REGULATIONS

BS 5266 Emergency Lighting: The Complete UK Guide

BS 5266-1:2025 is the current UK code of practice for emergency lighting. It covers escape route lighting, open area lighting, high-risk task areas, and standby lighting. This guide explains the design requirements, illuminance levels, testing intervals, and certification — essential knowledge for every electrician.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

12 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1BS 5266-1:2025 is the current UK code of practice for emergency lighting (revised from the 2016 edition), covering escape route lighting, open area lighting, high-risk task area lighting, and standby lighting.
  • 2Emergency lighting is a legal requirement under the Regulatory Reform (Fire Safety) Order 2005, the Health and Safety at Work Act 1974, and Building Regulations Approved Document B.
  • 3BS 7671 Reg 560.9 requires emergency lighting systems to comply with BS 5266-1:2025, BS EN 1838:2024, and BS EN 50172 — three standards that must be read together.
  • 4Emergency luminaires must provide a minimum of 1 lux along the centre line of an escape route, with a minimum duration of 3 hours for most commercial premises.
  • 5Testing intervals are defined as: monthly functional tests (flick test), annually a full rated duration test (3-hour battery discharge), and daily visual checks where practicable.
  • 6A BS 5266-1:2025 certificate is only valid when accompanied by a current signed checklist/report, photometric design data in an accepted format, and the site test log book.
  • 7Elec-Mate includes emergency lighting certificate templates, AI-powered defect coding, and training courses covering BS 5266 design, installation, and testing requirements.
01 · Regulations

What Is BS 5266? The UK Emergency Lighting Standard

BS 5266 is the British Standard code of practice for the emergency lighting of premises. The primary document is BS 5266-1:2025Emergency lighting. Code of practice for the emergency lighting of premises — which provides guidance on the design, installation, wiring, testing, and maintenance of emergency lighting systems in buildings. The standard was revised in 2025 from the previous 2016 edition; any reference to "BS 5266-1" in specifications or contracts should be understood to mean the current 2025 edition. It works alongside the European standard BS EN 1838, which specifies the minimum illuminance levels and design parameters.

Emergency lighting is the lighting that operates when the normal mains-powered lighting fails. Its purpose is to enable the safe evacuation of a building, to illuminate fire safety equipment (extinguishers, call points, fire exits), and to allow high-risk processes to be safely shut down. Without adequate emergency lighting, a power failure in a building at night or in a windowless space could leave occupants in complete darkness — creating a serious risk of injury from falls, collisions, and panic.

For electricians, emergency lighting is a core competence area. It features in domestic work (HMOs, blocks of flats), commercial work (offices, shops, warehouses), and industrial work (factories, plant rooms). Understanding BS 7671 alone is not enough — you also need to understand BS 5266-1:2025 and BS EN 1838 to design and install emergency lighting systems correctly.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

03 · Regulations

BS 7671 Wiring Requirements for Emergency Lighting

Emergency lighting is not just a fire-safety discipline — it is a wiring discipline governed by BS 7671:2018+A4:2026. Three regulations are particularly important for electricians installing or inspecting these systems.

  • Reg 560.9 — The three-standard compliance chain. BS 7671 Reg 560.9 states: "Emergency lighting systems shall comply with BS 5266-1:2025, BS EN 1838:2024 and BS EN 50172." All three standards must be satisfied — BS 5266-1:2025 for design and installation practice, BS EN 1838 for illuminance performance, and BS EN 50172 for the system as a whole. Specifying compliance with only one is not sufficient.
  • Reg 740.415.1 — Battery supply on the same RCD as normal lighting. In amusement parks and fairground installations (Chapter 74), the supply to a battery-operated emergency lighting circuit shall be connected to the same RCD protecting the associated lighting circuit. This ensures that a nuisance RCD trip on the normal lighting circuit does not leave emergency luminaires on a separate protected supply in an undefined state.
  • OSG Reg 7.4.1 — Circuit segregation. The On-Site Guide states: "Emergency lighting circuits shall be separated from other cables and from each other in compliance with BS 5266." This applies regardless of cable type. Fire alarm and emergency lighting circuits must each be segregated both from general wiring and from one another — simultaneous damage to both safety systems must be prevented.

When carrying out an EICR on a premises with emergency lighting, check that the system wiring is correctly segregated and that the circuit is identified on the distribution board schedule. Missing identification or mixed-circuit containment should be recorded as an observation code C2 or C3 depending on the risk presented.

04 · Regulations

Escape Route Lighting

Escape route lighting is the most critical component of an emergency lighting system. Its purpose is to illuminate the escape routes so that occupants can see where they are going during an evacuation. BS EN 1838 sets out the specific illuminance requirements:

  • Minimum 1 lux along the centre line of the escape route at floor level. The centre band (half the width of the route) must achieve at least 1 lux. The edge bands must achieve at least 0.5 lux (50% of the centre line value).
  • Uniformity ratio — the ratio of maximum to minimum illuminance on the escape route must not exceed 40:1. This prevents dark spots that could cause trips or falls.
  • 50% of required illuminance within 5 seconds. The emergency luminaire must achieve at least 50% of the required illuminance (0.5 lux on the centre line) within 5 seconds of the mains supply failing. Full illuminance (1 lux) must be achieved within 60 seconds.
  • Minimum duration of 3 hours. The emergency luminaire must maintain the required illuminance for at least 3 hours on battery power.

Emergency luminaires on escape routes should be positioned at every change of direction, at every change of floor level (stairways), at every intersection of corridors, at each final exit, immediately outside each final exit, near each first aid post, near each fire-fighting equipment point, and near each manual call point.

The positioning of luminaires is critical to achieving the uniformity requirement. Placing luminaires too far apart will create dark zones between them, while placing them too close together wastes equipment and increases maintenance costs. BS 5266-1:2025 provides guidance on luminaire spacing based on the mounting height and the light output of the luminaire.

05 · Regulations

Open Area (Anti-Panic) Lighting

Open area lighting (also called anti-panic lighting) is required in large open areas such as open-plan offices, shop floors, assembly halls, sports halls, and similar spaces exceeding 60m² in floor area. The purpose is to prevent panic and provide enough illumination for occupants to identify the escape routes and move safely towards them.

  • Minimum 0.5 lux at floor level across the entire open area. This is lower than the escape route requirement (1 lux) because the purpose is orientation, not detailed navigation.
  • Uniformity ratio — the ratio of maximum to minimum illuminance must not exceed 40:1.
  • Coverage — the 0.5 lux minimum must be achieved across the entire area, excluding a 0.5m border around the perimeter.
  • Duration — the same minimum of 3 hours applies, with 50% of required illuminance within 5 seconds and full illuminance within 60 seconds.

Open area lighting is often achieved by converting a proportion of the normal room luminaires to emergency operation (maintained or non-maintained with battery back-up packs). The designer must calculate how many luminaires need emergency conversion to achieve the 0.5 lux minimum across the area. Emergency lighting design software or manufacturer spacing tables are used to verify the design.

06 · Regulations

High-Risk Task Area Lighting

High-risk task area lighting is required where a sudden loss of normal lighting would create a direct hazard to the safety of the occupants. This applies to any work activity that involves a significant risk of injury if the lights go out — for example:

  • Machinery operation — workers operating lathes, presses, saws, or other dangerous machinery. A sudden loss of visibility while operating machinery could result in serious injury.
  • Chemical handling — areas where hazardous chemicals are handled, mixed, or stored. A loss of lighting could lead to spills, incorrect handling, or exposure to harmful substances.
  • Electrical switchrooms — a power failure in an electrical switchroom requires the operator to see clearly to carry out switching operations safely. Emergency lighting in switchrooms is essential.
  • Working at height — any area where workers are on scaffolding, ladders, or elevated platforms. A sudden loss of visibility could cause falls.

The illuminance requirement for high-risk task areas is significantly higher than for escape routes. BS EN 1838 specifies a minimum of 10% of the normal task illuminance or 15 lux, whichever is greater. The uniformity ratio must not exceed 10:1 (much tighter than the 40:1 for escape routes). The light must reach the required level within 0.5 seconds of mains failure — much faster than the 5-second requirement for escape routes.

This high requirement means that high-risk task area emergency lighting often needs higher-output luminaires with fast-response light sources (LEDs are ideal for this as they reach full output virtually instantly).

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
07 · Regulations

Standby Lighting

Standby lighting is not strictly part of the emergency escape lighting system, but it is covered by BS 5266-1:2025. Standby lighting is provided to enable normal activities to continue during a mains power failure. It is used in situations where a complete shutdown is not acceptable — for example:

  • Hospital operating theatres — surgical procedures cannot be interrupted by a power failure. Standby lighting (usually from a generator) provides full working illumination until the normal supply is restored.
  • Data centres — standby lighting allows staff to continue working during a power outage while the UPS and generator maintain server operations.
  • Control rooms — building management system control rooms, security monitoring centres, and similar facilities where continuous operation is essential.

Standby lighting is typically powered by a generator or central battery system with an automatic changeover switch. The illuminance level for standby lighting is determined by the specific requirements of the activity — it is often the same as the normal lighting level. The standby lighting system must be designed to integrate with the emergency escape lighting so that both systems can operate simultaneously during a mains failure.

Remedial estimator for emergency lighting defects

Found faulty emergency luminaires during testing? Elec-Mate's remedial works estimator prices each replacement — luminaire cost, labour…

Try it free for 7 days
Download on the App StoreGet it on Google Play
08 · Regulations

Central Battery Systems vs Self-Contained Luminaires

Emergency lighting systems fall into two primary architectures. Understanding the difference is essential for correct design, installation, and certification.

  • Self-contained luminaires. Each luminaire contains its own rechargeable battery, charger, and control gear. Installation is straightforward — each fitting is wired to the normal lighting circuit. Battery replacement is distributed across many individual units, which increases maintenance labour in larger buildings. Self-contained units with automatic self-test functions reduce the manual testing burden but do not eliminate the requirement to record and review results.
  • Central battery systems. A single central power supply unit (conforming to BS EN 50171 per BS 5266-1:2025 Clause 7.2) feeds all emergency luminaires from one location. This simplifies battery management — batteries are in one place — but introduces a single point of failure if the central unit is not correctly maintained. A critical installation requirement: all wiring on centrally powered runs must be fire-resistant cable (BS 5266-1:2025 Clause 8.2.1). Using standard building cable on these runs is one of the most common installation mistakes. Battery rooms serving central systems also require adequate ventilation to prevent the build-up of hydrogen gas during charging.

Common installation mistake — centrally powered systems

Standard twin-and-earth or standard SWA cable is not acceptable for the final circuit wiring of a centrally powered emergency lighting system. BS 5266-1:2025 Clause 8.2.1 requires fire-resistant cable (such as MICC or FP200 Gold equivalent) so that the circuit survives long enough in a fire to serve its purpose. Retain documentary evidence that the installed central power supply unit conforms to BS EN 50171.

