The current edition of the Wiring Regulations is BS 7671:2018+A4:2026. The 18th Edition was published in 2018 and has been amended four times — Amendment 1:2020, Amendment 2:2022, Amendment 3:2024 and Amendment 4:2026. Amendment 4 was issued on 15 April 2026; the previous edition remains current but is withdrawn on 15 October 2026.
Properties wired before 2000 were designed to earlier standards and will not match today's requirements in several respects. That is expected, and BS 7671 says so directly: an existing installation that does not comply with the current edition in every respect is not, for that reason alone, unsafe for continued use or in need of upgrading. What follows are the four areas an inspector will look at hardest in an older home.
No RCD protection on socket circuits
Required under Regulation 411.3.3 for socket-outlets rated up to 32 A. Properties wired before the 16th Edition (1991) commonly have no RCD protection at all. This is one of the most common C2 observations in older properties.
No supplementary bonding in bathrooms
Regulation 701.415.2 requires supplementary protective equipotential bonding in a room containing a bath or shower. It may be omitted only where all three of the following are met: every final circuit in the room meets the disconnection times of Regulation 411.3.2, every final circuit has additional protection by RCD to Regulation 415.1.1, and all extraneous-conductive-parts in the room are effectively connected to the main protective bonding. A property with no RCDs fails the second condition, so the bonding has to be there.
Original wiring at end of life
PVC-insulated cable has a design life of roughly 25 to 40 years, so wiring from the 1980s and early 1990s is approaching or past that range. Rubber-insulated wiring from the 1960s and earlier is well beyond its serviceable life and is a common trigger for a full rewire.
Combustible consumer unit enclosure
Regulation 421.1.201 requires consumer units in domestic premises to comply with BS EN 61439-3 and either have an enclosure of non-combustible material or be enclosed in one — ferrous metal such as steel being the example the standard gives. This came in with BS 7671:2008+A3:2015, so white plastic consumer units predating it are widespread and are typically recorded as C3, improvement recommended.
New at Amendment 4
RCD protection on domestic lighting circuits
Amendment 4, issued in April 2026, introduced Regulation 411.3.4: within domestic (household) premises, additional protection by an RCD with a rated residual operating current not exceeding 30 mA shall be provided for AC final circuits supplying luminaires. Virtually every home wired before 2026 lacks it.
BS 7671 is not applied retrospectively, so its absence in an existing installation does not automatically mean danger. An inspector assesses the installation against the current edition and uses professional judgement: C1 or C2 where a condition is dangerous or potentially dangerous, and C3 where the item is simply an improvement. Unprotected lighting on its own would usually sit at C3. Either way, it is a real cost to factor into a post-purchase upgrade plan.