RCD Testing Procedure: How to Test RCDs per BS 7671
The complete RCD testing procedure for UK electricians, updated for Amendment 4 — which deleted Table 3A and reduced verification to a single AC test at IΔn. Testing at 0 and 180 degree phase angle. Ramp test, button test, Type S time-delayed testing, and discrimination testing. BS 7671 compliant.
Under BS 7671:2018+A4:2026, an RCD's effectiveness is verified by an alternating-current test at its rated residual operating current (IΔn), whatever the device type — a general (non-delay) type must disconnect within 300 ms, a Type S between 130 ms and 500 ms (Regs 643.7.1 and 643.8), using test equipment to BS EN 61557-6 — and the integral test button is operated to confirm the test facility works (Reg 643.10). Run the test on both half-cycles (0° and 180°) and record the longer time. Amendment 4 deleted Table 3A of Appendix 3, so the old ½× and 5× tests are no longer part of the required verification — they remain useful diagnostics only.
1,600+
UK electricians
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Key takeaways
01Amendment 4 changed the test. Table 3A of Appendix 3 (time/current performance criteria for RCDs) has been deleted, and Regulations 643.7.1 (fault protection) and 643.8 (additional protection) now verify an RCD with a single alternating current test at the rated residual operating current, IΔn — whatever the device type, AC, A, F or B.
02A general (non-delay) RCD must operate within 300 ms at IΔn — that is the acceptance figure the A4 NOTE states, and it is what goes on the certificate. For a Type S (time-delayed) device the NOTE to Regulation 643.7.1 gives a band of 130 ms minimum to 500 ms maximum; the NOTE to Regulation 643.8 (additional protection) states only the 300 ms general non-delay figure.
03The half-rated and five-times tests are no longer part of the required verification. They remain genuinely useful for fault-finding, and 40 ms at 5x IΔn is still a device characteristic under BS EN 61008/61009 — but that is the product standard describing the device, not BS 7671 telling you what to test.
04Test on both positive (0 degree) and negative (180 degree) half-cycles — the worst-case (longest) trip time is the value recorded.
05The push-button test confirms the mechanical trip mechanism works but does NOT verify the electrical trip function — instrument testing is mandatory for compliance. Regulation 643.10 separately requires the effectiveness of any test facility incorporated in the device to be verified. BS 7671 Reg 514.12.2 requires a notice instructing occupants to test six-monthly by pressing the relevant test button(s), with an exception for domestic (household) premises where certification or an EICR complete with the Appendix 6 guidance for recipients has been issued.
06Elec-Mate validates all RCD trip times automatically against BS 7671 requirements and supports voice-to-test-results for hands-free data entry on site.
01 · Testing Guide
What Is RCD Testing?
What is the maximum trip time?
Pick the device and see the time BS 7671 accepts — and the test that actually applies since Amendment 4.
Changing the rating does not change the time. The acceptance time is the same for a 30 mA and a 300 mA general device — the rating sets the current you test at, not the time allowed.
Maximum permitted trip time
300 ms
General (non-delay) at IΔn (30 mA) — maximum
The test to run
One alternating-current test at IΔn (30 mA), whatever the device type — AC, A, F or B. Run it on both half-cycles (0° and 180°) and record the longer time.
Where the figure comes from
The NOTE to Regulation 643.7.1 (fault protection) and the NOTE to Regulation 643.8 (additional protection) both give 300 ms for a general non-delay device.
Not the ½× and 5× tests
Amendment 4 deleted Table 3A of Appendix 3, so the half-rated and five-times tests are no longer part of the required verification. BS EN 61008/61009 still quote 40 ms at five times rated current, but that describes how the device is built — not a test BS 7671 asks you to record.
Test equipment to BS EN 61557-6. Operate the integral test button as well, to confirm the test facility works (Regulation 643.10).
RCD (Residual Current Device) testing verifies that every RCD in an electrical installation — whether RCCB (Residual Current Circuit Breaker), RCBO (Residual Current Breaker with Overcurrent protection), or socket-outlet RCD — operates correctly at the specified current levels and within the required trip times. RCDs provide additional protection against electric shock by detecting small leakage currents to earth and disconnecting the supply before a lethal shock can occur.
RCD testing is test number seven in the GN3 testing sequence, performed after all dead tests and the other live tests (earth fault loop impedance and prospective fault current). It is a live test that requires the circuit to be energised and deliberately injects fault current through the earth path.
The test applies the rated residual operating current (IΔn) as an alternating current and verifies that the device operates within the required time. It is performed on both the positive and negative half-cycles of the supply waveform, because an RCD can behave differently depending on the polarity of the residual current when it appears.
A4:2026 introduced an important change to Regs 643.7.1 and 643.8: regardless of RCD type (AC, A, F, B etc.), an alternating current test at rated residual operating current (IΔn) is used to verify the effectiveness of the RCD. This means the 1x IΔn effectiveness test is always performed as an AC sinusoidal test, even for Type A, F, or B devices. Where your MFT has a type selector, select Type AC for the 1x IΔn effectiveness test; instruments without a type selector can only perform Type AC tests and this remains compliant for the effectiveness verification.
Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.
Every regulation change summarised
New model forms (EIC + MEIWC)
Free PDF — no subscription
02 · Testing Guide
The Full RCD Test Sequence
Amendment 4 made this shorter than most electricians expect. Table 3A of Appendix 3 — the time/current performance criteria table that drove the old half-rated, rated and five-times routine — has been deleted. Regulations 643.7.1 and 643.8 now verify an RCD with a single alternating current test at the rated residual operating current, IΔn, whatever the device type. Type AC, A, F and B are all verified the same way.
Required verification — 30 mA general-type RCD
Push-button test: Press the test button on the RCD — must trip mechanically. Reset. (A mechanical check, not a substitute for the instrument test.)
IΔn (30 mA) at 0 degrees: Must operate within 300 ms. Record time.
IΔn (30 mA) at 180 degrees: Must operate within 300 ms. Record time.
A Type S (time-delayed) device is verified with the same single AC test at IΔn, but should operate between 130 ms minimum and 500 ms maximum — the band stated in the NOTE to Regulation 643.7.1. The lower bound matters too, because a Type S that trips too quickly has lost the discrimination it exists to provide.
The worst-case (longest) trip time from the 0 degree and 180 degree tests is the value recorded on the schedule of test results. If the test gives 28 ms at 0 degrees and 34 ms at 180 degrees, you record 34 ms.
The half-rated and five-times tests have not become wrong — they have stopped being required. Both remain useful when you are investigating a specific problem, and the familiar 40 ms at five times IΔn is still a real figure from BS EN 61008/61009. It describes how the device must be built, though, not what BS 7671 asks you to measure. The practical consequence on site: record the trip time at IΔn as the certified value, and do not fail a device against a criterion the standard no longer applies.
03 · Testing Guide
The Test at IΔn — What BS 7671 Requires
The test applies the full rated residual operating current — 30 mA for a 30 mA device — as an alternating current, on both the positive and negative half-cycles. A general (non-delay) RCD must operate within 300 milliseconds. Since Amendment 4 this is the whole of the required verification, and it applies identically to Type AC, A, F and B devices.
The 300 ms figure is a limit, not a target. Most healthy RCDs operate far faster — typically 15 to 30 ms at IΔn. A device passing at 250 ms is compliant but worth a second look: trip times drift upward as a device ages, and a reading that high on a modern installation usually means something is wrong with the device rather than the circuit.
Both half-cycles matter because an RCD's sensitivity can differ with the polarity of the residual current at the instant it appears. A device can pass at 0 degrees and fail at 180. The worst-case (longest) trip time from either half-cycle is the one recorded on the certificate.
In the app
Auto-validated RCD trip times in the schedule of tests
Enter the trip time from your instrument and Elec-Mate validates it against the current BS 7671 requirement — 300 ms at IΔn for a general device, 130 to 500 ms for a Type S.
Free to use, no sign-up — enter the RCD rating and the trip time your instrument gave, and it tells you whether the device passes.
Use the worst-case (longest) of your 0 degree and 180 degree readings, and check it at IΔn — that is the value that goes on the certificate. The five-times option is kept for reference only, since Amendment 4 deleted Table 3A and that test is now a diagnostic rather than part of the required verification.
RCD Trip Time Chart Helper
Calculate RCD trip time requirements and verify BS 7671 compliance
ms
Enter the measured trip time for compliance verification
RCD Trip Time Requirements
Actual trip ≤ Maximum trip
1×IΔn= A4:2026 test — max 300ms for general RCDs (Reg 643.8)
Half-Rated, Five-Times and Ramp — Diagnostics, Not Verification
These three tests used to be part of the routine. Amendment 4 deleted Table 3A of Appendix 3, which is what required them, so they are no longer part of verifying an RCD. They have not become useless — they have become diagnostic tools you reach for when investigating something specific.
Half-rated (0.5x IΔn — 15 mA on a 30 mA device). The device should not trip. This is the test to run when chasing nuisance tripping, because it distinguishes an over-sensitive device from a circuit with genuine earth leakage. BS EN 61008/61009 requires an RCD to operate between 50% and 100% of IΔn, and BS 7671 makes the same point in NOTE 2 to Regulation 531.3.3 — an RCD may operate at any value of residual current in excess of 50% of the rated residual current — so a device tripping below 15 mA is out of specification. Bear in mind that existing leakage downstream — electronic equipment, long runs, damp — adds to the test current, so a trip here is not automatically the device's fault.
Five times (5x IΔn — 150 mA on a 30 mA device). The familiar 40 ms figure comes from BS EN 61008/61009 and describes how the device must be built. The reasoning behind it is sound and worth knowing: currents of that magnitude flowing through the body for more than roughly 40 ms risk inducing ventricular fibrillation, which is why a device intended for additional protection is built to clear a heavy residual current that quickly. What has changed is that BS 7671 no longer asks you to measure it. Run it when you want the extra evidence; record the IΔn result as the certified value.
Ramp test. Rather than applying a fixed current and timing the trip, a ramp test raises the current gradually from zero and reports the current at which the device actually operates — a 30 mA RCD might let go at 22 mA. It is the most informative of the three when a device is behaving oddly, and it has never been part of the required sequence.
06 · Testing Guide
Testing at 0 and 180 Degrees Phase Angle
The AC supply waveform is a continuous sine wave that oscillates between positive and negative peaks. When a fault occurs, it can happen at any point in this waveform. The magnitude of the fault current at the instant of the fault depends on where in the waveform cycle the fault occurs — at the peak (maximum voltage, maximum current) or at the zero crossing (zero voltage, zero current).
Testing at 0 degrees applies the test current as the waveform passes through zero going positive. Testing at 180 degrees applies it as the waveform passes through zero going negative. These represent the two worst-case starting conditions for the RCD — the points where the fault current starts from zero and must build up before the RCD can detect it.
Your multifunction tester has a setting to select 0 degree or 180 degree phase angle for RCD testing. Both tests must be performed at each current level, and the longer trip time is the one recorded. Some electricians abbreviate this by only testing on one half-cycle — this is not compliant with BS 7671 and could miss a device that fails on the other half-cycle.
07 · Testing Guide
The Ramp Test
The ramp test is a diagnostic test that gradually increases the leakage current until the RCD trips. Unlike the standard tests which apply a fixed current and measure time, the ramp test measures the actual trip current — the precise current level at which the device operates. GN3 describes the instrument behaviour: the ramp starts from less than 50% of the RCD's rating and rises to 110% of it, and the current at which the device trips is recorded as the tripping-current threshold.
BS EN 61008/61009 requires that a general-type RCD must trip between 50% and 100% of its rated residual operating current. For a 30 mA device, this means it must trip between 15 mA and 30 mA during a ramp test. A device that trips below 15 mA is overly sensitive and a nuisance tripping risk. A device that does not trip until above 30 mA is not providing adequate protection and must be replaced.
The ramp test is not always required on the schedule of test results, but it is a valuable diagnostic tool. If you are investigating nuisance tripping, the ramp test can confirm whether the RCD itself is overly sensitive or whether the issue is background leakage current on the circuit.
In the app
Record test results hands-free on site
AI board scanner, voice test entry, and automatic BS 7671 validation — finish the certificate before you leave the property. From £6.99/mo.
Every RCD has a test button on its front panel marked "T" or "Test." Pressing this button creates an artificial imbalance in the sensing toroid by passing a small current through an internal resistor, simulating a fault. The RCD should trip immediately.
The push-button test confirms three things: (1) the trip mechanism is free and operates correctly, (2) the contacts separate cleanly, and (3) the mechanical reset mechanism works. It does NOT confirm that the RCD will trip at the correct current level or within the required time — for that, you need the full instrument test sequence.
The push-button test should be performed first, before any instrument testing. If the button test fails (the RCD does not trip when the button is pressed), the device is faulty and must be replaced — there is no point proceeding with instrument tests. Occupants should be advised to press the test button six-monthly as a routine maintenance check between periodic inspections — this is the interval specified in the RCD instruction notice required by BS 7671 Reg 514.12.2. (A4:2026 added an exception to that regulation for domestic premises where certification or an EICR complete with the Appendix 6 guidance for recipients has been issued.) Note also that Regulation 643.10 requires the effectiveness of any test facility incorporated in an RCD to be verified, so the button check is itself a required part of initial verification — it is simply not the trip-time test.
09 · Testing Guide
Time-Delayed (Type S) RCD Testing
Time-delayed RCDs, designated Type S (selective), have an intentional time delay built into their operation. They are designed to achieve discrimination with downstream general-type RCDs — when a fault occurs, the downstream device should trip first, without the upstream Type S device also tripping.
Type S RCD Trip Time Limits
At IΔn — the required test: Should operate between 130 ms minimum and 500 ms maximum — the band stated in the NOTE to Regulation 643.7.1. The device must NOT operate faster than 130 ms — that minimum is the delay that makes discrimination possible.
At 5x IΔn — device characteristic: 50 ms to 200 ms under BS EN 61008/61009. This is the product standard describing the device, not a BS 7671 test — Amendment 4 deleted Table 3A of Appendix 3, so the five-times test is not part of the required verification for a Type S any more than it is for a general device.
Note the difference that catches people out: a Type S device has both a maximum and a minimum. Operating faster than 130 ms at IΔn is a failure, not a good result — the device is not providing the intended delay, and the downstream general-type RCD will no longer discriminate against it. Operating slower than 500 ms is also a failure. Both are recorded as such.
10 · Testing Guide
RCD Discrimination Testing
RCD discrimination ensures that when a fault occurs, only the RCD nearest to the fault trips — the upstream RCD remains closed, maintaining supply to other circuits. This is essential in modern consumer units where a main switch RCCB protects multiple circuits that also have individual RCBOs.
To achieve discrimination, the upstream device must be a Type S (time-delayed) RCD and the downstream device must be a general-type RCD. The time delay in the Type S device gives the downstream device time to operate first.
Testing Discrimination
Step 1: Perform the full test sequence on the downstream (general-type) RCD. During all tests, the upstream (Type S) RCD must NOT trip.
Step 2: If the upstream RCD trips during any downstream test, discrimination has failed. This means a fault on one circuit will disconnect all circuits protected by the upstream device.
Step 3: Record whether discrimination was achieved on the certificate. Failure of discrimination is typically classified as C3 (improvement recommended) unless the loss of supply poses a safety risk.
Discrimination between two general-type (non-time-delayed) RCDs cannot be guaranteed because both devices will attempt to trip at the same speed. One will trip first, but which one trips is essentially random and depends on the manufacturing tolerances of each device.
11 · Testing Guide
Recording RCD Test Results
RCD test results are recorded on the schedule of test results attached to the EICR or EIC. For each RCD, you must record the type (RCCB, RCBO, socket-outlet), the rated residual operating current (typically 30 mA), and the operating time measured at IΔn.
The worst-case (longest) trip time from the 0 degree and 180 degree half-cycle tests is the value recorded. If the test at IΔn gives 25 ms at 0 degrees and 32 ms at 180 degrees, you record 32 ms. Since Amendment 4 there is no second figure to enter alongside it — if you ran a five-times test as a diagnostic, that result is not the certified value.
In the app
Voice to test results — speak trip times hands-free
On site with your instrument in one hand? Just speak: 'RCBO 1, trip time 28 milliseconds.' Elec-Mate fills in the schedule of test results and validates it.
If the test fails, record the failure and classify the observation on what the device actually protects. An RCD that does not operate within 300 ms at IΔn on a circuit relying on it for additional protection is normally C2 (potentially dangerous). A device that proves over-sensitive on a diagnostic half-rated test may be C3 (improvement recommended) where it is merely causing nuisance tripping, or C2 where the nuisance is likely to lead occupants to bypass the device altogether.
12 · Testing Guide
Common RCD Testing Issues
Several common issues can affect RCD test results or cause confusion during testing.
Background earth leakage
Connected equipment (LED lighting, electronic controllers, IT equipment) can contribute background earth leakage current. This adds to the test current, which may cause the RCD to trip at the half-rated test or give faster-than-expected trip times. If you suspect background leakage, disconnect downstream equipment and retest.
Testing from the wrong circuit
When testing an RCBO, the test instrument must be connected to a circuit protected by that specific RCBO. Testing from a circuit on a different RCBO or one not protected by the device under test will not apply the test current through the correct sensing toroid and the device will not trip.
Worn RCD contacts
Over time, repeated tripping (including test button use and instrument testing) wears the RCD contacts. Worn contacts can increase the trip time, eventually causing the device to fail. RCDs have a limited mechanical life — typically 10,000 operations. Devices in high-use locations or those that experience frequent nuisance tripping may need more frequent replacement.
Not resetting between tests
The RCD must be reset (switched back on) between each test. If you attempt to test an already-tripped RCD, the test current has no effect because the circuit is already disconnected. Ensure the RCD is fully reset and the supply is restored before each subsequent test.
In the app
EICR and EIC forms capture all RCD test data
Elec-Mate's digital EICR and EIC forms have dedicated fields for RCD results — the operating time at IΔn on both half-cycles, device type and rating.
Step-by-step RCD testing per BS 7671:2018+A4:2026 — push-button check, then the required alternating current test at IΔn on both half-cycles.
1
Complete all preceding tests
RCD testing is test 7 in the GN3 sequence. Before testing RCDs, ensure continuity, insulation resistance, polarity, earth fault loop impedance, and prospective fault current tests have all been completed satisfactorily. The circuit must be energised and safe for live testing.
2
Press the RCD test button (mechanical check)
Press the test button on the front of the RCD. The device should trip immediately, disconnecting the supply. Reset the RCD. This confirms the mechanical trip mechanism works. If the test button does not trip the RCD, the device is faulty and must be replaced — do not proceed with instrument testing.
3
Test at IΔn on the positive half-cycle
This is the verification Regulations 643.7.1 and 643.8 require. Set the instrument to an alternating current test at the rated residual operating current (30 mA for a 30 mA device) and apply it on the positive half-cycle (0 degrees). Record the trip time. A general (non-delay) device must operate within 300 ms; a Type S between 130 and 500 ms. The same AC test at IΔn applies whatever the device type — AC, A, F or B.
4
Reset and repeat on the negative half-cycle
Reset the RCD and repeat the same test at IΔn on the negative half-cycle (180 degrees). An RCD can behave differently depending on the polarity of the residual current at the instant the fault occurs, so a device that passes on one half-cycle can fail on the other. The worst-case (longest) of the two readings is the value that must meet the limit.
5
Optional: diagnostic tests when investigating a problem
The half-rated and five-times tests are no longer part of the required verification — Amendment 4 deleted Table 3A of Appendix 3 — but they remain useful diagnostics. A half-rated test (15 mA for a 30 mA device, must not trip) helps confirm an over-sensitive device when chasing nuisance tripping, and a ramp test identifies the actual trip current. Run them when you are investigating something, not as a matter of routine.
6
Record the result on the schedule of test results
Record the worst-case trip time at IΔn, together with the RCD type and its rated residual operating current. Do not record a five-times figure as the certified trip time — the certified value is the one measured at IΔn. Elec-Mate validates trip times automatically against the current BS 7671 requirements.
Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.
Fantastic app for electricians
I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.
Absolutely amazing
I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.
Trusted by electricians across the UK
Real feedback from real sparks
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer
Sole Trader · DP Electrical
“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”
Nathan Perry
Electrician · NP Electrical Services
“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”
Jake Pizey
3rd Year Apprentice · Apprentice
7-day free trial
Validate RCD trip times automatically on site
Join 1,600+ UK electricians using Elec-Mate for on-site testing and certification. Auto-validated RCD trip times, voice test entry, EICR and EIC forms, 70+ calculators. 7-day free trial, cancel anytime.