09 · Regulations

Testing Intervals: Daily, Monthly, and Annual

Regular testing of emergency lighting is essential to ensure the system will function when needed. BS 5266-1:2025 defines a clear testing schedule:

  • Daily — Visual check. Where practicable, a visual check should be made to confirm that the green charging indicator on each self-contained luminaire is illuminated. This indicates the battery is charging normally. Any luminaire with a red fault indicator or no indicator light should be investigated.
  • Monthly — Functional test. Simulate a mains failure by switching off the supply to the emergency lighting circuit (or using a test switch on each luminaire). Check that each luminaire switches to battery mode within 5 seconds and provides adequate illumination. The test should last long enough to confirm operation but keep the discharge short — typically a few minutes. Record the results in the emergency lighting log book, noting any luminaires that fail to illuminate or show signs of reduced light output.
  • Annually — Full rated duration test. Discharge the batteries for the full rated duration (typically 3 hours). At the end of the test period, check that each luminaire is still providing adequate illumination. After the test, restore the mains supply and check that each luminaire recharges fully within 24 hours. Any luminaire that fails to maintain output for the full duration or fails to recharge must be replaced. This test should be carried out at a time that minimises disruption — ideally during daylight hours in a building with windows, or outside normal working hours.

Many modern self-contained emergency luminaires include automatic self-test functionality. These luminaires automatically carry out a brief functional test (30 seconds to 1 minute) at regular intervals and a full duration test once a year. The results are indicated by LED status lights on the luminaire. Self-testing luminaires reduce the manual testing burden but do not eliminate it entirely — the results must still be checked and recorded.

EICR/periodic inspection trap — insulation resistance testing

GN3 Reg 2.23 states: emergency lighting circuits and equipment shall be disconnected or isolated before performing insulation resistance tests. Applying the 500 V DC test voltage to connected emergency luminaires will damage the control gear and batteries, and will produce false high-resistance readings that invalidate the test results. This is a common mistake on first-time EICR visits to premises with emergency lighting — always identify and isolate emergency lighting circuits before starting IR testing.

All test results must be recorded in an emergency lighting log book, which should be kept on the premises and available for inspection by the fire authority. The log book should record the date, time, type of test, results, and any remedial action taken.

10 · Regulations

Emergency Lighting Certification with Elec-Mate

Proper documentation is essential for emergency lighting systems. Clients need test certificates to demonstrate compliance with the Fire Safety Order, and the fire authority can request evidence of regular testing at any time. Elec-Mate provides everything you need to manage emergency lighting work efficiently:

Certificate validity — three required documents

A BS 5266-1:2025 completion or periodic certificate is only valid when accompanied by all three of the following:

  1. A current signed checklist and inspection report.
  2. Photometric design data in an accepted format — authenticated spacing data, Annex D calculations, CIBSE/SLL LG12 calculations, or site test light readings — with all de-rating factors identified.
  3. The site test log book.

Issuing a certificate without the signed checklist, providing photometric data in an unidentified format, or omitting de-rating factors are the most common handover failures. A certificate handed over without these documents is technically incomplete.

Emergency Lighting Certificate

Elec-Mate includes a dedicated emergency lighting certificate template compliant with BS 5266-1:2025. Complete the certificate on your phone during the test, record luminaire statuses, and export as a professional PDF. Send it to the client by email or WhatsApp before you leave.

Photo Documentation

Attach photos of failed luminaires, damaged fittings, or compliance issues directly to the certificate. The photos are embedded in the PDF, providing clear evidence to the client and the fire authority.

Quoting and Invoicing

Found failed luminaires during testing? Use Elec-Mate's quoting tool to price the replacements and send the quote alongside the test report. Then invoice the client directly from the app. Complete the entire workflow on site — no desk time.

BS 5266 Training Course

Study BS 5266-1:2025 with Elec-Mate's structured training modules. Covers system design, luminaire siting, illuminance requirements, testing procedures, and certification. Part of the 46+ course library. Plus flashcards and mock exams.

Emergency lighting testing made efficient

Elec-Mate streamlines the entire emergency lighting workflow — testing, certification, defect reporting, quoting, and invoicing.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions About BS 5266 Emergency Lighting

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Emergency Lighting Certificates on Your Phone

Create professional BS 5266-compliant emergency lighting certificates with Elec-Mate. Complete testing, certification, quoting, and invoicing on site. Plus 46+ training courses and 70+ calculators. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy