INSTALLATION GUIDE

Electrical Installation Conduit — Complete UK Guide

Steel vs PVC conduit, BS EN 61386 classification, trunking fill calculations per BS 7671 Appendix 5, earthing requirements, IP ratings, and fire stopping — everything electricians need for compliant conduit installations.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

10 min readUpdated 2026-05-18Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Conduit is selected by material (steel or PVC), type (rigid or flexible), and installation environment. BS EN 61386 governs the performance classification of conduit systems using a four-digit code covering mechanical, thermal, electromagnetic and electrical properties.
  • 2Fill calculations for conduit and trunking must comply with BS 7671:2018+A4:2026 Appendix 5 and the associated cable factor tables. Overfilling conduit creates heat build-up and makes future cable changes impractical.
  • 3Steel conduit used as a circuit protective conductor (CPC) must be continuous throughout, with screwed fittings only — no push-fit joints are permissible. Cross-sectional area must be verified against BS 7671 Table 54.7.
  • 4Outdoor and underground conduit installations require appropriate IP-rated fittings and boxes. Buried conduit must meet BS 7671 Regulation 522.8.10 regarding depth and mechanical protection.
  • 5Fire stopping around conduit penetrations through fire-resisting structures is a legal requirement under Building Regulations Approved Document B and must be carried out with intumescent materials rated to match the element being penetrated.
01 · Installation Guide

Steel vs Plastic Conduit — Choosing the Right System

Conduit is one of the most widely used cable management systems in UK electrical installations, providing mechanical protection, a tidy finish, and — in the case of steel conduit — a circuit protective conductor path. The choice between steel and PVC conduit depends on the environment, mechanical demands, and whether the conduit is to serve as the CPC.

Steel Conduit

  • Material: Hot-dip galvanised or stove-enamelled mild steel. Standard sizes: 16mm, 20mm, 25mm, 32mm, 38mm, 50mm outside diameter. Conforms to BS EN 61386-21 (rigid steel conduit).
  • Advantages: Superior mechanical protection, fire resistance, can serve as CPC, EMC shielding for sensitive circuits, suitable for hazardous areas (with appropriate fittings), long service life.
  • Disadvantages: Heavier, more time-consuming to install, requires screwed fittings, susceptible to corrosion in wet environments unless stainless steel or galvanised grade is specified.
  • Typical applications: Industrial premises, plant rooms, exposed runs in commercial buildings, areas subject to mechanical impact.

PVC (Rigid Plastic) Conduit

  • Material: Unplasticised PVC (UPVC). Standard sizes: 16mm, 20mm, 25mm, 32mm outside diameter. Conforms to BS EN 61386-22 (rigid non-metallic conduit).
  • Advantages: Lightweight, corrosion-resistant, faster to install, lower material cost, push-fit or solvent-welded fittings available, no metallic continuity issues.
  • Disadvantages: Cannot serve as CPC (separate CPC required), less impact-resistant than steel, becomes brittle at low temperatures, melts in fire, requires separate bonding to exposed metalwork.
  • Typical applications: Domestic surface wiring, office installations, concealed runs in dry environments, underground ducts (heavy-duty grade).

Performance classification under BS EN 61386 uses a four-digit code. For most commercial and industrial applications, specify conduit classified to at least medium mechanical protection (third digit 3 or above). Always check the manufacturer data sheet against the installation environment requirements.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Installation Guide

Trunking Fill Calculations (BS 7671 Appendix 5)

Overloading conduit or trunking with too many cables is one of the most common installation defects identified on EICRs. The fill limits in BS 7671 Appendix 5 exist to ensure cables can dissipate heat safely and can be withdrawn and replaced without damage.

How to Calculate Conduit Fill

  • Step 1: Identify the cable type and conductor size for each cable to be installed. Look up the cable factor from BS 7671 Appendix 5 Table 5A (single-core PVC), Table 5B (multi-core PVC), or equivalent.
  • Step 2: Add up the cable factors for all cables to be installed in the conduit. This gives the total cable factor.
  • Step 3: Compare the total cable factor against the conduit factor from Table 5C. Use the straight run column for runs without bends, or the bend column if one or more bends are present. Select the conduit size whose factor exceeds the total cable factor.
  • Example: Six 2.5mm\u00b2 single-core PVC cables (factor 30 each) in a straight run = total factor 180. A 20mm conduit has a straight-run factor of 460. A 16mm conduit has a factor of 290. Either would accommodate the cables, but 20mm is preferred to allow future capacity.
  • Derating for grouping: Where cables are grouped together, the current-carrying capacity of each cable must be derated using BS 7671 Table 4C1 (for cables in conduit) or Table 4B1 (for trunking). This is separate from the fill calculation — both must be applied.
  • Trunking space factor: For cable trunking, BS 7671 Appendix 5 specifies that the ratio of the sum of cable cross-sectional areas to the internal trunking cross-sectional area (the space factor) should not exceed 45%. This applies to all new installations.

Always document your fill calculations as part of the installation records. If completing an , note the conduit sizes and cable quantities in the circuit schedule.

03 · Installation Guide

Bending and Cutting Techniques

Neat, correctly made bends are a mark of professional conduit installation. Poorly formed bends reduce the conduit internal cross-section, making cable pulling difficult and risking cable damage. The following techniques apply to both steel and PVC conduit.

Steel Conduit Bending

  • Use a purpose-made conduit bender (hickey bender) for 20mm and 25mm. For 32mm and above, a hydraulic bender is recommended. The minimum bending radius is 2.5 times the outside diameter for metal conduit per BS EN 61386.
  • Mark set distances accurately with a chinagraph pencil or felt tip. For a right-angle bend, measure from the end of the conduit to the centre of the bend, subtract the take-up (typically 100mm for 20mm conduit), and mark the bending point.
  • Cut steel conduit with a pipe slice or junior hacksaw. Deburr all cut ends with a conduit reamer before drawing cables — sharp edges will damage cable insulation. Bush all conduit entries to boxes with PVC or rubber bushes.

PVC Conduit Bending

  • Insert a correctly sized conduit spring inside the conduit before bending. For cold bending, lever the conduit gently over your knee — do not rush or the conduit will kink. Remove the spring by attaching a length of cord before insertion and pulling it free after bending.
  • For warm bending, apply a hot air gun evenly along the bend area (approximately 100mm length for 20mm conduit). Rotate the conduit to heat evenly. When pliable, bend over a former and hold until cool. Never use a naked flame.
  • Cut PVC conduit with a junior hacksaw or pipe cutter. Deburr with a file or deburring tool. Use solvent cement or push-fit couplers for jointing. Ensure push-fit joints are fully engaged — a partial joint will leak in wet environments and is mechanically weak.
04 · Installation Guide

Earthing of Steel Conduit

Steel conduit can be used as the circuit protective conductor (CPC) for circuits it contains, provided specific requirements under BS 7671:2018+A4:2026 Regulation 543 are met. This is a legitimate and widely used practice in industrial and commercial installations, but requires careful attention to jointing and continuity.

  • Screwed fittings only: Every joint in a conduit system used as a CPC must be made with screwed couplers and screwed-entry boxes. Push-fit or clip-together fittings do not provide reliable electrical continuity and must not be used where the conduit is the CPC.
  • Flexible conduit sections: Flexible conduit (also known as Anaconda or SWA flexible) does not provide reliable CPC continuity. A separate insulated CPC must be run inside flexible sections and connected at both ends.
  • Continuity testing: After installation, verify end-to-end continuity of the conduit system as a CPC. The resistance measured should be consistent with the cross-sectional area of the conduit and the length of run. Test at each circuit termination point.
  • Cross-sectional area check: Verify that the steel conduit provides sufficient CPC cross-sectional area per BS 7671 Table 54.7 for the phase conductor size. A 20mm steel conduit provides approximately 35mm\u00b2 equivalent CPC cross-section.

Where conduit runs are long or the fault current could be high, consider installing a separate insulated CPC inside the conduit in addition to relying on the steel for continuity. Record the CPC type used on the circuit schedule of the .

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
05 · Installation Guide

IP Ratings and Environmental Protection

Ingress Protection (IP) ratings define the degree of protection provided by conduit fittings and boxes against solid particles and liquids. The rating is defined in BS EN 60529 and consists of two digits — the first for solid particle protection (0–6), the second for liquid ingress protection (0–9).

  • IP2X: Protection against fingers and solid objects over 12mm. Minimum requirement for accessible indoor wiring accessories.
  • IP44: Dust protection (solid objects over 1mm) and splash protection from any direction. Minimum for outdoor above-ground conduit fittings and boxes in exposed locations.
  • IP65: Complete dust exclusion and protection against water jets from any direction. Required for conduit boxes in car washes, external walls exposed to direct rain, and food production areas.
  • IP67/IP68: Complete dust exclusion and temporary/permanent submersion protection. Required for underground junction boxes and conduit systems installed below ground level.

BS 7671 Regulation 522.3 requires that the installation method used provides adequate protection for the environment. Select conduit, fittings and boxes with IP ratings appropriate to the worst conditions they will encounter during the lifetime of the installation, not just during commissioning.

06 · Installation Guide

Fire Stopping Requirements

Every penetration through a fire-resisting wall, floor, or ceiling must be fire-stopped to maintain the element's fire resistance rating. This is a legal requirement under Building Regulations Approved Document B (England), Section 7 of the Technical Handbooks (Scotland), and Part B of the Building Regulations (Wales and Northern Ireland).

  • Steel conduit penetrations: Steel conduit does not melt or combust, so the main concern is any annular gap around the conduit. Pack with mineral wool and seal with intumescent mastic rated to match the wall's fire resistance (30, 60, or 90 minutes). Some manufacturers provide tested steel conduit sealing systems.
  • PVC conduit penetrations: PVC melts in fire, leaving an open hole. Intumescent collars must be fitted around PVC conduit at every penetration through a fire-resisting element. The collar expands on heating, sealing the gap left by the melting conduit. Use products with third-party test evidence to the required fire resistance period.
  • Record keeping: Retain product data sheets, installation instructions, and photographs as evidence of compliance. Building control may request this evidence during inspections, and it is invaluable if a subsequent EICR or fire risk assessment raises questions.
07 · Installation Guide

For Electricians — Documenting Conduit Installations

Conduit installations require an Electrical Installation Certificate (EIC) for new circuits and an EICR observation where defects are identified. Elec-Mate provides mobile-optimised certificate tools to make paperwork fast and compliant on-site.

  • — record conduit type, cable sizes, circuit protective conductor details, and test results in a fully compliant EIC with instant PDF export.
  • — document overfilled conduit, missing earth continuity, or absent fire stopping as C2 or C3 observations with full supporting evidence.
  • — issue minor electrical installation works certificates for small conduit extensions or additional circuit outlets.

Electrical Conduit Installation — Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Document conduit installations on your phone

Generate compliant EICs and EICRs on-site with Elec-Mate — fast, accurate, PDF-ready.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy