BS 7671 GUIDE

Bathroom Electrical Zones: BS 7671 Section 701 Zone Guide

BS 7671 Section 701 defines three zones in bathrooms based on proximity to water. Each zone has specific IP rating requirements and restrictions on the equipment permitted. This guide covers Zone 0, 1, and 2 in detail — boundaries, IP ratings, permitted equipment, and common mistakes.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

12 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1BS 7671 Section 701 defines three zones in bathrooms and shower rooms (Zone 0, Zone 1, Zone 2) based on proximity to water — each with specific IP rating requirements and restrictions on equipment permitted.
  • 2Zone 0 (inside the bath or shower tray) requires IPX7 rated equipment and only SELV at a maximum of 12V AC is permitted. No switches or socket outlets are allowed.
  • 3Zone 1 (above the bath or shower tray up to 2.25m) requires IPX4 minimum. No switches are permitted; SELV equipment rated IPX4 is acceptable.
  • 4Zone 2 (extending 0.6m beyond Zone 1 boundary) requires IPX4 minimum. Shaver sockets to BS EN 61558-2-5 are permitted. Note: a shaver socket conforming to BS EN 61558-2-5 is not required to be IPX4 rated in Zone 2 provided it is sited where direct spray from showers is unlikely (Reg 701.512.2 exception).
  • 5RCD protection (30mA) is mandatory for all circuits in bathroom zones under Regulation 701.411.3.3 of BS 7671.
  • 6A4:2026 Reg 411.3.4: all AC final circuits supplying luminaires in domestic premises now require additional protection by an RCD ≤30mA — this applies to the whole lighting circuit, not just as a Section 701 measure.
  • 7Supplementary bonding (Reg 701.415.2) may be omitted only where the building has a protective equipotential bonding system per Reg 411.3.1.2 AND three conditions are all satisfied: (d) all final circuits comply with automatic disconnection per Reg 411.3.2; (e) all final circuits have RCD additional protection per Reg 415.1.1; (f) all extraneous-conductive-parts are effectively connected to main bonding per Reg 411.3.1.2.
01 · BS 7671 Guide

BS 7671 Section 701: Locations Containing a Bath or Shower

BS 7671 Section 701 is the specific part of the IET Wiring Regulations that covers electrical installations in rooms containing a bath or shower. It is one of the most commonly encountered Special Location requirements for domestic electricians, since bathrooms and shower rooms are present in virtually every dwelling.

Section 701 is more restrictive than the general installation requirements because water and electricity are a dangerous combination. The presence of water dramatically reduces the body's resistance to electric shock, meaning that voltages and fault currents that would not be lethal in a dry environment can cause a fatal shock in a bathroom. The zone system provides a structured, risk-based approach to managing this danger.

All electrical work in bathrooms and shower rooms in dwellings is notifiable under Part P of the Building Regulations (except like-for-like replacement of accessories on existing circuits). Electricians carrying out bathroom electrical work must be registered with an approved competent person scheme to self-certify, or building control must be notified.

Section 701 also has specific requirements for supplementary protective equipotential bonding, RCD protection, and the prohibited types of equipment — all of which are covered in this guide.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · BS 7671 Guide

The Bathroom Zone System

Section 701 of BS 7671 defines zones based on the physical proximity to the bath or shower. The zone dimensions are measured from the interior of the bath or shower tray outwards, and from the finished floor level upwards. The zones determine what equipment is permitted and what IP rating is required.

Bathroom zones — cross-section

Vertical limits measured from finished floor level (BS 7671 Reg 701.32.3)

2.25 mZone 0Zone 1Zone 2Outsidethe zones0.6 m

Schematic only — for a shower without a basin there is no Zone 2; Zone 1 instead extends 1.2 m horizontally from the fixed water outlet (Reg 701.32.3).

0Zone 0

The interior of the bath or shower tray. The space occupied by the water. Extends from the bottom of the bath to the overflow or top of the tray.

1Zone 1

The area directly above the bath or shower tray, up to 2.25m from the finished floor level. For fixed shower heads, extends 1.2m horizontally from the head.

2Zone 2

Extends a further 0.6m horizontally from the boundary of Zone 1, from the floor up to 2.25m. The area typically containing the washbasin and towel rail.

Outside the zones, normal electrical installation rules apply, subject to the RCD protection requirement for circuits that supply equipment within the zones. In very small bathrooms, the entire floor area may fall within Zone 2, leaving no space that is outside the zones entirely.

03 · BS 7671 Guide

IP Ratings Required Per Zone

The IP (Ingress Protection) rating system, defined in BS EN 60529, uses two digits to indicate the level of protection against solid particles (first digit) and against water (second digit). In bathrooms, the water ingress protection (second digit) is the critical value.

ZoneMinimum IP RatingWhat This Means
Zone 0IPX7Protected against immersion in water up to 1 metre depth for 30 minutes
Zone 1IPX4Protected against water splashing from any direction
Zone 2IPX4Protected against water splashing from any direction
Outside ZonesNo minimumStandard equipment permitted; IPX4 recommended in practice

The IP rating must be marked on the luminaire or equipment. If a light fitting does not display an IP rating, it is not suitable for use within the zones. Common IP-rated bathroom luminaires display IP44 or IP65 ratings — both of which meet the Zone 1 and Zone 2 requirement of IPX4.

04 · BS 7671 Guide

Zone 0: Inside the Bath or Shower Tray

Zone 0 is the most restrictive zone. It encompasses the interior of the bath or shower tray — the space where the bather or person showering is in direct contact with water. The electrical risk here is the highest.

Zone 0 Requirements

  • Equipment must be rated IPX7 minimum
  • Only SELV (Safety Extra-Low Voltage) equipment permitted — maximum 12V AC or 30V DC
  • SELV transformer must be located outside the zones

Not Permitted in Zone 0

  • Socket outlets of any type
  • Switches or other switching devices
  • Mains voltage equipment
  • Equipment not rated for Zone 0 use (even if IP-rated)

In domestic practice, Zone 0 is rarely encountered as a design challenge because very few products are installed inside the bath or shower tray. The main Zone 0 product is specialist in-bath LED lighting, which is purpose-designed for this application. If a homeowner requests lighting inside a shower enclosure, the fitting must be rated for Zone 0 if it is positioned inside the shower tray, or Zone 1 if it is above the tray but within the shower enclosure.

05 · BS 7671 Guide

Zone 1: Above the Bath or Shower Tray

Zone 1 extends upward from the bath or shower tray to a height of 2.25m above the finished floor level. For showers with a fixed shower head, Zone 1 extends 1.2m horizontally from the shower head position in all directions (or to the wall of the shower enclosure if smaller). Zone 1 represents the area where water spray from the shower or splashing from the bath is likely.

Zone 1 Requirements

  • Equipment must be rated IPX4 minimum
  • SELV equipment rated IPX4 is permitted
  • Electric shower units are permitted in Zone 1 — they are specifically designed for this location and must be IPX4 rated
  • IPX4 rated luminaires are permitted

Not Permitted in Zone 1

  • Socket outlets (any type)
  • Switches (including pull-cords at or below 2.25m)
  • Consumer units or distribution boards

The ceiling of a bathroom is usually above 2.25m, which means that recessed ceiling luminaires directly above the bath or shower are technically in Zone 1 (assuming the ceiling is at 2.25m or below). These must be IPX4 rated minimum. Many bathroom recessed LED downlighters are rated IP65, which exceeds the Zone 1 requirement.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · BS 7671 Guide

Zone 2: The Wider Bathroom Area

Zone 2 extends 0.6m horizontally beyond the boundary of Zone 1 and from the floor up to 2.25m. In a typical bathroom, Zone 2 covers the area immediately adjacent to the bath or shower — where the washbasin, towel rail, and mirror are typically located.

Zone 2 Requirements and Permissions

  • Equipment must be rated IPX4 minimum
  • Shaver socket outlets to BS EN 61558-2-5 are permitted in Zone 2. These incorporate an isolating transformer and are specifically designed for bathroom use.
  • IPX4 rated luminaires, towel rails, and fan units are permitted
  • Mains voltage equipment (such as electric towel rails and heated mirror demister pads) is permitted, provided it is suitable for bathroom use and IPX4 rated

Not Permitted in Zone 2

  • Standard 13A socket outlets
  • Standard light switches
  • Equipment not rated for use in wet or damp locations
07 · BS 7671 Guide

Outside the Zones

The area outside Zone 2 is beyond 0.6m horizontally from the Zone 1 boundary and above 2.25m from the floor. In this area, standard electrical installation rules apply. However, there are important caveats:

  • RCD protection still required — Regulation 701.411.3.3 requires that all circuits supplying equipment in Zone 0, 1, or 2 are RCD protected at 30mA, regardless of where the supply cable runs. A lighting circuit that also supplies a bathroom luminaire must be RCD protected even if the consumer unit is remote from the bathroom.
  • Switches and sockets permitted outside zones — a standard mains switch can be installed outside the zones in a bathroom (where space permits). In small bathrooms, the entire floor area is within Zone 2, so a mains switch can only be placed at the door on the outside of the room, or as a pull-cord above 2.25m.
  • Supplementary bonding — Regulation 701.415.2 requires supplementary protective equipotential bonding connecting all circuit protective conductors to accessible extraneous-conductive-parts. It may be omitted only where the building already has a protective equipotential bonding system per Reg 411.3.1.2 AND all three of the following conditions are satisfied: (d) all final circuits comply with automatic disconnection per Reg 411.3.2; (e) all final circuits have additional RCD protection per Reg 415.1.1; (f) all extraneous-conductive-parts are effectively connected to main equipotential bonding per Reg 411.3.1.2. Where main bonding is absent, supplementary bonding cannot be omitted regardless of RCD protection.
08 · BS 7671 Guide

Common Mistakes in Bathroom Electrical Installations

Bathroom electrical work is one of the most commonly failed areas on EICRs. These are the most frequent mistakes encountered:

  • Towel rail positioned in wrong zone — an electric towel rail installed within Zone 1 (within the horizontal footprint of the bath or shower, above the tray) is a common error. Towel rails should be in Zone 2 or outside the zones.
  • Light fittings without IP rating in Zone 1 or 2 — recessed downlighters that are not IP rated installed directly above a bath. Without an IP rating the fitting is not suitable for Zone 1.
  • Shaver socket in Zone 1 — shaver sockets are only permitted in Zone 2 or outside the zones. Installing one within Zone 1 (within the footprint of the bath) is non-compliant.
  • No RCD protection on lighting circuit — bathroom lighting circuits without RCD protection. This is a very common C2 or C1 deficiency on older installations.
  • Standard socket outlets within the prohibited distance — Reg 701.512.3 prohibits socket outlets within 2.50m horizontally of the Zone 1 boundary, except for SELV socket outlets (Section 414) and shaver supply units (BS EN 61558-2-5). In most bathrooms the entire floor area falls within that 2.50m limit, making a standard 13A socket non-compliant anywhere in the room. In a large bathroom where a socket would be more than 2.50m from Zone 1, it is permitted — measure horizontally from the Zone 1 boundary to the socket centre.
  • Glass shower screen assumed to limit Zone 1 — a frameless glass screen or low partition does not reduce zone dimensions unless it is at least 2.25m high (Reg 701.32.2). A screen lower than 2.25m must be ignored when calculating zone boundaries; the full horizontal and vertical zone distances still apply beyond it. This causes non-compliant equipment placement on many installations where the installer assumed the screen ended Zone 1.

Complete bathroom EICs with zone compliance built in

Elec-Mate's EIC Certificate app includes Section 701 zone guidance. AI board scanning, voice test entry…

Try it free for 7 days
Download on the App StoreGet it on Google Play
09 · BS 7671 Guide

For Electricians: Bathroom Electrical Work in Practice

Bathroom electrical work requires careful zone assessment before any work is planned or quoted. The first step on any bathroom job is to establish the zone boundaries for the specific room layout. Small bathrooms are often entirely within Zone 2; larger bathrooms may have significant areas outside the zones.

EIC Certificate App

Issue your Electrical Installation Certificate on site after every bathroom installation. All bathroom work (except like-for-like) is Part P notifiable and requires an EIC or MEIWC.

Cable Sizing for Bathroom Circuits

Use the cable sizing calculator to correctly size shower circuits (typically 6mm to 10mm depending on the shower rating) and towel rail circuits.

A4:2026 — RCD Protection for Lighting Circuits (Reg 411.3.4)

BS 7671:2018+A4:2026 introduced Regulation 411.3.4, which requires all AC final circuits supplying luminaires in domestic premises to have additional protection by an RCD rated at no more than 30mA. This is a standalone Part 4 requirement, separate from the Section 701 bathroom RCD rule (Reg 701.411.3.3). When fitting new bathroom lights, the whole lighting circuit must satisfy both requirements. Consumer units without RCD-protected lighting ways will need an RCBO or rewiring to comply with the latest edition.

Frequently Asked Questions About Bathroom Electrical Zones

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Issue Bathroom Electrical Certificates On Site

Elec-Mate lets you complete EICs and Minor Works Certificates for bathroom electrical work on your phone. All Part P notifiable — get the certificate done on site before you leave. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy