BS 7671 Section 716: Power over Ethernet explained

Amendment 4 to BS 7671, issued on 15 April 2026, added a new Section 716 for distributing extra-low voltage DC power over data cabling. It is the section that applies to Power over Ethernet lighting, cameras, access points and other PoE devices.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 2,100+ UK electricians

7 min readUpdated 2026-10-28Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

The short answer

Does BS 7671 cover Power over Ethernet?

Yes. Section 716, added by Amendment 4:2026, applies to ELV DC power distributed over balanced data cables and accessories to BS EN 50173-1, including Power over Ethernet. The circuits must be SELV or PELV, the current in any conductor must not exceed 750 mA, and the cable must be Category 5 or above as listed in Regulation 716.521.101.

2,100+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5

Key takeaways

  1. 01Section 716 is new in BS 7671:2018+A4:2026. It covers ELV DC power over data cabling, including Power over Ethernet, and the use of existing data cabling for power. It does not apply to private branch exchange (PBX) cabling.
  2. 02The protective measure must be SELV or PELV (Regulation 716.410.3.3).
  3. 03The source must be power sourcing equipment to BS EN IEC 62368-1 and BS EN 60950-22, or another SELV/PELV source limited to 60 V ripple-free DC in dry locations and 15 V in other locations (Regulation 716.414.1.1).
  4. 04A source of the second kind must not feed data cabling that passes through or serves bathrooms, swimming pools, saunas, restrictive conductive locations or medical locations (Regulation 716.414.3.201).
  5. 05The load current in any conductor must not exceed 750 mA (Regulation 716.523.2.101), and connectors must support 750 mA per contact (Regulation 716.526.101).
  6. 06Cables must be Category 5, 6, 6A, 7, 7A, 8.1 or 8.2, or another cable defined in BS EN 50173-1 (Regulation 716.521.101).

01 · A4:2026 Change

What Section 716 covers

Regulation 716.1 applies the section to the distribution of ELV DC power using balanced information technology cables and accessories designed mainly for data, as specified in BS EN 50173-1, with power feeding equipment to BS EN IEC 62368-3. It covers the design, erection and verification of data infrastructure that carries both data and power, and the use of existing data cabling to carry power.

The power delivery systems include, but are not limited to, Power over Ethernet as specified in ISO/IEC/IEEE 8802-3. Section 716 does not apply to cables and accessories for private branch exchange (PBX) telephone systems.

Where it came from

Section 716 is based on HD 60364-7-716:2023 and first appeared in BS 7671 with Amendment 4:2026. Before A4, PoE was often discussed under Section 715 (extra-low voltage lighting); it now has its own section.

Free download · PDF

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · A4:2026 Change

Protection: SELV or PELV, and the source

Regulation 716.410.3.3 requires the protective measure extra-low voltage provided by SELV or PELV. Regulation 716.414.1.1 then allows one of two kinds of source:

  1. Power sourcing equipment (PSE), such as a PoE switch or injector, conforming to BS EN IEC 62368-1 and BS EN 60950-22, and meeting the interoperability requirements of ISO/IEC/IEEE 8802-3.
  2. A source described in Regulation 414.3, at no more than 60 V ripple-free DC in dry locations and no more than 15 V ripple-free DC in all other locations.

The notes to Regulation 716.414.1.1 add that where PELV is used, measures may be needed to limit the sharing of LV fault currents (BS EN 50310 and BS IEC 61000-5-2), and that exposed-conductive-parts of DC power equipment such as PoE switches can be connected to the main earthing terminal by a protective conductor. The screen of the data cable provides functional earthing only; it is not suitable for limiting the sharing of LV fault currents.

03 · A4:2026 Change

Bathrooms and other special locations

Regulation 716.414.3.201 says a source of the second kind (a Regulation 414.3 source rather than PoE equipment to the product standards) shall not be used to power data cabling that passes through, or serves, the special locations of Sections 701 (bath and shower rooms), 702 (swimming pools and fountains), 703 (saunas), 706 (conducting locations with restricted movement) and 710 (medical locations).

Check the route, not just the device

The restriction applies to cabling that passes through one of these locations as well as cabling that serves equipment in it, so plan PoE routes around bathrooms and plant rooms with that in mind.

In the app

Try Elec-Mate free for 7 days

19 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Download on the App StoreGet it on Google Play

04 · A4:2026 Change

Cables, current and connectors

  • Cable type (Regulation 716.521.101): Category 5, 6, 6A, 7, 7A, 8.1 or 8.2, or other cables defined in BS EN 50173-1 by reference to the BS EN 50288 series.
  • Design current (Regulation 716.523.1.101): must not exceed the limit in BS EN 50173-1. The notes warn that temperature rise from load current increases attenuation and can degrade data performance, and point to PD CLC/TR 50174-99-1, BS ISO/IEC 14763-2 and ISO/IEC TS 29125 for cable bundles.
  • Maximum load current (Regulation 716.523.2.101): no more than 750 mA in any conductor.
  • Connecting hardware (Regulation 716.526.101): to BS ISO/IEC 11801-1 and able to carry 750 mA per contact continuously. Where equipment may be unplugged under load, connectors must pass the endurance test of BS EN 60512-9-3 at that load, and the expected number of disconnections must not exceed the tested figure.

05 · A4:2026 Change

Overcurrent protection

Regulation 716.433.1.101 recognises current limitation to BS EN IEC 62368-3:2020 clause 5.3.1 as a suitable means of protection against overcurrent. In practice that is the current limiting built into compliant power sourcing equipment.

The low voltage circuit that supplies the PoE switch or injector is an ordinary LV circuit, designed, protected, tested and certified under the rest of BS 7671.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from electricians and apprentices

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-day free trial

Certify the LV supply to every PoE switch

Elec-Mate issues BS 7671:2018+A4:2026 EICs and EICRs on your phone, with 70+ calculators for the circuits that feed your PoE equipment. 7-day free trial.

Start your free trial

From £6.99/mo after the trial — no charge until day 8.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in one tap — no calls, no hassle
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play
Certificate types
19Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists