Earthing & Protection — EV Charging Installation Practice

Free topic-focused mock exam: all 16 questions on Earthing & Protection, drawn from the wider EV Charging Installation bank. 35-minute timer, 70% to pass, worked explanation on every question. Use this when you've taken the full mock once and want to drill the topics you got wrong.

Questions
16
Time limit
35 min
Pass mark
70% · 12/16
Question bank
16

Free, no sign-up. Retake as many times as you like — the questions are reshuffled, with the answer order changed.

Sample questions

  1. 01Which residual current device characteristic must EV charging equipment provide to detect smooth DC residual currents?
    • ATime-delayed selective operation (Type S)
    • BPulsating DC sensitivity only (Type A)
    • CDetection of AC residual current only (Type AC)
    • DDetection of DC residual current (Type B or Type A with RDC-DD)

    Why: BS 7671 Section 722 requires protection against smooth DC residual current, satisfied either by a Type B RCD or by a Type A RCD combined with a 6mA residual direct current detecting device (RDC-DD to BS IEC 62955).

  2. 02Why does BS 7671 Section 722 impose special measures where an EV charge point is supplied from a PME (TN-C-S) earthing arrangement?
    • AA PME supply cannot achieve a low enough Zs for a 32A charge point circuit
    • BPME earthing forbids any earth electrode being installed at the premises
    • CPME earthing prevents the use of a Type A RCD with 6mA DC detection
    • DAn open PEN conductor could raise exposed metalwork to a dangerous voltage

    Why: On a PME supply an open-circuit PEN conductor can raise the charge point CPC and the vehicle bodywork to a dangerous potential, so Section 722 requires an additional protective measure such as a voltage-monitoring device or a TT earth electrode.

  3. 03What is the maximum permitted earth fault loop impedance (Zs) for a 32A Type B overcurrent device protecting an EV charging circuit at 230V?
    • A0.35Ω
    • B1.37Ω
    • C1.44Ω
    • D0.87Ω

    Why: For a 32A Type B MCB/RCBO at 230V the maximum Zs is 1.37Ω per BS 7671 Table 41.3, which incorporates the Cmin factor of 0.95; 1.44Ω is the older pre-Cmin figure.

Common questions

Is the Earthing & Protection mock exam free?

Yes — 100% free, no sign-up needed. Questions are pulled at random from a substantial bank, with a worked explanation on every question after you submit.

Can I retake the mock exam?

Yes. Every attempt picks a different random selection and reshuffles the options, so each retake gives you genuinely new questions. No limit on retakes.

Does this count towards the real qualification?

No — this is independent practice material. To gain the actual qualification you need to sit the official assessment through an approved provider.

Certificate types
16Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy