BS 7671 SECTION 710

BS 7671 Section 710 Medical Locations

Electrical installation requirements for hospitals, dental surgeries, clinics and other medical premises. Covers group 0/1/2 classification, medical IT systems, AFDD and RCD rules, and the SELV/PELV voltage modifications required by BS 7671:2018+A4:2026.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

14 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Section 710 classifies medical locations into groups 0, 1 and 2 — different protection requirements apply to each.
  • 2Medical IT systems are mandatory for group 2 locations supplying life-support equipment, and must include insulation monitoring.
  • 3AFDDs (arc fault detection devices) are prohibited in circuits of medical locations of group 0 and group 2, and in any circuit supplied by a medical IT system (Regulation 710.421.1.7 and 710.421.1.7.101).
  • 4RCDs are required for additional protection on group 2 final circuits under Regulation 710.411.4.205(b), and on group I equipment circuits rated ≤ 32 A under sub-clause (a). RCDs must not be installed on final circuits supplied by a medical IT system (NOTE to 710.411.4.205 — advisory "should not").
  • 5SELV/PELV voltage limits in medical locations of group 1 and group 2 are reduced to 25 V AC RMS or 60 V ripple-free DC (Regulation 710.414.1.101) — modifying the values in Regulations 419.2 and 419.3.
  • 6Measured total leakage current for a medical IT transformer plus all connected final circuits (without load) must be 10 mA or less to meet Regulation 710.555.201.
  • 7Where ADS cannot achieve the required disconnection times in group 1 or group 2, supplementary protective equipotential bonding per Regulation 710.415.2 is mandatory and is deemed to comply with the 25 V AC / 60 V DC Uc limit in Regulation 710.419.3.
  • 8Group 2 medical locations require full overcurrent selectivity: a short-circuit on any final circuit shall not interrupt the incoming circuits of the upstream distribution board (Regulation 710.535.1.101).
01 · BS 7671 Section 710

Medical Location Groups 0, 1 and 2

Section 710 of BS 7671:2018+A4:2026 covers electrical installations in medical locations — hospitals, dental surgeries, GP clinics, veterinary practices, ambulance stations and similar premises where patients receive examination or treatment using electrical equipment. The section sits within Part 7 (Special Installations or Locations) and applies in addition to the general requirements of Chapters 41-54.

Medical locations are classified into three groups based on the type of medical procedure performed and the consequences of an electrical supply interruption:

  • Group 0 — medical locations in which no applied parts are intended to be used. Examples: massage rooms, consulting rooms with no patient contact equipment.
  • Group 1 — medical locations in which applied parts are intended to be used externally or internally, except in group 2 procedures. Examples: dialysis rooms, dental surgeries, MRI rooms.
  • Group 2 — medical locations in which applied parts are intended to be used in procedures such as intracardiac procedures, vital treatments and surgical operations where interruption of supply can cause danger to life. Examples: operating theatres, intensive care units, cardiac catheter labs.

Group classification matters for every protective decision

Annex A710 of BS 7671 provides informative guidance on allocating group numbers, but it is a guide only — Regulation 710.3 sets the actual classification rules. The risk classification must be made by the medical staff using the location, in consultation with the designer.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · BS 7671 Section 710

Medical IT Systems

Medical IT systems are isolating power supplies used in group 2 medical locations to supply life-support and similar critical equipment. The IT (isolé-terre) earthing arrangement keeps both live conductors isolated from earth, so a single insulation fault does not interrupt supply — critical for procedures where unexpected disconnection could endanger life.

Prohibition on RCDs — medical IT final circuits

Regulation 710.415 uses "shall not" — an absolute prohibition on additional protection by RCD on final circuits supplied by a medical IT system. The NOTE to Regulation 710.411.4.205 also advises that RCDs "should not" be provided for medical IT circuits (advisory language). Both point to the same outcome: RCDs on medical IT final circuits are non-compliant. If found during EICR, record as a C1/C2 observation and require remedial action.

  • Medical IT systems must include insulation monitoring (MED-IMD) — a dedicated device that continuously monitors the insulation resistance of the IT system and alarms on degradation.
  • Live conductors of medical IT final circuits must be identified by alphanumeric markings L1 and L2 in addition to the standard brown insulation colour.
  • For verification, total leakage current of the medical IT transformer plus all connected final circuits (with no load) must measure 10 mA or less (Regulation 710.555.201).
  • Automatic transfer switching to a safety source must operate within times specified in Regulation 710.536.101 so that 90% of luminaires in group 2 rooms remain supplied by a safety source during normal supply failure.
03 · BS 7671 Section 710

AFDD Prohibitions (A4:2026)

BS 7671 Amendment 4 introduced wider AFDD (arc fault detection device) requirements across many installation types, but medical locations have specific prohibitions that override the general rules:

  • Regulation 710.421.1.7 — AFDDs shall not be used in circuits in medical locations of group 0 and group 2.
  • Regulation 710.421.1.7.101 — AFDDs shall not be used in circuits supplied by IT systems specified as medical IT systems in Regulation 710.411.6.
  • The prohibition does not list group 1 medical locations explicitly — AFDDs are not blanket-prohibited there, but designers must consult related regulations before installing them.

AFDD already installed? Remove and document

If during inspection an AFDD is found on a medical IT system circuit, the responsible person or installer must remove or disable it to comply with Regulation 710.421.1.7.101. The change must be recorded on the circuit documentation and the client informed.

04 · BS 7671 Section 710

RCD Protection for Group 2 Final Circuits

Additional protection by RCDs is mandatory for final circuits in group 2 medical locations under Regulation 710.411.4.205(b). Sub-clause (a) also requires RCDs on circuits supplying group I medical equipment with a rated current not exceeding 32 A. Circuits rated above 32 A supplying group I equipment are not captured by sub-clause (a). The NOTE to Regulation 710.411.4.205 uses "should not" (advisory) for medical IT circuits — distinct from the absolute "shall not" prohibition in Regulation 710.415 for medical IT final circuits.

  • RCDs used for additional protection must have the characteristics specified in Regulation 415.1.1 (30 mA rated residual operating current, disconnection within the times in Table 41.1).
  • Type AC RCDs are prohibited in medical locations of group 1 and group 2 — Type A or Type F (or higher) must be selected to handle DC fault current components from medical equipment.
  • Where RCDs are required on a final circuit, the protective measure of automatic disconnection of supply (ADS) must satisfy Section 411 in addition to the RCD requirement.
05 · BS 7671 Section 710

SELV and PELV Voltage Limits in Medical Locations

Where SELV or PELV circuits are used in medical locations of group 1 and group 2, BS 7671 modifies the standard extra-low voltage limits. Regulation 710.414.1.101 reduces the nominal voltage that may be applied to current-using equipment to:

Reduced ELV limits in medical locations

Maximum 25 V AC RMS, or maximum 60 V ripple-free DC. These limits modify Regulations 419.2 and 419.3 and apply specifically to current-using equipment supplied from SELV/PELV circuits inside group 1 and group 2 medical locations.

Functional extra-low voltage (FELV) shall not be used as a method of protection against electric shock in medical locations, irrespective of the voltage value (Regulation 710.411.7). This is an absolute prohibition specific to medical locations.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · BS 7671 Section 710

Supplementary Protective Equipotential Bonding (Regs 710.415.2 and 710.419.3)

Where automatic disconnection of supply (ADS) cannot be achieved within the required times in group 1 or group 2 medical locations, Regulations 710.415.2 and 710.419.3 require that the conventional touch voltage Uc shall not exceed 25 V AC or 60 V DC. A supplementary protective equipotential bonding system installed in accordance with these regulations is deemed to meet this requirement.

  • Supplementary bonding connects all simultaneously accessible conductive parts and extraneous-conductive-parts within the medical location to reduce potential differences to safe levels.
  • The 25 V AC / 60 V DC Uc limit applies to IT, TN and TT earthing systems in group 1 and group 2 locations — modifying the values in Regulation 419.3.
  • Resistance of supplementary protective equipotential bonding conductors must be recorded in the Schedule of Test Results per Regulation 653.2 (as required for medical location certification).
  • Where ADS cannot be achieved and supplementary bonding is used as the deemed-to-comply route, this must be documented in the installation design records and on the certification.

Supplementary bonding is not optional where ADS fails

If fault loop impedance measurements confirm that ADS disconnection times cannot be met in a group 1 or group 2 medical location, supplementary protective equipotential bonding is mandatory under Regulation 710.415.2. The bonding conductor resistance must be measured and recorded — it cannot be assumed from visual inspection alone.

07 · BS 7671 Section 710

Overcurrent Selectivity for Group 2 Locations (Reg 710.535.1.101)

Regulation 710.535.1.101 introduces a mandatory selectivity requirement specific to group 2 medical locations. Selectivity (discrimination) between overcurrent protective devices shall be required for any prospective overcurrent. In the event of a short-circuit on a final circuit, the incoming circuits of the upstream distribution board shall not be interrupted.

  • The design of distribution boards supplying group 2 locations must demonstrate full discrimination — final-circuit devices operate before the upstream incomer trips.
  • Achieving selectivity requires co-ordination of time-current characteristics between final-circuit protective devices and upstream incoming protective devices.
  • Staged fault tests or documented time-current curve analysis provide the verification evidence that incoming circuits remain energised during a downstream short-circuit.
  • Failure to achieve selectivity in a group 2 location is a non-compliance — a single final-circuit fault could interrupt supply to multiple life-support circuits.

Selectivity must be designed in — it cannot be retrofitted easily

Selectivity for group 2 distribution boards must be considered at the design stage. Retrospective changes to achieve discrimination (replacing devices, adding current-limiting fuses, redesigning boards) are significantly more disruptive than designing for it from the outset. Check manufacturers’ co-ordination tables and record the evidence at verification.

08 · BS 7671 Section 710

Inspection, Testing and Verification

Medical locations require additional inspection and test items beyond a standard EICR. Verification covers:

  • Medical IT transformer total leakage current measurement (≤ 10 mA per Regulation 710.555.201) with no load and all final circuits connected.
  • Insulation monitoring device (MED-IMD) functionality test and alarm chain verification.
  • Automatic transfer switching to safety source — operation timing verified against Regulation 710.536.101.
  • Confirmation that no RCDs are installed on medical IT final circuits.
  • Confirmation that no AFDDs are installed on group 0/group 2 circuits or on medical IT circuits.
  • L1/L2 alphanumeric markings present on medical IT final circuit live conductors.
  • Type AC RCD audit — no Type AC RCDs in group 1 or group 2 locations.
  • Supplementary protective equipotential bonding conductor resistance recorded in the Schedule of Test Results (Reg 710.415.2 / 653.2) where ADS disconnection times cannot be met.
  • Overcurrent selectivity evidence for group 2 distribution boards — confirm upstream incoming circuits are not interrupted by a final-circuit short-circuit fault (Reg 710.535.1.101).

Periodic inspection interval — medical locations

IET Guidance Note 3 recommends a maximum periodic inspection interval of 1 year for hospitals, and 3 years for surgeries and clinics. Group 2 locations supporting life-support equipment may require shorter intervals based on a risk assessment.

How to apply Section 710 on a real medical project

Practical sequence for an electrician or designer working on a hospital, dental surgery, clinic, or veterinary practice installation.

1

Classify the medical location group

Before any design decision, agree the group number (0, 1, or 2) with the medical staff using the location. Document the classification — every subsequent protection decision depends on it. Refer to Regulation 710.3 and Annex A710.

2

Identify circuits supplied by a medical IT system

Trace every final circuit in a group 2 location to determine whether it is supplied from a medical IT system or from a TN/TT system. Medical IT circuits have specific prohibitions (no RCDs, no AFDDs, L1/L2 marking required) that override general rules.

3

Select RCDs and AFDDs by group and earthing arrangement

For group 2 final circuits NOT supplied by a medical IT system, install 30 mA RCDs (Type A minimum, not Type AC). For medical IT final circuits, do not install RCDs or AFDDs. Document the rationale on the circuit schedule.

4

Apply reduced SELV/PELV voltage limits

In group 1 or group 2 locations, any SELV/PELV current-using equipment must be limited to 25 V AC RMS or 60 V ripple-free DC. Confirm equipment ratings against this limit before specifying.

5

Design and verify overcurrent selectivity for group 2 boards

For every distribution board supplying group 2 circuits, confirm full discrimination between final-circuit devices and upstream incoming protective devices (Regulation 710.535.1.101). Use manufacturers' co-ordination tables or time-current curves to demonstrate that a final-circuit short-circuit will not operate the incomer. Record the evidence — staged fault tests or documented analysis — in the O&M pack.

6

Check supplementary bonding where ADS disconnection times cannot be met

If fault loop impedance measurements confirm that ADS cannot achieve the required disconnection times in a group 1 or group 2 location, supplementary protective equipotential bonding must be installed per Regulation 710.415.2. Measure bonding conductor resistance and record in the Schedule of Test Results to meet Regulation 653.2.

7

Verify medical IT leakage at handover

Measure total leakage of the medical IT transformer plus all final circuits with no load. If above 10 mA, the installation does not meet Regulation 710.555.201 — locate the offending circuit and remediate before sign-off.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Run medical location inspections with confidence

Elec-Mate ships the digital EICR tool, 70+ calculators and A4:2026 reference materials UK electricians use on hospital and clinic projects. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy