios.

Works Offline, On Site

No signal in a basement? On a scaffold? In a plant room? Elec-Mate works offline. YouTube and Google don’t.

Always Up to Date

YouTube videos from 2019 still reference the 17th Edition. Elec-Mate is updated to BS 7671:2018+A3:2024 (Amendment 4, issued July 2024).

Calculations Done for You

70+ calculators with all BS 7671 tables built in. No manual formula work, no spreadsheet errors, no hunting through Appendix 4.

Everything in One Place

Certificates, calculators, training, AI tools, business management — all integrated. No jumping between 10 different websites and apps.

Professional Output

Generate BS 7671 compliant certificates, RAMS, cost estimates, and PDF reports automatically. Try doing that from a YouTube tutorial.

Cable Sizing Calculator Built for UK Electricians

Elec-Mate's digital EICR and test certificates make inspection reporting faster and more professional — and all 70+ calculators…

Try Elec-Mate free
Download on the App StoreGet it on Google Play

Frequently Asked Questions

What is the cable sizing process to BS 7671?

Cable sizing to BS 7671 follows four steps: (1) Determine the design current (Ib) from the load. (2) Select a protective device with rated current In ≥ Ib. (3) Calculate the tabulated current rating It by dividing In by all applicable correction factors (ambient temperature, grouping, thermal insulation, semi-enclosed fuse). (4) Select a cable from BS 7671 Appendix 4 with current-carrying capacity Iz ≥ It. Then verify voltage drop and fault current withstand. Elec-Mate’s cable sizing calculator does all of this automatically with every BS 7671 table built in.

What are the BS 7671 correction factors for cable sizing?

There are four correction factors: Ca (ambient temperature — from Table 4B1, e.g. 0.87 at 40°C for 70°C PVC), Cg (grouping — from Table 4C1, e.g. 0.70 for 3 circuits touching on a surface), Ci (thermal insulation — 0.5 if fully surrounded, 0.89 if one side only), and Cc (semi-enclosed fuse factor — 0.725 for BS 3036 fuses). These multiply together: It = In ÷ (Ca × Cg × Ci × Cc).

What are the voltage drop limits in BS 7671?

BS 7671 limits voltage drop to 3% for lighting circuits and 5% for all other circuits, measured from the origin of the installation. From a 230V single-phase supply, that’s 6.9V for lighting and 11.5V for power. For three-phase 400V supplies, it’s 12V for lighting and 20V for power. Voltage drop is calculated as: VD = mV/A/m × Ib × L ÷ 1000, where mV/A/m comes from Appendix 4 tables.

How do I check fault current withstand for a cable?

Use the adiabatic equation: k²S² ≥ I²t, where k is the cable factor (115 for PVC/copper line conductor, 143 for PVC/copper CPC), S is the cross-sectional area in mm², I is the prospective fault current in amps, and t is the disconnection time of the protective device in seconds. If k²S² is greater than or equal to I²t, the cable can withstand the fault. Elec-Mate calculates this automatically.

What cable size do I need for a 32A ring circuit?

A standard domestic ring final circuit uses 2.5mm² twin and earth cable with a 32A Type B MCB. This is suitable for a maximum floor area of 100m². The cable has a current-carrying capacity of 27A per leg (Reference Method C), but because it’s a ring, both legs share the load. Always check voltage drop for longer cable runs and apply derating factors if cables are grouped or in thermal insulation.

Do I need to derate cables in thermal insulation?

Yes. If a cable is enclosed in thermal insulation for more than 0.5m, you must apply correction factor Ci. For cables totally surrounded by thermal insulation: Ci = 0.5 (a massive derating). For cables touching insulation on one side only: Ci = 0.89. This is one of the most commonly missed derating factors and can lead to undersized cables overheating. BS 7671 Regulation 523.9 covers this requirement.

Is Elec-Mate’s cable sizing calculator free?

Elec-Mate offers a 7-day free trial with full access to all 70+ calculators, 16 certificate types, 8 Elec-AI agents, and 46+ training courses. After the trial, plans start from £4.99/month. Cancel anytime — no contracts, no lock-in.

7-Day Free Trial — Cancel Anytime, No Hassle

Size Cables in Seconds, Not Minutes

Join 1,000+ UK electricians using Elec-Mate. 70+ calculators, 16 certificate types, 8 Elec-AI agents, and 46+ training courses — all BS 7671:2018+A4:2026 compliant.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy