BS 7671 Compliant

Cable Derating Calculator — Correction Factors Made Simple

Apply all four BS 7671 correction factors in seconds. Enter the ambient temperature, number of grouped circuits, insulation conditions, and protective device type. The calculator determines the required tabulated current carrying capacity (It) so you select the correct cable size every time.

Ca FactorCg FactorCi FactorCf Factor

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

9 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate
ShareXinW
Follow

Cable Derating Calculator

Calculate cable current carrying capacity with BS 7671 derating factors

Circuit Design (Optional)

A
A

From BS 7671 current capacity tables

K·m/W

Standard is 2.5 K·m/W

Iz = It × Ca × Cg × Ci × Cs where It is tabulated current, and C factors are derating corrections.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Cable derating adjusts the tabulated current carrying capacity (Iz) to account for real-world installation conditions that differ from the BS 7671 reference conditions.
  • 2Ca (ambient temperature factor) reduces the cable rating when ambient temperature exceeds the reference 30°C — for example, Ca = 0.87 at 40°C for 70°C thermoplastic cable.
  • 3Cg (grouping factor) accounts for mutual heating between cables installed together — six circuits in conduit gives Cg = 0.57, nearly halving the permitted current.
  • 4Ci (thermal insulation factor) applies when cables are enclosed in thermal insulation — a cable totally surrounded for more than 0.5m receives a 0.5 derating factor.
  • 5Cf (semi-enclosed fuse factor) of 0.725 applies when protection is by BS 3036 rewirable fuses, because their fusing factor allows currents up to twice the rated value before disconnection.

What Is Cable Derating?

Content verified against BS 7671:2018+A4:2026 by a JIB-registered electrician.

How do you calculate cable derating?

Identify the four BS 7671 correction factors for your installation: Ca (ambient temperature), Cg (grouping), Ci (thermal insulation) and Cf (semi-enclosed fuse). Multiply them together, then divide the protective device rating (In) by the result — It = In / (Ca × Cg × Ci × Cf). Select a cable whose tabulated capacity (Iz) for your reference method is at least equal to It.

Cable derating is the process of reducing the tabulated current carrying capacity of a cable to account for installation conditions that are less favourable than the reference conditions assumed in the BS 7671 tables. The current carrying capacity tables in Appendix 4 of BS 7671 assume a specific set of conditions: an ambient temperature of 30°C, a single circuit with no grouping, no thermal insulation in contact with the cable, and protection by an MCB or HRC fuse with a fusing factor close to 1.

When real-world conditions differ from these assumptions — and they almost always do — correction factors must be applied. Each factor adjusts the effective current carrying capacity of the cable. The combined effect of all applicable factors determines the minimum tabulated current (It) that the selected cable must have. This directly affects the cable sizing calculation and can mean the difference between a cable that runs safely within its thermal limits and one that overheats, degrades its insulation, and ultimately poses a fire risk.

Understanding and correctly applying these correction factors is one of the fundamental skills in electrical design. It is tested extensively in the City and Guilds 2391 examination and is a daily requirement for any electrician designing or verifying circuits to BS 7671.

Calculate Derating Factors Instantly

Enter your installation conditions and the calculator applies all four correction factors automatically.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Ca — Ambient Temperature Correction Factor

The ambient temperature correction factor (Ca) adjusts the cable rating for installations where the surrounding air temperature differs from the reference temperature. For cables in air, the reference temperature is 30°C. For cables buried directly in the ground, the reference temperature is 20°C.

The Ca values are found in BS 7671 Tables 4B1 (for cables in air) and 4B2 (for cables in the ground). Higher ambient temperatures reduce the cable rating because the cable cannot dissipate heat as effectively when the surrounding air is already warm. Conversely, temperatures below the reference value increase the permitted current slightly.

Ca values from Table 4B1 — 70°C thermoplastic (PVC) vs 90°C thermosetting (XLPE):

Ambient temperature70°C thermoplastic90°C thermosetting
25°C1.031.04
30°C (reference)1.001.00
35°C0.940.96
40°C0.870.91
45°C0.790.87
50°C0.710.82
55°C0.610.76
60°C0.500.71

90°C thermosetting (XLPE/LSOH) cable derates far less aggressively at high temperatures, which is one reason it is preferred in hot locations such as plant rooms and beneath PV modules.

In most UK domestic installations, the ambient temperature is close to 30°C and Ca does not significantly affect the cable size. However, in plant rooms, boiler cupboards, roof spaces in summer, and commercial kitchens, temperatures of 35-45°C are common and Ca becomes a significant factor. The voltage drop calculator can also apply a temperature correction to the mV/A/m values for more accurate results on lightly loaded cables.

Solar PV installations — BS 7671 Reg 712.523.101 (A4:2026)

For cables subjected to direct heating from the underside of a PV module, BS 7671 Reg 712.523.101 (introduced in Amendment 4:2026) requires that the ambient temperature used for Ca derating shall be taken as at least 70°C, regardless of the actual measured air temperature. This mandatory requirement applies at the design and sizing stage, and also governs the minimum insulation temperature rating of cables selected for that location. Standard 70°C thermoplastic (PVC) cable is therefore not suitable beneath PV modules — XLPE or LSOH insulated cable rated to 90°C is the typical compliant solution.

Cg — Grouping Correction Factor

The grouping correction factor (Cg) accounts for the mutual heating effect when multiple cables or circuits are installed together. Cables generate heat when carrying current, and when they are grouped close together, they heat each other up. This reduces the ability of each cable to dissipate its own heat, so the current carrying capacity must be reduced.

The Cg values are found in BS 7671 Tables 4C1 through 4C5, depending on the installation arrangement. The factor depends on the number of circuits grouped together and the installation method (conduit, trunking, cable tray, clipped direct, etc.).

Cg values from Table 4C1 — bunched/enclosed vs single layer spaced on a perforated tray:

Circuits groupedBunched / enclosedSingle layer on tray
1 circuit1.001.00
2 circuits0.800.88
3 circuits0.700.82
4 circuits0.650.77
5 circuits0.600.75
6 circuits0.570.73
9 circuits0.500.72

Bunched factors apply when cables touch in conduit, trunking or clipped together; the single-layer column applies to multicore cables spaced on a perforated horizontal or vertical tray. No grouping factor is needed at all where horizontal spacing between cables exceeds twice their overall diameter.

Grouping is one of the most impactful correction factors. Six circuits in a single conduit reduces each cable's capacity to just 57% of its tabulated value. This is why cables in heavily loaded trunking runs often need to be larger than you might expect. The conduit fill calculator and trunking fill calculator work alongside the derating calculator to ensure both physical space and thermal capacity are adequate.

Ci — Thermal Insulation Correction Factor

The thermal insulation correction factor (Ci) applies when cables are in contact with or enclosed by thermal insulating material. Modern building regulations require high levels of thermal insulation, which means cables increasingly pass through or are surrounded by insulation in walls, ceilings, and loft spaces.

BS 7671 Regulation 523.9 provides the rules for cables in thermal insulation. The derating depends on the extent of contact with the insulation:

  • Totally surrounded for more than 0.5m: Ci = 0.5 — this is the most severe derating, halving the cable capacity.
  • One side in contact with insulation: Use Reference Method 100 (formerly 101/102), which is built into the current carrying capacity table values.
  • Short penetration through insulation: If the cable is totally surrounded for less than 0.5m, the derating depends on the length in insulation, as set out in the table below.

Derating for a cable totally surrounded for less than 0.5m (Appendix 4, Section 2.6):

Length in insulationDerating factor
50 mm0.88
100 mm0.78
200 mm0.63
400 mm0.51
500 mm or more0.50

These factors apply to conductors up to 10mm² in insulation with a thermal conductivity greater than 0.04 W/m·K. At 0.5m or more, the factor settles at 0.5 — the same as the fully enclosed case.

In practice, the most common scenario in domestic installations is flat twin and earth cable running through joist spaces where loft insulation lies over the cable. This is treated as one side in contact, and Reference Method 100 values are used from the tables. The Ci = 0.5 factor is reserved for cables that are genuinely enclosed in insulation — for example, a cable run through a fully insulated cavity wall where the insulation wraps around the cable on all sides.

All Four Correction Factors in One Calculator

Stop looking up Ca, Cg, Ci, and Cf values in separate tables. The derating calculator applies all factors automatically and recommends the minimum cable…

Try it free for 7 days
Download on the App StoreGet it on Google Play

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play

Cf — Semi-Enclosed Fuse Factor

The semi-enclosed fuse factor (Cf = 0.725) applies when the circuit is protected by a BS 3036 rewirable fuse. These fuses have a fusing factor of approximately 2, meaning they may not blow until the current reaches twice their rated value. This means the cable could be carrying significantly more current than the fuse rating for an extended period before the fuse operates.

To compensate, the cable must be rated higher. The Cf factor of 0.725 effectively increases the required tabulated current carrying capacity by approximately 38%. For example, if the protective device is a 30A BS 3036 fuse, the required It = 30 / (Ca x Cg x Ci x 0.725), which gives a significantly larger cable than would be needed with an MCB or HRC fuse.

