IET Code of Practice

EV Charger Load Calculator — Demand Assessment for Electric Vehicle Installations

Calculate the electrical load for EV charger installations. Single-phase 7kW, three-phase 22kW, or multiple charger sites with diversity. Check supply capacity, PME earthing requirements, and cable sizing in one integrated calculation.

EV InstallationsLoad AssessmentPME ChecksSmart Charging

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

11 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate
ShareXinW
Follow

EVSE Load Calculator

Calculate electrical load and infrastructure requirements

Charging Points

Add charging points to calculate EVSE load requirements

Supply & Installation

V
kW
m

Cable Derating (BS 7671)

Professional design required. Verify calculations with supply authority for commercial installations.

EVSE Load Formulas
I = P / (V × √3 × PF)
I= Design current (A)
P= Total diversified power (W)
V= Supply voltage (V)
PF= Power factor

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1A standard 7kW single-phase EV charger draws approximately 32A at 230V — equivalent to the load of a full ring final circuit and a significant addition to any domestic supply.
  • 2Three-phase 22kW chargers draw approximately 32A per phase at 400V, providing much faster charging but requiring a three-phase supply connection.
  • 3Load management (smart charging) systems can dynamically limit EV charger current to avoid exceeding the available supply capacity, as required by the 2022 EV chargepoint regulations.
  • 4For multiple EV chargers, diversity factors from the IET Code of Practice for Electric Vehicle Charging Equipment Installation allow reduced cable and supply sizing.
  • 5PME (TN-C-S) earthing requires additional protective measures for EV charging — either an earth electrode with protective equipotential bonding, or a charging unit with PEN fault detection.

EV Charger Electrical Loads Explained

Electric vehicle chargers place a substantial and sustained load on the electrical supply. Unlike most domestic appliances that cycle on and off or draw variable power, an EV charger draws a near-constant current for several hours — often overnight. Understanding these loads is essential for correct maximum demand assessment and supply capacity verification.

The most common domestic EV charger in the UK is a 7kW single-phase unit, which draws approximately 32A at 230V. This is a dedicated circuit requiring a 32A MCB or RCBO, 6mm² cable for most run lengths, and a Type A (or better) 30mA RCD. The charger typically runs for 4-8 hours per charge, depending on the vehicle battery capacity and state of charge.

For commercial and workplace installations, three-phase 22kW chargers are common. These draw approximately 32A per phase at 400V and can charge an EV in 1-3 hours. Rapid DC chargers (50kW and above) are typically limited to forecourt and public charging locations and require specialist power supplies beyond the scope of standard BS 7671 installation design.

The cable sizing calculator in Elec-Mate includes specific EV charger presets that account for the sustained nature of the load when sizing cables and selecting protective devices.

Calculate EV Charger Load Instantly

Enter the charger rating, supply type, and number of units. The calculator determines the total demand, recommends cable sizes…

Try it free for 7 days
Download on the App StoreGet it on Google Play

Single-Phase vs Three-Phase EV Charging

The choice between single-phase and three-phase EV charging depends on the available supply, the desired charging speed, and the cost implications. Most UK domestic properties have a single-phase 100A supply, which limits EV charging to 7kW maximum (32A at 230V).

Single-Phase (7kW)

  • 32A at 230V
  • 20-30 miles of range per hour
  • 6-8 hours for full charge (typical EV)
  • Available on all domestic supplies
  • 6mm² or 10mm² cable (depending on length)

Three-Phase (22kW)

  • 32A per phase at 400V
  • 60-80 miles of range per hour
  • 1-3 hours for full charge
  • Requires three-phase supply
  • 6mm² or 10mm² 4-core SWA cable

Not all electric vehicles can accept three-phase charging. Many popular models in the UK (including some Tesla variants) have single-phase onboard chargers limited to 7kW, even when connected to a three-phase supply. It is important to check the vehicle specification before recommending a three-phase charger installation. The three-phase power calculator can help verify the per-phase current for balanced and unbalanced loads.

Load Management and Smart Charging

The Electric Vehicles (Smart Charge Points) Regulations 2021, which came into force on 30 June 2022, require all new domestic and workplace EV chargepoints to be "smart" — capable of adjusting their charging rate in response to signals. From an electrical design perspective, load management is critical because it allows the charger to reduce its current draw when the total site load approaches the supply capacity.

There are two main types of load management:

  • Static Load Management

    The charger is set to a fixed maximum current that, combined with the estimated maximum demand of the rest of the installation, does not exceed the supply capacity. For example, on a 100A supply with an estimated existing load of 60A, the charger would be limited to 30-35A.

  • Dynamic Load Management

    A current transformer (CT clamp) on the main supply monitors the total site load in real time. The charger dynamically adjusts its current to use only the available spare capacity, ramping up when other loads reduce and throttling back when they increase.

Dynamic load management is the preferred approach because it maximises charging speed while preventing supply overload. The Elec-Mate calculator models both approaches and can determine whether load management is needed based on the existing maximum demand and the supply capacity.

Diversity for Multiple EV Chargers

When installing multiple EV chargers — for example, in a car park, housing development, or fleet depot — it is unrealistic to assume all chargers will be drawing full current simultaneously. Diversity factors allow the electrical design to account for the statistical likelihood that chargers will be used at different times and at varying power levels.

The IET Code of Practice for Electric Vehicle Charging Equipment Installation provides diversity factors based on the number of chargers:

  • 1 charger: 1.00 (no diversity)
  • 2 chargers: 0.80
  • 5 chargers: 0.60
  • 10 chargers: 0.50
  • 20 chargers: 0.40
  • 50+ chargers: 0.30

These factors significantly reduce the total demand calculation for multi-charger installations. For example, ten 7kW chargers without diversity would require a 70kW supply (approximately 300A at 230V). With a 0.50 diversity factor, the assessed demand drops to 35kW (approximately 150A), which may be feasible on an existing supply. The diversity factor calculator in Elec-Mate applies these factors automatically for multi-charger installations.

Multi-Charger Load Assessment Made Simple

Enter the number of chargers and their ratings. The calculator applies IET diversity factors and determines the total assessed demand for supply sizing.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play

PME Earthing Considerations for EV Charging

One of the most critical considerations for EV charger installations is the earthing arrangement. The majority of UK domestic properties use a TN-C-S (PME) earthing system, where the neutral and earth are combined in the supply cable (the PEN conductor) and separated at the origin of the installation.

PME earthing presents a specific risk for EV charging because the vehicle is simultaneously connected to the electrical supply (via the charging cable) and to true earth (via its tyres on the ground). If the PEN conductor were to become open circuit (a PEN fault), the vehicle body could rise to a dangerous potential relative to true earth.

The IET Code of Practice and BS 7671 Regulation 722.411.4.1 require additional protective measures when EV charging equipment is connected to a PME supply. The acceptable solutions include:

  • Earth electrode with protective equipotential bonding: Install a local earth electrode (earth rod) and connect it to the protective conductor of the EV circuit, providing a TT-like earth path independent of the PME system.
  • Charger with PEN fault detection: Some EV chargers include built-in PEN fault detection that disconnects the supply if a PEN conductor fault is detected. This eliminates the need for a separate earth electrode.

The Elec-Mate calculator flags PME earthing requirements automatically when you specify a TN-C-S earthing system and an EV charger installation. For more information on earthing arrangements, see our dedicated guide.

Assessing Supply Capacity

Before installing any EV charger, you must verify that the existing electrical supply has sufficient spare capacity to accommodate the additional load. A standard UK domestic supply is typically 60A or 100A single-phase, provided by the distribution network operator (DNO).

Adding a 7kW (32A) EV charger to a 60A supply is particularly challenging because the charger alone consumes more than half the total supply capacity. If the existing installation already draws 40-50A during peak demand (evening cooking, heating, lighting), the combined load would exceed the 60A supply. In this case, options include:

  • Requesting a supply upgrade from the DNO (from 60A to 100A, or from single-phase to three-phase)
  • Implementing dynamic load management to limit the charger when other loads are high
  • Reducing the charger current from 32A to a lower setting (e.g., 16A / 3.6kW)
  • Scheduling charging to off-peak hours when other loads are minimal

The maximum demand calculator helps you assess the existing installation demand, and the EV charger load calculator determines whether there is sufficient headroom for the charger. The results can be documented on the EIC certificate for the charger installation.

How to Assess EV Charger Load

Five steps to calculate the electrical load and design the supply for an EV charger installation.

1

Determine the charger specification

Note the EV charger power rating (typically 3.6kW, 7kW, 11kW, or 22kW), the supply type (single-phase or three-phase), and the number of units to be installed.

2

Assess the existing supply

Check the incoming supply capacity (main fuse rating), the earthing system (TN-S, TN-C-S, or TT), and the existing maximum demand. This determines how much spare capacity is available for the EV charger.

3

Calculate the total demand

Add the EV charger load to the existing maximum demand. For multiple chargers, apply the IET diversity factors. Check that the total demand does not exceed the supply capacity.

4

Check PME earthing requirements

If the earthing system is TN-C-S (PME), determine the additional protective measures needed — either a local earth electrode or a charger with PEN fault detection.

5

Size the cable and protective device

Select the cable size and MCB/RCBO rating for the EV charger circuit. A 7kW charger typically requires a 32A Type B MCB/RCBO and 6mm² cable, but check voltage drop for longer runs.

EV Charger Calculator Features

Complete EV charging installation design tool — from demand assessment to cable sizing.

EV Charger Load Calculation

Calculate the electrical load for 3.6kW, 7kW, 11kW, and 22kW EV chargers. Single-phase and three-phase options with automatic current calculation.

Diversity for Multiple Chargers

Apply IET Code of Practice diversity factors for multi-charger installations. Automatically reduces the assessed demand based on the number of chargers.

PME Earthing Assessment

Flags PME earthing requirements and recommends additional protective measures including earth electrode installation or PEN fault detection chargers.

Load Management Guidance

Determines whether static or dynamic load management is needed based on existing demand and supply capacity. Recommends the appropriate approach.

Cable and Device Sizing

Recommends cable sizes and protective device ratings for the EV charger circuit, including voltage drop verification for long cable runs.

Supply Capacity Check

Compares the total assessed demand against the available supply capacity and flags when a DNO supply upgrade may be required.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Design EV charger installations with confidence

Join 1,000+ UK electricians using Elec-Mate for EV charger load assessment and cable sizing. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy