Bathroom Electrical Zones: BS 7671 Section 701 Zone Guide
Zone 0 is the interior of the bath tub or shower basin. Zone 1 runs to the higher of 2.25 m or the highest fixed shower head. Zone 2 is the 0.60 m strip beyond it. This guide gives the boundaries, the IP ratings, the equipment permitted in each zone and the regulation numbers behind them.
Zone 0 is the interior of the bath tub or shower basin and needs IPX7 with SELV at no more than 12 V AC RMS or 30 V ripple-free DC. Zone 1 surrounds the bath or basin up to the higher of 2.25 m or the highest fixed shower head. Zone 2 is the 0.60 m strip beyond it. Both need IPX4.
Section 701 also requires 30 mA RCD additional protection for low voltage circuits serving the location and for circuits passing through zones 1 and 2 (Reg 701.411.3.3), and prohibits socket-outlets within 2.50 m horizontally of the Zone 1 boundary apart from SELV socket-outlets and shaver supply units to BS EN 61558-2-5 (Reg 701.512.3).
1,000+
UK electricians
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Key takeaways
01Zone 0 is the interior of the bath tub or shower basin. Minimum IPX7, and current-using equipment must be fixed, permanently connected and SELV at no more than 12 V AC RMS or 30 V ripple-free DC with the safety source outside zones 0, 1 and 2 (Regs 701.512.2 and 701.55).
02Zone 1 and Zone 2 both require a minimum of IPX4 (Reg 701.512.2). Equipment exposed to water jets — for example for cleaning purposes — needs at least IPX5.
03Both zones rise to the higher of 2.25 m above finished floor level or the plane of the highest fixed shower head or water outlet (Regs 701.32.3 and 701.32.4). Zone 2 is the 0.60 m strip beyond the Zone 1 boundary.
04For a shower without a basin there is no Zone 2 — Zone 1 is instead extended to 1.20 m from the centre point of the fixed water outlet (Reg 701.32.3(b)(ii)).
05Zone 1 permits only fixed, permanently connected whirlpool units, electric showers, shower pumps, SELV/PELV equipment up to 25 V AC RMS or 60 V ripple-free DC, ventilation equipment, towel rails, water heating appliances and luminaires (Reg 701.55).
06Socket-outlets are prohibited within 2.50 m horizontally of the Zone 1 boundary, except SELV socket-outlets to Section 414 and shaver supply units to BS EN 61558-2-5 (Reg 701.512.3).
07Reg 701.411.3.3 requires 30 mA RCD additional protection for low voltage circuits serving the location and for circuits merely passing through zones 1 and/or 2 — not only for circuits feeding equipment inside the zones.
08Supplementary bonding (Reg 701.415.2) may be omitted only where the building has a protective equipotential bonding system to Reg 411.3.1.2 and conditions (d), (e) and (f) of 701.415.2 are all met.
01 · BS 7671 Guide
Every Bathroom Zone at a Glance
BS 7671 Section 701 applies to locations containing a fixed bath (bath tub) or shower and to the surrounding zones. It does not apply to emergency facilities such as emergency showers used in industrial areas or laboratories (Reg 701.1). The table below is the whole zone system on one screen; the sections that follow give the detail behind each row.
BS 7671 Section 701 bathroom zones: extent, minimum IP rating and permitted equipment
Zone
Extent
Minimum IP
Headline restriction
Zone 0
Interior of the bath tub or shower basin
IPX7
Fixed, permanently connected SELV equipment only — 12 V AC RMS / 30 V ripple-free DC. No switchgear or accessories.
Zone 1
Vertical surface circumscribing the bath or basin, floor up to the higher of 2.25 m or the highest fixed shower head
IPX4
Only the fixed equipment listed in Reg 701.55. Switches only on SELV circuits at 12 V AC RMS / 30 V ripple-free DC.
Zone 2
0.60 m beyond the Zone 1 boundary, over the same height
IPX4
No switchgear, accessories incorporating switches or socket-outlets, except SELV and shaver supply units to BS EN 61558-2-5.
Outside the zones
Beyond Zone 2, or above the zone height
None stated
Socket-outlets still prohibited within 2.50 m horizontally of the Zone 1 boundary (Reg 701.512.3).
Two rules cut across every zone. Regulation 701.512.2 raises the minimum to IPX5 for equipment exposed to water jets, for example for cleaning purposes. And Regulation 701.411.3.3 requires 30 mA RCD additional protection for low voltage circuits serving the location as well as circuits that merely pass through zones 1 and/or 2.
Section 701 also rules out three protective measures outright: obstacles and placing out of reach (Reg 701.410.3.5), and non-conducting location and earth-free local equipotential bonding (Reg 701.410.3.6). Protection by electrical separation is allowed, but only for a circuit supplying one item of current-using equipment or one single socket-outlet (Reg 701.413).
Free download
Get the BS 7671 A4:2026 Cheat Sheet — free
Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.
Every regulation change summarised
New model forms (EIC + MEIWC)
Free PDF — no subscription
02 · BS 7671 Guide
How the Zone Boundaries Are Measured
Zone dimensions are measured from the interior of the bath tub or shower basin outwards, and from finished floor level upwards. Get the boundary wrong and every equipment decision downstream of it is wrong too, so it is worth measuring rather than eyeballing.
Bathroom zones — cross-section
Vertical limits measured from finished floor level (BS 7671 Regs 701.32.2 to 701.32.4)
Schematic only. Where the highest fixed shower head or water outlet sits above 2.25 m, that higher plane becomes the top of zones 1 and 2.
The vertical limit is not always 2.25 m
Regulations 701.32.3(a) and 701.32.4(a) both set the top of the zone at the finished floor level up to the horizontal plane corresponding to the highest fixed shower head or water outlet, or the plane 2.25 m above finished floor level — whichever is higher. A drencher head at 2.4 m therefore lifts the top of Zone 1 and Zone 2 to 2.4 m, and a fitting that would have been outside the zones is now inside them.
Showers without a basin behave differently
Where a shower has no basin, Zone 1 is bounded laterally by the vertical surface 1.20 m from the centre point of the fixed water outlet on the wall or ceiling (Reg 701.32.3(b)(ii)), and there is no Zone 2 — the enlarged Zone 1 replaces it (Reg 701.32.4). Zone 0 in that arrangement is 0.10 m high with the same horizontal extent as Zone 1 (Reg 701.32.2). The 1.20 m figure does not apply to a bath or a shower tray; for those, Zone 1 is bounded by the vertical surface circumscribing the bath tub or basin.
Under the bath is Zone 1 — usually
The space under the bath tub or shower basin is Zone 1. If that space is only accessible with a tool, it is considered to be outside the zones (Reg 701.32.3). A screwed or clipped bath panel that comes away by hand does not buy you the exemption.
Walls, ceilings and partitions
Ceilings, walls, doors, floors and fixed partitions may be taken into account where they effectively limit the extent of the location and its zones. Where a fixed partition is smaller than the relevant zone — Reg 701.32.1 gives the example of a partition lower than 2.25 m — the minimum distance in the horizontal and vertical directions must be taken into account, so the zone is measured around the partition rather than stopping at it. For equipment set into a wall or ceiling that limits a zone but forms part of that surface, the requirements for the zone apply.
03 · BS 7671 Guide
Zone 0: Inside the Bath or Shower Basin
Zone 0 is the interior of the bath tub or shower basin (Reg 701.32.2) — the space the water occupies and where a person is in direct contact with it. It carries the tightest requirements in the whole of Section 701.
Reg 701.55 — all three conditions must be met
(a) The equipment complies with the relevant standard and is suitable for use in Zone 0 according to the manufacturer’s instructions for use and mounting.
(b) The equipment is fixed and permanently connected.
(c) The equipment is protected by SELV at a nominal voltage not exceeding 12 V AC RMS or 30 V ripple-free DC, with the safety source installed outside zones 0, 1 and 2.
Plus, from elsewhere in Section 701
Minimum degree of protection IPX7 (Reg 701.512.2).
Switchgear and accessories must not be installed at all (Reg 701.512.3).
Where SELV or PELV is used, basic protection must be provided by basic insulation to Reg 416.1 or by barriers or enclosures to Reg 416.2, whatever the nominal voltage (Reg 701.414.4.5). The low-voltage exemptions that apply elsewhere do not apply here.
The SELV or PELV source described in Reg 414.3(d) must not be used in zones 0, 1 or 2 (Reg 701.414.3).
In domestic practice Zone 0 is rarely a design problem, because very little is ever installed inside a bath or shower basin. The main Zone 0 product is purpose-made in-bath LED lighting. A fitting inside a shower enclosure but above the tray is in Zone 1, not Zone 0 — check which one you are actually in before selecting the product.
04 · BS 7671 Guide
Zone 1: Around the Bath or Shower
Zone 1 is bounded laterally by the vertical surface circumscribing the bath tub or shower basin, and vertically by finished floor level up to the higher of 2.25 m or the plane of the highest fixed shower head or water outlet (Reg 701.32.3). It excludes Zone 0. Minimum degree of protection is IPX4 (Reg 701.512.2).
Regulation 701.55 gives a closed list. Only the following fixed and permanently connected current-using equipment may be installed in Zone 1, and only where it is suitable for Zone 1 according to the manufacturer’s instructions.
Current-using equipment permitted in bathroom Zone 1 under BS 7671 Reg 701.55
Reg 701.55
Permitted in Zone 1
Notes
(d)
Whirlpool units
Fixed and permanently connected
(e)
Electric showers
Fixed and permanently connected
(f)
Shower pumps
Fixed and permanently connected
(g)
SELV or PELV equipment
Not exceeding 25 V AC RMS or 60 V ripple-free DC, safety source outside zones 0, 1 and 2
(h)
Ventilation equipment
Extract fans rated for the zone
(i)
Towel rails
Expressly permitted in Zone 1
(j)
Water heating appliances
Fixed and permanently connected
(k)
Luminaires
IPX4 minimum; IP65 downlighters are common practice
Anything not on that list has no place in Zone 1. Note in particular that the SELV/PELV limit for current-using equipment in Zone 1 is 25 V AC RMS or 60 V ripple-free DC, which is a different figure from the 12 V AC RMS / 30 V ripple-free DC limit that applies to Zone 0 equipment and to Zone 1 switches.
Switchgear and accessories in Zone 1 (Reg 701.512.3)
Only switches of SELV circuits at a nominal voltage not exceeding 12 V AC RMS or 30 V ripple-free DC may be installed, with the safety source outside zones 0, 1 and 2. Every other switch, accessory and socket-outlet is prohibited.
Two exclusions sit outside that prohibition entirely: switches and controls incorporated in fixed current-using equipment suitable for use in that zone, and the insulating pull cords of cord-operated switches. The pull cord of a ceiling switch may therefore hang into Zone 1 — it is the switch body that has to be sited acceptably.
A ceiling above 2.25 m puts recessed downlighters outside the zones, but only if no fixed shower head or water outlet sits higher than they do. Where the ceiling is at or below the zone height, a luminaire directly over the bath is in Zone 1 and must be at least IPX4.
05 · BS 7671 Guide
Zone 2: The 0.60 m Strip Beyond
Zone 2 is bounded by the vertical surface at the Zone 1 boundary and the parallel vertical surface 0.60 m from it, over the same height as Zone 1 (Reg 701.32.4). In a typical bathroom that strip takes in the washbasin, the mirror and often the towel rail. Minimum degree of protection is IPX4 (Reg 701.512.2). Remember that a shower without a basin has no Zone 2 at all.
Regulation 701.55 restricts current-using equipment in zones 0 and 1 only, so in Zone 2 any equipment suitable for the location may be used provided it meets the IP requirement. Switchgear and accessories are where Zone 2 bites.
Reg 701.512.3 — switchgear, accessories and socket-outlets
Switchgear, accessories incorporating switches and socket-outlets must not be installed in Zone 2, with two exceptions:
(a) switches and socket-outlets of SELV circuits, the safety source being installed outside zones 0, 1 and 2;
(b) shaver supply units complying with BS EN 61558-2-5.
The 2.50 m rule reaches past Zone 2
Except for SELV socket-outlets complying with Section 414 and shaver supply units complying with BS EN 61558-2-5, socket-outlets are prohibited within 2.50 m horizontally of the boundary of Zone 1. That distance is measured from the Zone 1 boundary, not from Zone 2, and it applies irrespective of mounting height — so in most bathrooms a 13 A socket is non-compliant anywhere in the room.
The shaver socket IP exception
Regulation 701.512.2 states that the IPX4 requirement does not apply to shaver supply units complying with BS EN 61558-2-5 installed in Zone 2 and located where direct spray from showers is unlikely. Where direct spray is possible, IPX4 still applies.
In the app
Try Elec-Mate free for 7 days
16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.
Additional protection by one or more RCDs having the characteristics specified in Reg 415.1.1 — a rated residual operating current not exceeding 30 mA — must be provided for low voltage circuits:
(a) serving the location; and
(b) passing through zones 1 and/or 2 not serving the location.
Limb (b) is the one that gets missed. A circuit that merely runs through Zone 1 or Zone 2 on its way to a bedroom needs 30 mA RCD protection even though nothing in the bathroom is fed from it. The regulation’s note points to Regs 314.1(d) and 531.3.2 on avoiding unwanted tripping — the practical answer is usually an RCBO per circuit rather than everything on one RCD.
A separate and wider requirement sits in Chapter 41: Regulation 411.3.4 requires additional protection by a 30 mA RCD for AC final circuits supplying luminaires within domestic (household) premises. It is not a Section 701 measure and it is not limited to bathrooms — but when you add a bathroom light to an existing lighting circuit, both requirements have to be satisfied.
Local supplementary bonding to Reg 415.2 must connect together the terminals of the protective conductor of each circuit supplying Class I and Class II equipment to the accessible extraneous-conductive-parts within the room, including:
(a) metallic pipes supplying services and metallic waste pipes, for example water and gas;
(b) metallic central heating pipes and air conditioning systems;
(c) accessible metallic structural parts of the building. Metallic door architraves, window frames and similar parts are not extraneous-conductive-parts unless they are connected to metallic structural parts of the building.
The bonding may be installed inside or outside the room, preferably close to the point at which the extraneous-conductive-parts enter it.
Supplementary bonding may be omitted only where the location is in a building with a protective equipotential bonding system in accordance with Reg 411.3.1.2 and all three of these conditions are met: (d) all final circuits of the location comply with the requirements for automatic disconnection according to Reg 411.3.2; (e) all final circuits of the location have additional protection by means of an RCD in accordance with Reg 415.1.1; and (f) all extraneous-conductive-parts of the location are effectively connected to the protective equipotential bonding according to Reg 411.3.1.2. Where main protective bonding is missing or unproven, supplementary bonding cannot be omitted however good the RCD protection is. Reg 415.2.2 gives the test used to assess condition (f) where necessary.
07 · BS 7671 Guide
Common Mistakes in Bathroom Electrical Installations
Bathrooms are among the most frequently coded areas on an EICR. These are the errors that come up again and again.
Assuming the zone stops at 2.25 m. Where the highest fixed shower head or water outlet is above 2.25 m, that plane becomes the top of zones 1 and 2 (Regs 701.32.3 and 701.32.4). Drencher heads on a raised arm routinely pull ceiling fittings back into Zone 1.
Light fittings with no IP marking in Zone 1 or 2. If the luminaire does not declare an IP rating it cannot be shown to meet the IPX4 minimum of Reg 701.512.2, so it is not suitable for either zone.
Shaver socket in Zone 1. Shaver supply units to BS EN 61558-2-5 are permitted in Zone 2 and outside the zones, never in Zone 0 or Zone 1 (Reg 701.512.3).
Missing RCD protection on a circuit that only passes through. Reg 701.411.3.3(b) catches cables routed through zones 1 and 2 that serve rooms elsewhere. These are easy to overlook because nothing in the bathroom is fed from them.
13 A socket inside the 2.50 m exclusion. Reg 701.512.3 prohibits socket-outlets within 2.50 m horizontally of the Zone 1 boundary, except SELV socket-outlets to Section 414 and shaver supply units to BS EN 61558-2-5. In a large bathroom a socket beyond 2.50 m is compliant; in most it is not.
Treating a glass screen as the end of the zone. Reg 701.32.1 allows fixed partitions to be taken into account only where they effectively limit the zone. Where a partition is smaller than the zone — the standard’s example is one lower than 2.25 m — the minimum distance in the horizontal and vertical directions must be taken into account, so the zone is measured around it.
Under-bath equipment written off as outside the zones. The space under the bath tub or shower basin is Zone 1 unless it is accessible only with a tool (Reg 701.32.3). A hand-removable bath panel does not qualify.
Floor heating with no earthed metallic screen. Reg 701.753 requires a metal sheath, metal enclosure or fine mesh metallic grid connected to the protective conductor of the supply circuit, unless SELV is used for the heating system. It is a requirement, not a recommendation.
08 · BS 7671 Guide
For Electricians: Bathroom Work in Practice
The first job on any bathroom is to establish the zone boundaries for that specific room — measure to the highest fixed water outlet, decide whether there is a basin, and only then choose equipment. Small bathrooms often sit entirely inside the 2.50 m socket exclusion; larger ones have real space outside the zones.
Use the cable sizing calculator to size electric shower and towel rail circuits against the actual installation method, grouping and ambient temperature rather than a rule of thumb.
Two RCD requirements, not one
Reg 701.411.3.3 covers circuits serving the location and circuits passing through zones 1 and 2. Reg 411.3.4 separately requires 30 mA RCD additional protection for AC final circuits supplying luminaires within domestic premises. A consumer unit with an unprotected lighting way will not satisfy either once a bathroom light is added to it.
Frequently Asked Questions About Bathroom Electrical Zones
Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.
Fantastic app for electricians
I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.
Absolutely amazing
I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.
Trusted by electricians across the UK
Real feedback from real sparks
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer
Sole Trader · DP Electrical
“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”
Nathan Perry
Electrician · NP Electrical Services
“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”
Jake Pizey
3rd Year Apprentice · Apprentice
7-day free trial
Issue Bathroom Electrical Certificates On Site
Elec-Mate lets you complete EICs and Minor Works Certificates for bathroom electrical work on your phone. All Part P notifiable — get the certificate done on site before you leave. 7-day free trial.