Motor Starter Installation UK: DOL, Star-Delta & VFD Guide
Everything UK electricians need to know about motor starter installation — DOL starters for small motors, star-delta for medium motors, VFDs for speed control, overload protection, forward/reverse control circuits, and commissioning documentation.
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer — DP Electrical
Key Takeaways
1DOL starters are suitable for motors up to 5.5 kW (some up to 7.5 kW) and draw 6–8 times full load current on starting — only acceptable where the supply can handle the inrush.
2Star-delta starters reduce starting current to approximately one-third of DOL, making them the standard choice for motors from 7.5 kW to 45 kW in industrial premises.
3Variable Frequency Drives (VFDs) provide fully controlled acceleration, speed control, and the lowest starting current — essential for pumps, fans, compressors, and conveyor systems.
4All motor circuits require overload protection set to the motor full load current (FLC) — typically a bi-metallic overload relay or electronic motor protection relay.
5Control circuits (24 VDC or 110 VAC SELV) must be segregated from power circuits, and all conductors must be labelled in accordance with BS 7671 and the installation drawings.
6Forward/reverse contactors must be mechanically and electrically interlocked to prevent simultaneous energisation, which would cause a phase-to-phase short circuit.
01 · Industrial Guide
Types of Motor Starters
Motor starters control the starting, stopping, and protection of electric motors. Choosing the correct starter type is essential — an undersized or incorrectly specified starter damages equipment, trips protection devices, and can cause supply voltage dips that affect neighbouring plant. The three principal starter types used in UK industrial installations are direct on-line (DOL), star-delta, and variable frequency drives (VFDs). Each has distinct characteristics, cost profiles, and application ranges.
DOL (Direct On-Line) — simplest and lowest cost. Motor connected directly to supply voltage. Starting current 6–8 × FLC. Suitable for motors up to approximately 5.5 kW where supply can absorb the inrush.
Star-Delta — motor windings connected in star during starting (reduces voltage per winding to 58%), then switched to delta for running. Reduces starting current to ~33% of DOL. Suitable for motors 7.5 kW to 45 kW.
VFD / Inverter Drive — converts AC to DC then back to variable frequency AC. Fully controlled acceleration ramp, speed control, and lowest starting current. Suitable for all motor sizes where speed control or soft-start is required.
Soft starters (electronic reduced voltage starters) are a fourth option for applications where speed control is not required but a smooth torque ramp is needed, particularly for conveyors and compressors. They reduce the voltage electronically during starting but run at fixed speed.
Free download
Get the BS 7671 A4:2026 Cheat Sheet — free
Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.
Every regulation change summarised
New model forms (EIC + MEIWC)
Free PDF — no subscription
02 · Industrial Guide
Direct On-Line (DOL) Starters
A DOL starter consists of a main contactor, an overload relay, and a control transformer or 24 VDC power supply. On pressing the start button, the control circuit energises the contactor coil, closing the main contacts and connecting the motor directly to the three-phase supply. The overload relay monitors current continuously; if current exceeds the set point for longer than the trip time characteristic, the relay opens its contact in the control circuit, de-energising the contactor.
Main contactor selection — rated by AC utilisation category. AC-3 (squirrel cage motors) is standard for DOL applications. The contactor must be rated for the motor kW rating and the associated making and breaking duty.
Overload relay setting — set to motor nameplate FLC (full load current in amps). Allow for Class 10 trip class for standard motors, Class 20 for high-inertia loads. The dial on bi-metallic relays is marked in amps; set precisely.
Short-circuit protection — a motor circuit breaker (MCB Type D or MCCB) upstream of the contactor provides short-circuit protection. Motor circuit breakers combine the MCB and overload relay function in a single device.
Control circuit — typically 24 VDC from a PELV power supply, or 110 VAC SELV from a control transformer. Start/stop pushbuttons, pilot lamps, and auxiliary contacts for interlocking wired in the control circuit.
03 · Industrial Guide
Star-Delta Starters
Star-delta starting is the most widely used reduced-voltage starting method for motors between 7.5 kW and 45 kW in UK industrial premises. The motor must have six terminals accessible (both ends of each winding) — motors wound for star-only connection cannot be used with star-delta starters.
Three contactors required — main contactor (KM1), star contactor (KM3, closed during starting), and delta contactor (KM2, closed during running). Mechanical interlock between star and delta contactors is mandatory.
Timer relay — an off-delay timer relay (typically 5–15 seconds) controls the star-to-delta transition. Setting too short causes excessive current spike at transition; setting too long causes the motor to run in star (drawing high current at load) before switching to delta.
Transition current spike — the open-circuit transition from star to delta causes a current transient that can exceed DOL starting current. Closed transition star-delta (with a resistor bank during switching) eliminates this but is more complex and expensive.
Overload relay position — fitted in the delta circuit (between KM2 contacts and motor terminals), not in the main line. This means the overload relay sees delta current (57.7% of line current). Set the overload relay dial to 58% of motor FLC, or use a relay with star-delta compensation.
Star-delta starters are not suitable for loads that require significant torque during starting (e.g., loaded conveyors, positive displacement pumps) because starting torque is reduced to one-third of DOL torque. For high-inertia or high-torque starting requirements, specify a VFD or soft starter.
04 · Industrial Guide
VFD / Inverter Drives
Variable Frequency Drives (VFDs), also called inverter drives or variable speed drives (VSDs), are now the preferred solution for motor control in most new industrial installations. They convert the incoming 50 Hz AC supply to DC (rectifier stage), then synthesise a variable frequency, variable voltage AC output (inverter stage) using pulse-width modulation (PWM).
Starting current — typically 100–150% of motor FLC during acceleration, compared to 600–800% for DOL. Acceleration ramp time is adjustable (typically 0–60 seconds) to match the load inertia and torque requirements.
Energy savings — for centrifugal loads (pumps, fans), reducing speed by 20% reduces power consumption by approximately 49% (affinity laws). VFDs pay for themselves rapidly in systems that run below full speed for significant periods.
Harmonic distortion — VFDs generate harmonic currents (primarily 5th and 7th harmonics) that can cause overheating in transformers and cables, and interfere with other equipment. Mitigate with line reactors, DC link reactors, or active front-end drives in large installations.
Motor cable length — PWM switching causes voltage reflections on long cables. Use screened motor cable and install an output reactor or dV/dt filter if cable length exceeds the VFD manufacturer's recommendation (typically 50–100 m without filtering).
Earthing the VFD — the VFD screen (EMC gland) must be bonded to the panel earth bar at both ends. The motor cable screen must be bonded at the VFD and at the motor terminal box. This is essential for EMC compliance and for protection against bearing currents in larger motors.
05 · Industrial Guide
Wiring and Control Circuits
Motor control panels are complex electrical assemblies that must comply with both BS 7671 (wiring of the fixed installation) and BS EN 61439 (the LV switchgear and controlgear assembly standard). Control circuit wiring requires particular care to ensure safe operation and to facilitate fault-finding.
Power and control segregation — run power conductors (400 V, motor leads) and control conductors (24 VDC or 110 VAC) in separate cable trays or conduit runs, physically separated by at least 50 mm or a metallic barrier. This prevents induced noise on control circuits.
Conductor identification — all conductors in the panel must be identified at every termination with ferrules marked to match the circuit diagram. Use the IEC colour code: brown/black/grey for three-phase, blue for neutral, green and yellow for earth. Control circuit conductors commonly use black or grey with numbered ferrules.
DIN rail layout — arrange devices logically from top to bottom: incoming isolator, MCBs/MCCBs, contactors, overload relays, control power supply, control terminal strip. Allow at least 25 mm clearance between device rows and provide sufficient cable duct capacity for the conductors.
Terminal blocks — use DIN rail-mounted terminal blocks for all external connections. Label terminal blocks with the circuit diagram reference. Provide separate terminal blocks for power (PE, L1, L2, L3, N) and control (common, start, stop, run indication, fault indication).
Try Elec-Mate free for 7 days
16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.
BS 7671 Regulation 552.1 requires that motors are protected against overload unless overload cannot occur (e.g., the motor is protected by its load characteristic) or where overload protection could cause a greater hazard than the overload itself (e.g., a fire pump that must run until it fails). In virtually all industrial installations, overload relays are required.
Bi-metallic overload relays — the standard solution for DOL and star-delta starters. Current through bi-metallic strips heats and deflects them, tripping the relay after a time that depends on the degree of overload. Set dial to motor nameplate FLC. Always test operation during commissioning.
Electronic motor protection relays — microprocessor-based relays that measure true RMS current on all three phases. Provide phase loss detection (single phasing protection), phase imbalance alarm, motor thermistor input (PTC), stall detection, and ground fault detection. Essential for pumps and compressors in unmanned locations.
Thermistor protection — motors in arduous duty (high ambient temperature, frequent starting) should be fitted with PTC thermistors in the stator windings. Connect the thermistor output to the motor protection relay for direct winding temperature monitoring independent of current measurement.
Resetting — after an overload trip, investigate and rectify the cause before resetting. Never manually force a contactor closed or bypass the overload relay. Repeated tripping without investigation leads to motor winding failure.
07 · Industrial Guide
Forward/Reverse Control Circuits
Many industrial applications require motors to run in both directions — lathes, hoists, conveyors, and valve actuators being common examples. Forward/reverse control requires two contactors wired to swap two of the three supply phases (swapping any two phases reverses a three-phase induction motor). The critical safety requirement is that both contactors must never be energised simultaneously.
Mechanical interlock — a physical bar or lever mechanism that prevents both contactors from closing simultaneously. This is a hard-wired mechanical safety measure, not dependent on the control circuit logic. Always use mechanically interlocked contactor pairs for forward/reverse.
Electrical interlock — auxiliary normally-closed (NC) contacts from each contactor wired in series with the opposing contactor coil circuit. If the forward contactor is energised, its NC auxiliary contact opens the reverse contactor circuit, providing a second layer of protection.
Stop before direction change — the control logic should require the motor to be stopped (and ideally allow time to decelerate) before selecting the opposite direction. Plugging (reversing a running motor) causes very high current and mechanical stress and should be avoided unless specifically designed for.
Limit switches — travel limit switches (position limit switches) should be wired to de-energise the relevant contactor when the mechanical limit of travel is reached, preventing damage to machinery. Use NC contacts wired in series with the contactor coil.
08 · Industrial Guide
Typical Applications by Starter Type
Correct starter selection depends not only on motor size but also on the load characteristics, duty cycle, and whether speed control or soft starting is required. The following guidance covers the most common UK industrial applications.
DOL starters — small workshop machinery (bench drills, grinders, lathes), small air compressors (up to 4 kW), roller shutter doors, small conveyor drives, exhaust fans, and sump pumps where motor size is within DOL limits.
Star-delta starters — medium air compressors (7.5–45 kW), large fans started unloaded, centrifugal pumps started against a closed valve, machine tools with large spindle motors, and industrial refrigeration compressors.
VFD drives — HVAC supply and extract fans (all sizes), chilled water pumps, cooling tower fans, variable-pressure hydraulic systems, conveyor systems requiring speed matching, extruder drives, mixers, and centrifuges.
Soft starters — loaded conveyor belts where VFD speed control is not required, large air compressors on fixed-speed systems, applications where smooth torque ramp is needed but speed variation is not required, and situations where VFD harmonics are a concern on isolated generators.
When specifying motor starters for new installations, document the load type, required starting torque, duty cycle (continuous, intermittent, or periodic), and ambient temperature. This information is needed to select the correct contactor AC utilisation category, overload relay trip class, and VFD derating if applicable.
09 · Industrial Guide
For Electricians: Motor Starter Commissioning and Documentation
Motor starter installation and commissioning is typically notifiable work under Part P of the Building Regulations for domestic premises, and requires an Electrical Installation Certificate (EIC) for all new motor circuits in commercial and industrial premises under BS 7671. Thorough commissioning records protect you and your client.
Issue the EIC On Site
Use the Elec-Mate EIC app to complete the Electrical Installation Certificate on your phone during commissioning. Record the overload relay setting, motor FLC, circuit protective conductor size, and test results — then export the PDF before you leave the site.
Quote VFD Upgrades on the Day
When servicing star-delta or DOL starters, calculate the energy savings from a VFD upgrade and quote immediately using the Elec-Mate quoting app. A VFD upgrade on a 15 kW pump running at 80% speed typically pays back in under two years — an easy sell to a facilities manager.
Motor circuit certification and quoting with Elec-Mate
Join 1,000+ UK electricians using Elec-Mate for on-site EIC completion, motor circuit test recording, and instant PDF export.
Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.
Fantastic app for electricians
I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.
Absolutely amazing
I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.
Trusted by electricians across the UK
Real feedback from real sparks
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer
Sole Trader · DP Electrical
“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”
Nathan Perry
Electrician · NP Electrical Services
“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”
Jake Pizey
3rd Year Apprentice · Apprentice
7-Day Free Trial — Cancel Anytime, No Hassle
Complete Motor Circuit EICs on Your Phone
Join 1,000+ UK electricians using Elec-Mate for on-site electrical installation certification, test result recording, and instant PDF export. 7-day free trial, cancel anytime.
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer, DP Electrical
From £6.99/mo after trial — less than a coffee a week
or download the app
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents
1,000+ electricians · From £6.99/mo after trial
We use cookies to improve the app and measure what works. Cookie Policy