BS 7671 Compliant

Disconnection Time Calculator — Verify 0.4s and 5s Rules to BS 7671

Check whether your protective devices will disconnect within the required time under earth fault conditions. Enter the earth fault loop impedance (Zs), select the protective device, and instantly verify compliance with BS 7671 Regulation 411 — 0.4s for socket-outlet circuits up to 63A, 0.4s for fixed-load final circuits up to 32A, and 5s for distribution circuits — for both TN and TT systems.

0.4s & 5s RulesBS 7671 CompliantTN & TT SystemsZs Verification

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

10 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate
ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1BS 7671 Regulation 411.3.2 requires disconnection within 0.4 seconds for final circuits rated up to 63A in TN systems, and 0.2 seconds for TT systems.
  • 2Distribution circuits and circuits exceeding 63A are permitted a maximum disconnection time of 5 seconds in TN systems, provided all exposed-conductive-parts are connected within the same protective equipotential bonding system.
  • 3The maximum permitted earth fault loop impedance (Zs) for each protective device and disconnection time is tabulated in BS 7671 Tables 41.2 to 41.6.
  • 4TT systems rely on RCDs for disconnection because the earth fault loop impedance through the general mass of earth is too high for overcurrent devices alone.
  • 5The Elec-Mate calculator checks Zs against tabulated maximums for your specific protective device type and rating, giving instant pass/fail results on site.
  • 6On-site cold Zs measurements must be multiplied by 0.8 (GN3 site factor) before comparing against BS 7671 Table 41.3 values — for example, a Type B 32A MCB has a table maximum of 1.37 ohms but a cold-measurement site limit of 1.10 ohms.
  • 7A4:2026 Regulation 411.3.4 introduces a new requirement: 30 mA RCD protection is now mandatory for AC final circuits supplying luminaires in domestic premises — unprotected domestic lighting circuits are a C2 code on an EICR.

What Is Disconnection Time and Why Does It Matter?

Disconnection time is the maximum duration a protective device is permitted to take to disconnect the supply under earth fault conditions. When a live conductor comes into contact with exposed conductive parts (such as a metal appliance casing), fault current flows through the earth fault loop. The protective device must interrupt this current quickly enough to prevent a person receiving a lethal electric shock.

BS 7671:2018+A4:2026 sets specific disconnection time limits based on the type of circuit and the earthing system in use. The fundamental requirement comes from Regulation 411.3.2, which states that protective devices must disconnect the supply within the times specified in Table 41.1. These times are derived from the IEC body current curves — the relationship between current magnitude, duration, and the likelihood of ventricular fibrillation.

Getting disconnection time wrong has serious safety consequences. If a device takes too long to disconnect, anyone touching exposed metalwork during a fault could receive a sustained electric shock. The earth fault loop impedance determines the magnitude of fault current, and the protective device characteristics determine how quickly it disconnects at that current level. Both must be verified.

Verify Disconnection Times Instantly

Enter your measured Zs value and select the protective device. The calculator checks against BS 7671 tables and gives a clear pass/fail result in seconds.

Try it free for 7 days
Download on the App StoreGet it on Google Play

BS 7671 Disconnection Time Requirements

The maximum disconnection times are defined in BS 7671 Table 41.1 and depend on the nominal voltage and earthing system. For a 230V single-phase supply — the standard UK domestic supply — the requirements are:

TN Systems — 0.4 seconds

For final circuits not exceeding 63A with one or more socket outlets, or for final circuits supplying portable equipment intended to be held in the hand during use.

TN Systems — 5 seconds

For distribution circuits and circuits exceeding 63A. This longer time is permitted because these circuits typically do not supply equipment that people hold or touch directly.

TT Systems — 0.2 seconds

For final circuits not exceeding 63A. TT systems require faster disconnection because touch voltages can exceed 50V more readily due to the higher earth electrode resistance.

These disconnection times apply to circuits where the protection against electric shock is provided by automatic disconnection of supply (ADS), which is the most common protective measure in UK installations. The cable sizing calculator and disconnection time calculator work together to ensure both thermal protection and shock protection are satisfied.

Disconnection in TN Systems (TN-S and TN-C-S)

In TN systems — which include TN-S (separate neutral and earth) and TN-C-S (PME / combined neutral and earth) — the earth fault return path is through the metallic sheath or PEN conductor back to the transformer. This provides a low-impedance fault loop, meaning relatively high fault currents flow during an earth fault.

Because fault currents are high in TN systems, overcurrent protective devices (MCBs and fuses) can generally provide disconnection within the required times. The key is to verify that the actual earth fault loop impedance (Zs) at the furthest point of the circuit does not exceed the maximum value tabulated in BS 7671 for the specific protective device type and rating.

For example, a 32A Type B MCB in a TN system requires a maximum Zs of 1.37 ohms to disconnect within 0.4 seconds (Table 41.3 of BS 7671). If the measured Zs at the furthest socket on the ring final circuit exceeds 1.37 ohms, the MCB will not trip quickly enough and the circuit fails the disconnection time test. You would need to either reduce the circuit impedance (shorter cables, larger CPC) or add supplementary protection such as an RCD.

BS 7671 Regulation 411.3.3 (A4:2026) requires 30 mA RCD additional protection for all socket outlets rated up to 32 A, regardless of whether the overcurrent device meets the disconnection time on its own. In domestic premises this is an absolute requirement. In non-dwellings, the RCD may be omitted only where a documented risk assessment determines that RCD protection is not necessary — omission without that assessment is a non-compliance on an EICR.

A4:2026 also introduces Regulation 411.3.4, which requires additional protection by a 30 mA RCD for AC final circuits supplying luminaires in domestic premises. This is a new requirement — lighting circuits in dwellings that were previously unprotected by an RCD will now be coded C2 on an EICR if no RCD is present. When verifying disconnection times for lighting circuits in domestic properties, also confirm 30 mA RCD protection is in place.

The calculators live where your certs and quotes are

Run the calc, fill the certificate, and price the job in the same app — 70+ calculators, 16 certificate types, quoting with AI cost estimation. From £6.99/mo.

Start free 7-day trial
Download on the App StoreGet it on Google Play

Disconnection in TT Systems

TT earthing systems use a local earth electrode (typically an earth rod) for the installation's earth connection, with the fault return path running through the general mass of earth. The resistance of this earth path is significantly higher than in TN systems — typically between 10 and 200 ohms for the earth electrode alone.

Because the earth fault loop impedance is so much higher in TT systems, the fault current is correspondingly lower. In most cases, the fault current in a TT system is insufficient to operate an MCB or fuse within the required disconnection time. This is why RCD protection is essential in TT installations — the RCD detects the imbalance between live and neutral caused by the earth fault current, and disconnects even when that current is relatively small.

For a 30mA RCD to disconnect within 0.2 seconds in a TT system, BS 7671 Table 41.5 requires the Zs to not exceed 1667 ohms (calculated as 50V / 0.03A). In practice, even the worst earth electrodes easily meet this requirement. The challenge in TT systems is not usually the Zs value but rather ensuring the RCD is correctly installed, functioning properly, and regularly tested.

The Elec-Mate electrical testing calculators include specific TT system verification, checking the earth electrode resistance (Ra), the total Zs, and confirming the RCD will operate within the required time.

TN and TT System Calculations Built In

The disconnection time calculator handles both TN and TT earthing systems. Select your system type, enter Zs…

Try it free for 7 days
Download on the App StoreGet it on Google Play

Protective Device Coordination

Protective device coordination ensures that the correct device operates first during a fault — the device closest to the fault should disconnect before upstream devices. This is known as discrimination or selectivity. While discrimination is a separate topic from disconnection time, the two are closely related because both depend on the fault current magnitude and the device operating characteristics.

The maximum permitted Zs values for common protective devices at 0.4 seconds disconnection time in TN systems are tabulated in BS 7671 as follows:

  • Type B MCB 6A: Zs max = 7.28 ohms
  • Type B MCB 16A: Zs max = 2.73 ohms
  • Type B MCB 32A: Zs max = 1.37 ohms
  • Type C MCB 32A: Zs max = 0.68 ohms
  • BS 88-2 gG fuse 32A: Zs max = 0.99 ohms (BS 88-3 system C 32A: 0.91 ohms)

GN3 Site Factor — apply 0.8 to your measured Zs

BS 7671 table values are based on conductors at their maximum operating temperature. When you measure Zs on site with cold cables, the reading is lower than it would be under load. GN3 guidance requires you to multiply your cold measured Zs by 0.8 before comparing against the table maximum. For example: a Type B 32A MCB has a table maximum of 1.37 Ω, but the on-site pass/fail limit for a cold measurement is 1.10 Ω (1.37 × 0.8). Similarly, Type B 6A: table 7.28 Ω, site limit 5.82 Ω; Type B 16A: table 2.73 Ω, site limit 2.18 Ω. A cold reading below the site limit confirms compliance.

When testing on site, you compare your measured Zs against these maximum values. The Elec-Mate calculator has all the tabulated values from Tables 41.2 through 41.6 built in, so you do not need to carry the regulation book. Simply select the device type and rating, enter the measured Zs, and the calculator tells you whether the circuit passes or fails.

The prospective fault current calculator complements this tool by verifying that the prospective fault current does not exceed the breaking capacity of the protective device — another critical BS 7671 requirement under Regulation 434.

How to Verify Disconnection Time

Five steps to check whether your protective device meets the BS 7671 disconnection time requirements.

1

Identify the earthing system

Determine whether the installation uses a TN-S, TN-C-S (PME), or TT earthing system. This affects the disconnection time requirements and the maximum permitted Zs values.

2

Determine the circuit type

Identify whether the circuit is a final circuit (up to 63A) or a distribution circuit. Final circuits with socket outlets require 0.4s in TN systems and 0.2s in TT systems. Distribution circuits allow 5 seconds.

3

Select the protective device

Note the type and rating of the protective device — for example, Type B MCB 32A, Type C MCB 20A, or BS 88 fuse 20A. Each device has a specific maximum Zs value for the required disconnection time.

4

Measure or calculate Zs

Measure the earth fault loop impedance at the furthest point of the circuit using a calibrated loop impedance tester. Alternatively, calculate Zs from Ze (external earth fault loop impedance) plus R1+R2 (circuit conductor impedances).

5

Compare against the BS 7671 maximum

Compare your measured Zs against the maximum value from the appropriate BS 7671 table. If Zs is less than or equal to the maximum, the disconnection time requirement is met. If it exceeds the maximum, corrective action is needed.

Disconnection Time Calculator Features

Everything you need to verify disconnection times to BS 7671 on any job site.

Instant Zs Verification

Enter the measured Zs and the protective device details. The calculator checks against BS 7671 Tables 41.2-41.6 and gives a clear pass/fail result.

0.4s and 5s Rule Checks

Automatically applies the correct disconnection time requirement based on the circuit type — 0.4s for final circuits…

TN and TT System Support

Handles both TN (TN-S, TN-C-S) and TT earthing systems with the correct disconnection time requirements and Zs limits for each.

All Device Types Covered

Includes maximum Zs values for Type B, C, and D MCBs, BS 88 fuses, BS 3036 fuses, and RCBOs at all standard current ratings.

BS 7671:2018+A4:2026 Data

All tabulated values are from the current edition of BS 7671 including Amendment 4 (2026). Verified against published regulation tables.

Works Offline on Site

The calculator runs entirely on your device with no internet connection required. Verify disconnection times in meter cupboards, basements…

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Verify disconnection times in seconds

Join 1,000+ UK electricians using Elec-Mate for BS 7671 compliance checks. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy