BS 7671 GUIDE

AFDD Arc Fault Detection
BS 7671 Requirements Explained

Arc Fault Detection Devices (AFDDs) are becoming increasingly important in UK electrical installations. This guide explains what AFDDs are, how they work, where BS 7671 requires them, the difference between AFDDs and RCBOs, installation requirements, and the practical considerations for electricians specifying them.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

15 min readUpdated 2026-05-18Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1AFDDs detect dangerous arc faults (both series and parallel) that cannot be detected by MCBs, RCDs, or RCBOs. They protect against electrical fires caused by damaged cables, loose connections, and deteriorated insulation.
  • 2BS 7671 Regulation 421.1.6 recommends AFDDs in locations with sleeping accommodation in higher-risk premises — HMOs, buildings over 4 storeys, care homes, student accommodation, and premises with combustible construction.
  • 3AFDDs are not a replacement for MCBs or RCDs — they provide an additional layer of protection. Most AFDD units combine arc detection with RCBO functionality (30mA RCD + MCB + AFDD in one device).
  • 4Major manufacturers include Siemens, Schneider Electric, and Hager. Typical cost is £80 to £150 per device — significantly more than a standard RCBO at £25 to £50.
  • 5Elec-Mate certificate forms include AFDD fields, and the AI regulations lookup explains exactly where AFDDs are recommended under BS 7671.
01 · BS 7671 Guide

What Are Arc Fault Detection Devices?

An Arc Fault Detection Device (AFDD) is a protective device designed to detect dangerous electrical arc faults and disconnect the circuit before the arc can start a fire. Arc faults occur when electricity jumps across a gap between conductors — for example, through damaged cable insulation, at a loose terminal connection, at a cracked conductor, or through carbonised material in an aged accessory.

Arc faults are particularly dangerous because they can generate temperatures exceeding 6,000 degrees Celsius at the point of arcing — hot enough to ignite surrounding materials including cable insulation, timber, plasterboard, and soft furnishings. Yet the current flowing through an arc fault may be too small to trip a conventional MCB or fuse, and the fault does not produce the earth leakage that an RCD detects. This means a dangerous arc can persist for extended periods, gradually heating surrounding materials until a fire starts.

There are two types of arc fault that AFDDs protect against:

Series Arc Faults

Occur when a conductor breaks or a connection loosens within the circuit, creating a gap that current arcs across. The current is limited by the load impedance, so it is always less than the normal load current — an MCB will never trip. The arc generates intense heat at the fault point. Common causes include nails or screws driven through cables, rodent damage, cables crushed during building work, and aged connections that have loosened over time.

Parallel Arc Faults

Occur when insulation between line and neutral (or line and earth) deteriorates to the point where current arcs between the conductors. The current is limited by the arc impedance, which can vary from near-short-circuit to just a few amps. Small parallel arcs may not draw enough current to trip an MCB. If the arc is between line and earth, an RCD should detect it — but line-to-neutral arcs produce no earth leakage and will not trip an RCD.

Electrical Safety First estimates that electrical faults cause around 14,000 house fires per year in the UK, with faulty wiring, cables, and connections being among the leading causes. AFDDs address a critical gap in protection that conventional devices cannot fill.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · BS 7671 Guide

How AFDDs Work

AFDDs use sophisticated electronic analysis to distinguish between dangerous arc faults and the normal arcing that occurs during everyday electrical operation. This distinction is critical — a light switch produces a brief arc every time it is operated, a motor produces arcing at its commutator brushes, and many electronic devices produce switching transients that look superficially like arcs. An AFDD must detect genuinely dangerous arcs without nuisance tripping on these normal events.

The detection method relies on analysing the high-frequency noise signature superimposed on the 50Hz power waveform. When an arc occurs, it produces a characteristic pattern of high-frequency current fluctuations (typically in the kilohertz to megahertz range) that differ from normal switching transients. The AFDD contains a microprocessor that continuously samples the current waveform and applies algorithmic analysis to identify these arc fault signatures.

The AFDD analyses several characteristics of the current waveform:

  • High-frequency noise content — Arcs produce broadband high-frequency noise that normal loads do not. The AFDD monitors the frequency spectrum of the current for patterns consistent with arcing.
  • Current irregularities at zero-crossing — Arcs tend to extinguish momentarily as the AC waveform passes through zero and re-ignite as the voltage rises, creating characteristic discontinuities in the current waveform.
  • Duration and persistence — Normal switching events are brief (milliseconds). Dangerous arc faults persist for multiple cycles and show repeating patterns. The AFDD requires the signature to persist for a minimum number of half-cycles before tripping.
  • Current amplitude changes — The AFDD monitors for the random amplitude variations characteristic of an unstable arc, as opposed to the stable, predictable current drawn by a normal load.

AFDDs are manufactured to BS EN 62606, which sets out the performance requirements and test methods. The standard defines specific arc fault test scenarios that the device must detect, and specific non-arc scenarios that must not cause tripping. This standardisation ensures consistent performance across manufacturers.

03 · BS 7671 Guide

Where AFDDs Are Required by BS 7671

BS 7671 Regulation 421.1.6 was introduced in Amendment 2 to the 18th Edition and provides a recommendation (not a mandatory requirement) for the use of AFDDs. The regulation states that arc fault detection devices conforming to BS EN 62606 are recommended to provide additional protection against fire caused by arc faults in AC final circuits.

The regulation specifically recommends AFDDs for circuits in the following locations:

Locations Where AFDDs Are Recommended

  • Houses in Multiple Occupation (HMOs) — HMOs present a higher fire risk due to multiple independent households sharing a building, often with modified wiring, high occupancy, and limited means of escape. AFDDs add fire protection to circuits serving individual lettings.
  • Buildings with sleeping accommodation above the fourth floor — In buildings over four storeys, escape in the event of fire takes longer and is more dangerous. AFDDs provide earlier detection of electrical faults that could start fires.
  • Care homes and residential homes — Occupants may have limited mobility or awareness, making them more vulnerable in a fire. Electrical fire prevention is critical in these settings.
  • Student accommodation — High occupancy, high use of electrical equipment, and sleeping accommodation create a combination of risk factors that AFDDs help to mitigate.
  • Premises with combustible construction — Timber-framed buildings, buildings with thatched roofs, and properties with significant combustible materials in the structure are at higher risk from electrical fires. AFDDs provide an additional layer of protection for cables running through combustible materials.
  • Locations with a risk of fire due to stored materials — Premises where combustible materials, goods, or products are stored close to electrical circuits — including some commercial and retail premises.

It is important to note that the regulation uses the word "recommended" rather than "shall" — AFDDs are not currently a mandatory requirement under BS 7671. However, the trend in the industry is clear: AFDDs are increasingly being specified by designers and clients, and it is likely that future amendments will strengthen the recommendation towards a requirement, as has happened previously with RCDs and SPDs.

Some local authority building control departments and fire officers are already requiring AFDDs for specific applications, particularly in HMOs and care homes. When working on these types of premises, check the specific requirements with the local authority before finalising the design.

04 · BS 7671 Guide

AFDD vs RCBO — What Is the Difference?

An AFDD and an RCBO protect against completely different types of fault, and one is not a substitute for the other. In practice, most modern AFDD devices combine all three functions — arc fault detection, RCD, and MCB — into a single unit, but understanding the distinction is important.

MCB

Protects against overcurrent — short circuits and sustained overloads. Trips when current exceeds the device rating. Does not detect arc faults or earth leakage.

Detects: Overcurrent only

RCBO

Combines MCB and RCD in one device. Protects against overcurrent AND earth leakage (residual current). Does not detect arc faults — particularly series arcs and line-to-neutral parallel arcs.

Detects: Overcurrent + earth leakage

AFDD/RCBO

Combines all three functions — arc fault detection, RCD, and MCB. Protects against overcurrent, earth leakage, AND arc faults. Provides the most comprehensive circuit protection currently available.

Detects: Overcurrent + earth leakage + arc faults

The key point is that an AFDD addresses a protection gap that RCBOs cannot fill. A series arc fault produces current that is always less than the normal load current (so the MCB element will not trip) and creates no earth leakage (so the RCD element will not trip). Only the arc fault detection function can identify the characteristic signature of the arc and disconnect the circuit. For this reason, AFDDs are specified in addition to existing protection, not as a replacement.

When specifying AFDDs, most electricians choose combined AFDD/RCBO devices that replace the standard RCBO in the consumer unit. This provides all three levels of protection from a single device, occupying a single (wider) module position in the distribution board.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
05 · BS 7671 Guide

AFDD Installation Requirements

Installing AFDDs is straightforward from a wiring perspective — the device replaces a standard RCBO in the distribution board. However, there are several practical considerations that affect the design and specification.

  • Board compatibility — AFDD/RCBO devices are wider than standard RCBOs (typically 2 modules instead of 1). The consumer unit or distribution board must have sufficient space. Some manufacturers produce boards specifically designed to accommodate AFDDs with the correct bus-bar configuration.
  • Wiring method — Both the line and neutral conductors for the protected circuit must pass through the AFDD. This is similar to an RCBO installation — the neutral is connected to the device, not to the common neutral bar.
  • One AFDD per circuit — Each final circuit that requires AFDD protection must have its own device. AFDDs cannot protect multiple circuits through a single unit because the arc detection algorithm needs to analyse the current signature of an individual circuit.
  • Circuit length and cable type — Some AFDD manufacturers specify maximum circuit lengths or restrictions on cable types. Long circuits with high capacitance (such as lengthy runs of SWA cable) can affect the high-frequency analysis. Check manufacturer guidance for specific limitations.
  • Testing — AFDDs have a built-in test button that simulates an arc fault to verify the trip mechanism. This should be tested at commissioning and during periodic inspection. There is currently no standardised instrument test for AFDDs — the built-in test is the primary verification method.

Certificate Forms Include AFDD Fields

Elec-Mate's EIC and EICR forms include dedicated fields for recording AFDD protection on each circuit.

Try it free for 7 days
Download on the App StoreGet it on Google Play
06 · BS 7671 Guide

AFDD Manufacturers and Cost

The UK market for AFDDs has grown significantly since their introduction to BS 7671. The main manufacturers offering AFDD devices compatible with UK consumer units and distribution boards are:

Siemens (5SV6 series)

Siemens was one of the first manufacturers to bring AFDDs to the UK market. Their 5SV6 series combines AFDD, 30mA RCD, and MCB in a single 2-module-wide device. Available in ratings from 6A to 40A with Type B or Type C curve. Compatible with Siemens consumer units and some other manufacturers' boards via adaptors. Typical trade price £90 to £130.

Schneider Electric (iC60 AFDD series)

Schneider offers AFDD/RCBO combination devices in their iC60 range. Available in ratings from 6A to 40A. The devices are 3 modules wide in the Schneider format. Compatible with Schneider Acti 9 distribution boards. Schneider also offers standalone AFDD modules that can be added upstream of an existing RCBO. Typical trade price £100 to £150.

Hager (AFDD series)

Hager offers combined AFDD/RCBO devices compatible with their consumer unit and distribution board ranges. Available in common domestic ratings. Hager has also developed consumer units with AFDD-ready bus-bar configurations, making retrofitting easier. Typical trade price £85 to £120.

The cost differential between a standard RCBO (typically £25 to £50) and an AFDD/RCBO (typically £80 to £150) is significant — roughly doubling or tripling the cost per circuit. For a typical 10-way domestic consumer unit, using AFDDs on every circuit would add approximately £500 to £1,000 to the installation cost. This is the main barrier to wider adoption and the reason the regulation currently recommends rather than requires AFDDs.

Many electricians take a pragmatic approach, installing AFDDs on the highest-risk circuits — bedrooms, living rooms, and circuits running through combustible building elements — while using standard RCBOs on lower-risk circuits such as the cooker and immersion heater.

07 · BS 7671 Guide

Practical Considerations for Electricians

Before specifying AFDDs on a job, there are several practical factors to consider beyond the regulatory recommendation.

Nuisance tripping

Early AFDD devices had a reputation for nuisance tripping, particularly on circuits supplying equipment with electronic switching (LED drivers, switch-mode power supplies, motor speed controllers). Newer generations have significantly improved algorithms that better distinguish between dangerous arcs and normal switching signatures. Always use the latest hardware revision from the manufacturer and check for compatibility with the specific loads on the circuit.

Board space

AFDD/RCBO devices are wider than standard RCBOs. A consumer unit that accommodates 12 standard RCBOs may only fit 6 to 8 AFDD devices. When specifying a new installation with AFDDs, you may need a larger board or a dedicated AFDD-ready board. When retrofitting AFDDs into an existing installation, board replacement may be necessary.

Client cost expectations

The additional cost of AFDDs needs to be discussed with the client. Explain the fire protection benefit clearly and let the client make an informed decision. For HMOs, care homes, and other high-risk premises where AFDDs are recommended by BS 7671, include them in the specification as standard and quote accordingly.

As the technology matures and costs reduce — a trend that has already begun — AFDDs will likely become as standard as RCDs are today. Forward-thinking electricians are already gaining experience with AFDDs and discussing them with clients as part of the design process. The RCD types guide covers the complementary protection provided by different RCD types alongside AFDDs.

AI Regulations Lookup for AFDD Requirements

Not sure if AFDDs are needed on your current job? Ask Elec-Mate's AI regulations agent. Describe the premises type and the AI will explain exactly which…

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Certify AFDD Installations Digitally

Elec-Mate's certificate forms include AFDD fields, AI regulations lookup, and consumer unit design guidance. Join 1,000+ UK electricians. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy