Emergency Lighting Not Working: Fault Finding and BS 5266 Compliance
Your emergency lighting is failing tests, showing fault indicators, or failing to illuminate during a mains failure. This guide covers battery failure, charging circuit faults, lamp failure, test mode issues, and the monthly and annual BS 5266 testing requirements.
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer — DP Electrical
Key Takeaways
1Emergency lighting must comply with BS 5266-1:2016 (Code of practice for the emergency lighting of premises). Failure to maintain emergency lighting in commercial, public, and HMO premises is a breach of fire safety legislation and can result in enforcement action.
2The most common emergency lighting fault is battery failure — sealed lead-acid or NiCd batteries degrade over time and may not sustain the minimum 3-hour duration (or 1-hour for some categories) required by BS 5266-1. Battery replacement is the most frequent maintenance intervention.
3Charging circuit faults prevent the battery from reaching full charge. A fitting that passes the monthly function test but fails the annual duration test often has a charging circuit fault rather than a completely failed battery.
4Emergency lighting fittings must be tested monthly (a function test of at least 25% rated duration) and annually (a full rated-duration discharge test). Both test results must be recorded in a log book as required by BS 5266-1.
5Central battery systems and addressable emergency lighting systems require specialist knowledge to fault find. Individual self-contained fitting failures are within the capability of a competent electrician, but system-level faults on central battery installations should be referred to the system installer.
01 · Fault Finding Guide
Battery Failure
Battery failure is the most common cause of emergency lighting faults. Every self-contained emergency lighting fitting contains a rechargeable battery — most commonly a sealed lead-acid (VRLA) or NiCd cell — that powers the lamp during a mains failure. These batteries degrade through charge cycles and calendar ageing, eventually failing to hold sufficient charge for the required duration.
Symptoms of battery failure — the fitting illuminates briefly during a test but extinguishes before the test period expires, a red fault indicator is lit on a fitting that otherwise appears to be operating, or the fitting fails to illuminate at all during a simulated mains failure.
Battery lifespan — sealed lead-acid batteries in emergency lighting fittings typically last 3 to 4 years. NiCd batteries (increasingly rare in new fittings due to EU RoHS restrictions) may last slightly longer. Replace batteries proactively at the manufacturer's recommended interval, not just when they fail.
Correct replacement specification — always replace with the battery type and capacity specified in the fitting's documentation. An incorrect capacity (Ah rating) will result in a fitting that either does not reach full charge or provides insufficient duration. An incorrect voltage will damage the charging circuit.
Charge recovery period — after fitting a new battery, the fitting must be left on mains supply for a full recharge period (typically 24 hours for lead-acid, up to 24 hours for NiCd) before a duration test is performed. Testing too soon after battery replacement will give a falsely short duration result.
Free download
Get the BS 7671 A4:2026 Cheat Sheet — free
Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.
Every regulation change summarised
New model forms (EIC + MEIWC)
Free PDF — no subscription
02 · Fault Finding Guide
Charging Circuit Faults
The charging circuit within each self-contained fitting converts the maintained mains supply to the correct DC charge voltage for the battery. A fault in the charging circuit means the battery is not being recharged after each test or after a real mains failure event — the battery progressively discharges until the fitting fails completely.
Identifying a charging fault — measure the DC voltage across the battery terminals with the mains supply connected. The voltage should be above the battery's nominal voltage (typically 3.6 V to 4.2 V for a NiCd cell, or 2.15 V per cell for a lead-acid battery in float charge). A battery voltage below nominal with the mains supply on indicates a charging circuit fault.
Failed charging components — the charging circuit typically consists of a voltage regulator IC, current-limiting resistors, and a diode. Failure of any of these components will prevent charging. Component-level repair of emergency lighting PCBs is generally not cost-effective — replace the fitting.
Mains supply interruption — if the maintained mains circuit to the emergency lighting has been interrupted (tripped MCB, blown fuse, or isolation left on following maintenance), the fittings receive no mains supply and the batteries progressively discharge. Check that the emergency lighting circuit MCB is closed and that no local isolation has been left in the off position.
03 · Fault Finding Guide
Lamp Failure
Modern emergency lighting fittings use LED light sources with very long service lives — typically 50,000 hours or more — making lamp failure much less common than with older fluorescent or incandescent sources. However, LED modules can still fail, particularly in fittings exposed to heat, vibration, or repeated voltage transients.
LED module failure — a fitting that does not illuminate during a test but has a satisfactory battery voltage is most likely suffering from LED module failure or a driver PCB fault. LED modules in emergency lighting fittings are not typically user-replaceable — replace the fitting.
Maintained lamp vs. emergency lamp — some combined maintained and emergency fittings have separate lamp circuits for the mains-powered maintained operation and the battery-powered emergency operation. A fault in the maintained lamp circuit does not affect the emergency lamp, and vice versa. Confirm which lamp has failed before replacing the fitting.
Luminance and lux levels — BS 5266-1 specifies minimum illuminance levels (typically 1 lux on the centreline of escape routes, higher in high-risk areas). A fitting with degraded LEDs may illuminate but fail to meet the minimum lux requirement. Annual testing should include lux verification at representative points on the escape route.
04 · Fault Finding Guide
Test Mode Issues
Addressable and central battery emergency lighting systems allow testing via a central controller rather than by testing each fitting individually. Faults in the test mode system can prevent testing from being completed or can provide false test results.
Test inhibit left active — some systems allow a test inhibit to be set (for example, to prevent an automatic test running during an event). An inhibit that has been left active will prevent the scheduled test from running. Check the controller settings and remove any active inhibits.
Communication fault preventing remote test — on bus-connected addressable systems, a wiring fault on the bus loop will prevent communication with all downstream fittings. The controller will report a communication fault rather than a test result. The loop wiring must be repaired before testing can proceed.
Manual test as alternative — if the automated test system is faulty, the monthly and annual tests can still be performed manually by simulating mains failure at each fitting. Manual test results must still be recorded in the log book. Restore the automatic test function as soon as practicable.
Try Elec-Mate free for 7 days
16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.
BS 5266-1:2016 requires that emergency lighting is subject to a monthly function test. This is a key maintenance obligation for commercial premises, HMOs, and any building where emergency lighting is installed as a fire safety measure.
Test procedure — simulate mains failure by pressing the test button on each self-contained fitting, or by operating the maintained circuit isolator for central battery systems. Each fitting must be visually confirmed to illuminate. The test period should be at least 25% of the rated duration (45 minutes for a 3-hour rated fitting).
Allow recharge before next test — after the monthly function test, the battery must be allowed to fully recharge (minimum 24 hours) before the next test or before the premises are closed. Do not carry out multiple tests in quick succession.
Recording results — the date of the test, the tester's name, and the result (pass or fail, with the identity of any failed fitting) must be recorded in the emergency lighting log book. Unsigned or undated log book entries are not acceptable evidence of compliance.
06 · Fault Finding Guide
Annual BS 5266 Duration Test
The annual full-rated-duration test is the most rigorous maintenance requirement for emergency lighting. It confirms that each fitting can sustain illumination for the complete rated duration — typically 3 hours — following complete mains failure, meeting BS 5266-1:2016.
Pre-test battery charge — all fittings must be fully charged before the annual test begins. This requires at least 24 hours on mains supply following any previous test or mains failure event. Beginning the annual test with partially charged batteries will give misleadingly low duration results.
Test execution — simulate complete mains failure across the installation and monitor all fittings throughout the full rated duration. Any fitting that extinguishes before the end of the duration period has failed the test and must be repaired or replaced and retested.
Post-test recharge and restrictions — after the annual test, the batteries are fully discharged. The premises should not be occupied during the recharge period (typically 24 hours) unless alternative emergency lighting arrangements are in place. This is a significant operational consideration for busy commercial premises.
Formal certificate — the annual test should be documented with a formal test certificate signed by the competent person who carried out the test. This certificate forms part of the fire safety record for the premises and may be required by the fire authority or building insurer.
07 · Fault Finding Guide
For Electricians: Emergency Lighting Testing and Certification
Emergency lighting testing and maintenance is a steady source of recurring work for commercial electricians. Every commercial and public building, HMO, and licensed premises requires monthly testing and an annual duration test — creating a regular maintenance cycle for every customer on your books.
Emergency Lighting on the EICR
When carrying out an EICR on premises with emergency lighting, function-test each fitting and record any failures as C2 or C3 observations. Record the results and the date of the last annual test in the schedule of particulars. Use the Elec-Mate EICR app to capture observations and generate the report on site.
Annual Test Certificates
The annual BS 5266 duration test requires a formal written certificate. Elec-Mate allows you to capture test results for each fitting, record pass and fail status, and generate a professional test certificate — all on your phone, on site. Upsell annual testing contracts to every commercial EICR customer.
Manage emergency lighting testing with Elec-Mate
Join 1,000+ UK electricians using Elec-Mate for EICRs, emergency lighting test records, and BS 7671-compliant documentation. 7-day free trial.
Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.
Fantastic app for electricians
I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.
Absolutely amazing
I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.
Trusted by electricians across the UK
Real feedback from real sparks
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer
Sole Trader · DP Electrical
“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”
Nathan Perry
Electrician · NP Electrical Services
“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”
Jake Pizey
3rd Year Apprentice · Apprentice
7-Day Free Trial — Cancel Anytime, No Hassle
Manage Emergency Lighting Testing with Elec-Mate
Join 1,000+ UK electricians using Elec-Mate for EICRs, emergency lighting test records, and compliant documentation. 7-day free trial, cancel anytime.
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer, DP Electrical
From £6.99/mo after trial — less than a coffee a week
or download the app
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents
1,000+ electricians · From £6.99/mo after trial
We use cookies to improve the app and measure what works. Cookie Policy