In TN systems — which include TN-S (separate neutral and earth) and TN-C-S (PME / combined neutral and earth) — the earth fault return path is through the metallic sheath or PEN conductor back to the transformer. This provides a low-impedance fault loop, meaning relatively high fault currents flow during an earth fault.
Because fault currents are high in TN systems, overcurrent protective devices (MCBs and fuses) can generally provide disconnection within the required times. The key is to verify that the actual earth fault loop impedance (Zs) at the furthest point of the circuit does not exceed the maximum value tabulated in BS 7671 for the specific protective device type and rating.
For example, a 32A Type B MCB in a TN system requires a maximum Zs of 1.37 ohms to disconnect within 0.4 seconds (Table 41.3 of BS 7671). If the measured Zs at the furthest socket on the ring final circuit exceeds 1.37 ohms, the MCB will not trip quickly enough and the circuit fails the disconnection time test. You would need to either reduce the circuit impedance (shorter cables, larger CPC) or add supplementary protection such as an RCD.
BS 7671 Regulation 411.3.3 (A4:2026) requires 30 mA RCD additional protection for all socket outlets rated up to 32 A, regardless of whether the overcurrent device meets the disconnection time on its own. In domestic premises this is an absolute requirement. In non-dwellings, the RCD may be omitted only where a documented risk assessment determines that RCD protection is not necessary — omission without that assessment is a non-compliance on an EICR.
A4:2026 also introduces Regulation 411.3.4, which requires additional protection by a 30 mA RCD for AC final circuits supplying luminaires in domestic premises. This is a new requirement — lighting circuits in dwellings that were previously unprotected by an RCD will now be coded C2 on an EICR if no RCD is present. When verifying disconnection times for lighting circuits in domestic properties, also confirm 30 mA RCD protection is in place.