Electrical Load Calculation — UK Electrician Guide
A complete guide to calculating electrical load for domestic and commercial premises: diversity factors from BS 7671 Appendix 1, maximum demand, cable sizing correction factors, three-phase calculations, and IET On-Site Guide methods with worked examples.
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer — DP Electrical
Key Takeaways
1Electrical load calculation determines the maximum demand on a circuit, distribution board, or supply in order to select correctly rated protective devices, cables, and supply capacity. Under-sizing any of these elements creates a fire and shock risk.
2BS 7671:2018+A4:2026 Appendix 1 provides diversity factors for domestic and commercial installations, allowing the calculated maximum demand to be reduced below the simple sum of all connected loads to reflect the realistic simultaneous usage pattern.
3The IET On-Site Guide (OSG) provides tabulated diversity factors and simplified methods for domestic load calculations. For commercial and industrial premises, full calculations using first principles are required.
4Cable current-carrying capacity (CCC) must be derated for grouping, ambient temperature, and installation method using the correction factors in BS 7671 Appendix 4. The corrected CCC must not be less than the design current of the circuit.
5For three-phase supplies, phase balance should be considered during load allocation. Unbalanced loading increases neutral current, which must be accounted for in neutral conductor sizing under BS 7671 Regulation 523.6.
6Maximum demand calculations must be reviewed when significant new loads are added to an existing installation — for example, EV chargers, heat pumps, or electric showers. The supply capacity and protective device ratings must be adequate for the revised maximum demand.
01 · Technical Guide
What is Electrical Load?
Electrical load is the total power demand placed on a circuit, distribution board, or supply by the connected electrical equipment. It is expressed in amperes (A) for current, watts (W) or kilowatts (kW) for power, or volt-amperes (VA) for apparent power. The design current (Ib) is the current that a circuit is expected to carry under normal operating conditions.
Load calculations are required when designing a new installation, when modifying an existing installation to add significant new loads, and when assessing whether an existing installation can safely accommodate additional loads. Incorrectly sized circuits, distribution boards, or supply connections are a significant cause of electrical fires and equipment damage.
Design current (Ib): The current the circuit is designed to carry. Must not exceed the current-carrying capacity (Iz) of the cable after applying correction factors.
Maximum demand: The highest assessed demand that the installation will draw simultaneously. Used to size the main switch, supply cable, and supply fuse.
Connected load: The sum of the rated power of all connected equipment. The maximum demand is always less than the connected load for most installations because not all loads run simultaneously.
Free download
Get the BS 7671 A4:2026 Cheat Sheet — free
Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.
Every regulation change summarised
New model forms (EIC + MEIWC)
Free PDF — no subscription
02 · Technical Guide
Diversity Factors — BS 7671 Appendix 1
BS 7671:2018+A4:2026 Appendix 1 provides guidance on diversity factors for assessing the maximum demand of domestic and commercial installations. Diversity factors reduce the calculated maximum demand to reflect realistic simultaneous usage, rather than the theoretical worst-case where all loads run simultaneously.
Lighting: 66% of total connected lighting load (or 100% of the largest circuit + 50% of remaining, per IET OSG method)
Heating and water heating (thermostatically controlled): 100% of the largest + 50% of remaining
Cooking appliances: 10A + 30% of connected load above 10A + 5A if second outlet on cooker control unit
Socket outlet circuits: 100% of largest + 40% of remaining (residential); 100% of total in commercial
EV chargers and heat pumps: These loads should generally be assessed at 100% (no diversity) unless a load management system is installed that actively limits output. Always discuss with the client and document the assessment basis in the design.
03 · Technical Guide
Maximum Demand Calculation
Maximum demand calculation brings together connected loads and diversity factors to establish the design basis for a supply, distribution board, or circuit. The result is used to select the main protective device rating and the supply cable CCC.
Ring final circuits (2 × 32A rings): 32A + (32A × 40%) = 44.8A (but limited by supply)
Cooker (7kW): 10A + (30% × 20.4A) = 16.1A
Immersion heater (3kW): 100% = 13A
Assessed maximum demand: approximately 52A — 60A supply adequate
The actual calculation must be performed using the connected loads specific to the property. Document the calculation and retain it with the EIC for the installation. Use
Once the design current (Ib) for a circuit is established, the cable must be selected with sufficient current-carrying capacity (Iz) after applying all relevant correction factors. The fundamental relationship is:
Iz (corrected) = tabulated Iz × Ca × Cg × Ci ≥ Ib
Ca — Ambient temperature correction: Applied when the ambient temperature at the cable location exceeds 30°C. Cables in roof spaces in summer can reach 60°C+ ambient — Ca can reduce CCC by 40% or more.
Cg — Grouping correction: Applied when cables are grouped together or run in a common enclosure. For 4 touching cables, Cg = 0.65 (35% reduction in CCC).
Ci — Insulation enclosure correction: Applied to cables fully enclosed in thermal insulation. For full enclosure, Ci = 0.5 for some installation methods — a 50% reduction in CCC.
BS 7671 Appendix 4 contains the full tables of CCC and correction factors. The IET On-Site Guide provides simplified tables for common installation methods. Always check voltage drop (Regulation 525) as well as CCC — the voltage drop from supply to load must not exceed 3% for lighting circuits and 5% for other circuits under normal operating conditions.
Try Elec-Mate free for 7 days
16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.
Three-phase supplies are standard for commercial and industrial premises, and are increasingly used in domestic premises with large electrical loads (EV charging, large heat pumps). The load calculation approach differs from single-phase.
Three-phase balanced load: For balanced three-phase loads (three-phase motors, three-phase heaters), P = √3 × V_L × I × pf, where V_L is the line voltage (400V in the UK). A 22kW three-phase EV charger draws 22,000 / (√3 × 400 × 1.0) = 31.8A per phase.
Single-phase loads on a three-phase supply: Each single-phase load draws current on one phase only. Phase balance must be considered during circuit design — allocate single-phase circuits to phases to minimise the difference in loading between L1, L2, and L3.
Neutral conductor sizing: For balanced three-phase loading with no significant harmonic distortion, the neutral current is zero or negligible. Where significant single-phase loads cause phase imbalance, or where non-linear loads (LEDs, VFDs, switched-mode power supplies) create third-harmonic currents, the neutral current may exceed the phase current — requiring the neutral to be the same cross-section as the phase conductors (BS 7671 Regulation 523.6.3).
06 · Technical Guide
Commercial and Industrial Load Calculations
Commercial and industrial load calculations follow the same principles as domestic calculations, but the scale and complexity is greater and the consequences of errors more significant. Full first-principles calculations are required — not simplified OSG methods.
Distribution board schedules: Each distribution board requires a schedule documenting circuit designation, protective device rating, cable size, design current, and diversity. This schedule forms part of the EIC documentation.
Demand diversity in commercial premises: BS 7671 Appendix 1 provides diversity factors for offices and commercial premises. For socket outlet circuits, 100% of total connected load is often assumed in commercial locations — unlike the 40% diversity applied in domestic.
Power factor correction: Industrial premises with large motor loads have a lagging power factor — the apparent power (kVA) exceeds the true power (kW). Power factor correction (PFC) capacitors reduce the reactive demand and can avoid penalty charges from the supply authority. Cable sizing uses apparent current (kVA / V), not true power current.
07 · Technical Guide
Worked Examples
The following worked examples illustrate the application of diversity factors and load calculation methods for common UK electrical installation scenarios.
Example 1 — EV Charger Added to Existing Installation
Existing assessed maximum demand: 52A (from previous calculation)
New 7kW EV charger (32A): added at 100% demand (no diversity) = 32A
Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.
Fantastic app for electricians
I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.
Absolutely amazing
I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.
Trusted by electricians across the UK
Real feedback from real sparks
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer
Sole Trader · DP Electrical
“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”
Nathan Perry
Electrician · NP Electrical Services
“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”
Jake Pizey
3rd Year Apprentice · Apprentice
7-Day Free Trial — Cancel Anytime, No Hassle
Issue Electrical Installation Certificates with load calculation records
Generate compliant EIC documents on your phone with Elec-Mate. Start your free 7-day trial.
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer, DP Electrical
From £6.99/mo after trial — less than a coffee a week
or download the app
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents
1,000+ electricians · From £6.99/mo after trial
We use cookies to improve the app and measure what works. Cookie Policy