BS 3036 fuses are still found in older installations but are rarely specified for new work. If you encounter them during an EICR inspection, you need to verify that the cables are adequately rated with the Cf factor applied. The Elec-Mate derating calculator makes this straightforward — select BS 3036 as the protective device type and the 0.725 factor is applied automatically.

The current-carrying capacity requirements that the correction factors serve sit in Section 523 of BS 7671. During periodic inspection and testing (Chapter 65), an inspector assessing an installation has to satisfy themselves that conductors were selected with adequate current-carrying capacity for the conditions — which in practice means that all applicable correction factors (Ca, Cg, Ci, and Cf) were correctly applied at the design stage. Correct cable derating is therefore not just a design obligation but a judgement that feeds directly into the EICR coding decision when an undersized circuit is found.

Combining All Correction Factors

When more than one correction factor applies — which is the case in almost every real-world installation — the factors are multiplied together to give the overall correction. The required tabulated current carrying capacity is then:

It = In / (Ca x Cg x Ci x Cf)

It = required tabulated current carrying capacity

In = nominal rating of the protective device

Ca, Cg, Ci, Cf = correction factors as applicable

For example, consider a circuit protected by a 32A Type B MCB, with 4 circuits grouped in trunking (Cg = 0.65), at an ambient temperature of 35°C (Ca = 0.94), with no thermal insulation (Ci = 1.0) and no BS 3036 fuse (Cf = 1.0):

It = 32 / (0.94 x 0.65 x 1.0 x 1.0) = 32 / 0.611 = 52.4A

The selected cable must have a tabulated Iz of at least 52.4A for the relevant reference method. This is significantly higher than the 32A device rating, demonstrating how correction factors can substantially increase the required cable size.

The Elec-Mate electrical calculator suite links the derating calculator directly to the cable sizing tables, so once you have your It value, the recommended cable size is displayed immediately.

How to Apply Cable Derating Factors

Six steps to calculate the required tabulated current carrying capacity using BS 7671 correction factors.

1

Determine the protective device rating

Note the nominal current rating (In) of the protective device for the circuit — for example, 20A, 32A, or 40A. This is the starting value for the calculation.

2

Measure or estimate the ambient temperature

Determine the maximum ambient temperature in the cable route. For most domestic installations, 30°C is standard. For plant rooms, commercial kitchens, or roof spaces, measure the actual temperature and look up the Ca value from BS 7671 Table 4B1.

3

Count the grouped circuits

Count the number of circuits grouped together in the same conduit, trunking, or cable run. Look up the Cg value from Tables 4C1-4C5 based on the number of circuits and arrangement method.

4

Assess thermal insulation contact

Determine whether the cable is in contact with thermal insulation. If totally surrounded for more than 0.5m, apply Ci = 0.5. If one side is in contact, use Reference Method 100 values from the tables.

5

Check the protective device type

If the protective device is a BS 3036 semi-enclosed (rewirable) fuse, apply Cf = 0.725. For MCBs, RCBOs, and cartridge fuses, Cf = 1.0 (no additional derating needed).

6

Calculate It and select the cable

Divide the protective device rating (In) by the product of all applicable correction factors to get It. Select a cable from the BS 7671 Appendix 4 tables with a tabulated Iz value equal to or greater than It for your installation reference method.

Cable Derating Calculator Features

Every BS 7671 correction factor table at your fingertips, with automatic calculations and cable recommendations.

Automatic Ca Lookup

Enter the ambient temperature and cable insulation type. The calculator looks up the correct Ca value from BS 7671 Tables 4B1/4B2 automatically.

Grouping Factor Tables

Select the number of circuits and arrangement method. All grouping tables from 4C1 to 4C5 are built in, covering conduit, trunking, cable tray…

Insulation Assessment

Specify the thermal insulation conditions. The calculator applies Ci = 0.5 for enclosed cables or selects Reference Method 100 for one-sided contact…

BS 3036 Fuse Detection

Select the protective device type and the 0.725 factor is applied when a BS 3036 rewirable fuse is specified. MCBs and HRC fuses are handled with Cf = 1.0.

Instant It Calculation

All factors are multiplied together and the required tabulated current (It) is calculated instantly.

Works Offline on Site

All BS 7671 correction factor tables are stored locally. Calculate derating factors in any location with no internet connection required.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Calculate derating factors in seconds

Join 1,000+ UK electricians using Elec-Mate for BS 7671 cable sizing and derating. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy