TESTING GUIDE

RCD Testing Procedure: How to Test RCDs per BS 7671

The complete RCD testing procedure for UK electricians. Full test sequence at half-rated, 1x, and 5x rated current. Testing at 0 and 180 degree phase angle. Ramp test, button test, Type S time-delayed testing, and discrimination testing. BS 7671 compliant.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

22 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

How do you test an RCD to BS 7671?

Under BS 7671:2018+A4:2026, an RCD's effectiveness is verified by an alternating-current test at its rated residual operating current (IΔn) — a general (non-delay) type must disconnect within 300 ms (Reg 643.7.3), using test equipment to BS EN 61557-6 — and the integral test button is operated to confirm the test facility works. The familiar sequence of ½×, 1× and 5× tests at 0° and 180° is still used in practice, but A4 simplified the pass criterion to the single IΔn AC test.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1RCD testing involves multiple tests at different current levels: half-rated (must NOT trip), 1x rated (must trip within 300 ms), and 5x rated (must trip within 40 ms for general-type 30 mA RCDs).
  • 2All tests must be performed on both positive (0 degree) and negative (180 degree) half-cycles of the supply waveform — the worst-case (longest) trip time is the value recorded on the certificate.
  • 3Time-delayed (Type S) RCDs have different trip time requirements: 130 to 500 ms at 1x rated current and 50 to 200 ms at 5x rated current — they must NOT trip faster than the lower limit.
  • 4The push-button test confirms the mechanical trip mechanism works but does NOT verify the electrical trip function — instrument testing is mandatory for compliance. BS 7671 Regs 514.12.1/514.12.2 require a notice instructing occupants to test six-monthly by pressing the relevant test button(s).
  • 5Elec-Mate validates all RCD trip times automatically against BS 7671 requirements and supports voice-to-test-results for hands-free data entry on site.
01 · Testing Guide

What Is RCD Testing?

RCD (Residual Current Device) testing verifies that every RCD in an electrical installation — whether RCCB (Residual Current Circuit Breaker), RCBO (Residual Current Breaker with Overcurrent protection), or socket-outlet RCD — operates correctly at the specified current levels and within the required trip times. RCDs provide additional protection against electric shock by detecting small leakage currents to earth and disconnecting the supply before a lethal shock can occur.

RCD testing is test number seven in the GN3 testing sequence, performed after all dead tests and the other live tests (earth fault loop impedance and prospective fault current). It is a live test that requires the circuit to be energised and deliberately injects fault current through the earth path.

The test procedure involves applying specific multiples of the rated residual operating current (IΔn) and verifying that the device trips within the required time — or, in the case of the half-rated test, does NOT trip. The tests must be performed on both the positive and negative half-cycles of the supply waveform to verify correct operation under all conditions.

A4:2026 introduced an important change to Reg 643.3: regardless of RCD type (AC, A, F, B etc.), an alternating current test at rated residual operating current (IΔn) shall be used to verify the effectiveness of the RCD. This means the 1x IΔn effectiveness test is always performed as an AC sinusoidal test, even for Type A, F, or B devices. Where your MFT has a type selector, select Type AC for the 1x IΔn effectiveness test; instruments without a type selector can only perform Type AC tests and this remains compliant for the effectiveness verification.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Testing Guide

The Full RCD Test Sequence

For each RCD in the installation, the following tests must be performed in order. Each test must be carried out on both the positive (0 degree) and negative (180 degree) half-cycles.

RCD Test Sequence — 30 mA General-Type RCD

  • Push-button test: Press the test button on the RCD — must trip mechanically. Reset.
  • 0.5x IΔn (15 mA) at 0 degrees: Must NOT trip.
  • 0.5x IΔn (15 mA) at 180 degrees: Must NOT trip.
  • 1x IΔn (30 mA) at 0 degrees: Must trip within 300 ms. Record time.
  • 1x IΔn (30 mA) at 180 degrees: Must trip within 300 ms. Record time.
  • 5x IΔn (150 mA) at 0 degrees: Must trip within 40 ms. Record time.
  • 5x IΔn (150 mA) at 180 degrees: Must trip within 40 ms. Record time.

The worst-case (longest) trip time from the 0 degree and 180 degree tests at each current level is the value recorded on the schedule of test results. For example, if the 5x test gives 28 ms at 0 degrees and 34 ms at 180 degrees, you record 34 ms.

03 · Testing Guide

Half-Rated Current Test — Must NOT Trip

The half-rated current test (0.5x IΔn) is often overlooked but is an essential part of the RCD test sequence. For a 30 mA RCD, this means applying 15 mA of fault current. The RCD must NOT trip at this current on either half-cycle.

The purpose of this test is to verify that the RCD is not overly sensitive. BS EN 61008/61009 specifies that an RCD must trip between 50% and 100% of its rated residual operating current. A device that trips below 50% (below 15 mA for a 30 mA device) is excessively sensitive and presents a nuisance tripping risk. Nuisance tripping is not just an inconvenience — it can lead occupants to bypass or remove the RCD entirely, leaving circuits unprotected.

If the RCD trips at half-rated current, investigate the cause. There may be existing earth leakage on the downstream circuits (from electronic equipment, long cable runs, or damp conditions) that, combined with the test current, exceeds the trip threshold. Alternatively, the RCD itself may be faulty and should be replaced.

04 · Testing Guide

1x Rated Current Test

The rated current test (1x IΔn) applies the full rated residual operating current — 30 mA for a 30 mA RCD. The device must trip within 300 milliseconds on both the positive and negative half-cycles.

The 300 ms limit applies to general-type (non-time-delayed) RCDs. This is the maximum acceptable trip time at the rated current. In practice, most healthy RCDs trip significantly faster — typically between 15 ms and 30 ms at rated current. A trip time approaching 300 ms, while technically a pass, may indicate a device that is nearing the end of its useful life.

The test is performed on both half-cycles because the RCD's sensitivity may differ depending on the polarity of the fault current at the instant the test is applied. The worst-case (longest) trip time from either half-cycle is recorded on the certificate.

05 · Testing Guide

5x Rated Current Test

The five times rated current test (5x IΔn) is the most critical test for shock protection. For a 30 mA RCD, this applies 150 mA of fault current. The device must trip within 40 milliseconds for a general-type RCD.

The 40 ms limit is specifically designed to ensure protection against ventricular fibrillation — the most dangerous consequence of electric shock. Research has shown that currents above 30 mA flowing through the body for more than approximately 40 ms can induce fibrillation. The 5x test simulates a significant fault condition where a large leakage current is flowing to earth, and the rapid 40 ms disconnection prevents the shock duration from reaching dangerous levels.

If an RCD fails the 5x test (trips in more than 40 ms), it must be replaced. This is a C2 (potentially dangerous) observation on an EICR because the delayed disconnection could result in a lethal electric shock.

Auto-validated RCD trip times in the schedule of tests

Enter the trip times from your MFT and Elec-Mate instantly validates them against BS 7671 requirements — 300 ms at 1x, 40 ms at 5x for general-type…

Try it free for 7 days
Download on the App StoreGet it on Google Play
06 · Testing Guide

Testing at 0 and 180 Degrees Phase Angle

The AC supply waveform is a continuous sine wave that oscillates between positive and negative peaks. When a fault occurs, it can happen at any point in this waveform. The magnitude of the fault current at the instant of the fault depends on where in the waveform cycle the fault occurs — at the peak (maximum voltage, maximum current) or at the zero crossing (zero voltage, zero current).

Testing at 0 degrees applies the test current as the waveform passes through zero going positive. Testing at 180 degrees applies it as the waveform passes through zero going negative. These represent the two worst-case starting conditions for the RCD — the points where the fault current starts from zero and must build up before the RCD can detect it.

Your multifunction tester has a setting to select 0 degree or 180 degree phase angle for RCD testing. Both tests must be performed at each current level, and the longer trip time is the one recorded. Some electricians abbreviate this by only testing on one half-cycle — this is not compliant with BS 7671 and could miss a device that fails on the other half-cycle.

07 · Testing Guide

The Ramp Test

The ramp test is a diagnostic test that gradually increases the leakage current from zero until the RCD trips. Unlike the standard tests which apply a fixed current and measure time, the ramp test measures the actual trip current — the precise current level at which the device operates.

BS EN 61008/61009 requires that a general-type RCD must trip between 50% and 100% of its rated residual operating current. For a 30 mA device, this means it must trip between 15 mA and 30 mA during a ramp test. A device that trips below 15 mA is overly sensitive and a nuisance tripping risk. A device that does not trip until above 30 mA is not providing adequate protection and must be replaced.

The ramp test is not always required on the schedule of test results, but it is a valuable diagnostic tool. If you are investigating nuisance tripping, the ramp test can confirm whether the RCD itself is overly sensitive or whether the issue is background leakage current on the circuit.

Record test results hands-free on site

AI board scanner, voice test entry, and automatic BS 7671 validation — finish the certificate before you leave the property. From £6.99/mo.

Try the certificate tools free
Download on the App StoreGet it on Google Play
08 · Testing Guide

The Push-Button Test

Every RCD has a test button on its front panel marked "T" or "Test." Pressing this button creates an artificial imbalance in the sensing toroid by passing a small current through an internal resistor, simulating a fault. The RCD should trip immediately.

The push-button test confirms three things: (1) the trip mechanism is free and operates correctly, (2) the contacts separate cleanly, and (3) the mechanical reset mechanism works. It does NOT confirm that the RCD will trip at the correct current level or within the required time — for that, you need the full instrument test sequence.

The push-button test should be performed first, before any instrument testing. If the button test fails (the RCD does not trip when the button is pressed), the device is faulty and must be replaced — there is no point proceeding with instrument tests. Occupants should be advised to press the test button six-monthly as a routine maintenance check between periodic inspections — this is the interval specified in the mandatory RCD instruction notice required by BS 7671 Regs 514.12.1 and 514.12.2.

09 · Testing Guide

Time-Delayed (Type S) RCD Testing

Time-delayed RCDs, designated Type S (selective), have an intentional time delay built into their operation. They are designed to achieve discrimination with downstream general-type RCDs — when a fault occurs, the downstream device should trip first, without the upstream Type S device also tripping.

Type S RCD Trip Time Limits

  • At 1x IΔn (rated current): Must trip between 130 ms and 500 ms. The device must NOT trip faster than 130 ms — this is the minimum time that provides the delay for discrimination.
  • At 5x IΔn (five times rated): Must trip between 50 ms and 200 ms per BS EN 61008/61009 device-standard requirements. Again, the device must NOT trip faster than 50 ms. Note: BS 7671 Reg 643.7.3 specifies the 1x IΔn window (130–500 ms) for Type S — the 5x window is governed by the device product standard, not by BS 7671 directly.
  • At 0.5x IΔn (half-rated): Must NOT trip — same as general-type RCDs.

Note the critical difference: for a Type S device, there is both a maximum AND a minimum trip time. If the device trips faster than the minimum (for example, tripping at 1x in less than 130 ms), it is not providing the intended time delay and discrimination will fail. If it trips slower than the maximum (for example, tripping at 5x in more than 200 ms), it is not providing adequate protection. Both conditions are failures.

10 · Testing Guide

RCD Discrimination Testing

RCD discrimination ensures that when a fault occurs, only the RCD nearest to the fault trips — the upstream RCD remains closed, maintaining supply to other circuits. This is essential in modern consumer units where a main switch RCCB protects multiple circuits that also have individual RCBOs.

To achieve discrimination, the upstream device must be a Type S (time-delayed) RCD and the downstream device must be a general-type RCD. The time delay in the Type S device gives the downstream device time to operate first.

Testing Discrimination

  • Step 1: Perform the full test sequence on the downstream (general-type) RCD. During all tests, the upstream (Type S) RCD must NOT trip.
  • Step 2: If the upstream RCD trips during any downstream test, discrimination has failed. This means a fault on one circuit will disconnect all circuits protected by the upstream device.
  • Step 3: Record whether discrimination was achieved on the certificate. Failure of discrimination is typically classified as C3 (improvement recommended) unless the loss of supply poses a safety risk.

Discrimination between two general-type (non-time-delayed) RCDs cannot be guaranteed because both devices will attempt to trip at the same speed. One will trip first, but which one trips is essentially random and depends on the manufacturing tolerances of each device.

11 · Testing Guide

Recording RCD Test Results

RCD test results are recorded on the schedule of test results attached to the EICR or EIC. For each RCD, you must record the type (RCCB, RCBO, socket-outlet), the rated residual operating current (typically 30 mA), and the trip times at each test level.

The worst-case (longest) trip time from the 0 degree and 180 degree half-cycle tests is the value recorded. For example, if the 5x test gives 25 ms at 0 degrees and 32 ms at 180 degrees, you record 32 ms. For the half-rated test, record "Did not trip" or the appropriate pass indication.

Voice to test results — speak trip times hands-free

On site with your MFT in one hand? Just speak: 'RCBO 1, 5x trip time 28 milliseconds.' Elec-Mate fills in the schedule of test results and validates the…

Try it free for 7 days
Download on the App StoreGet it on Google Play

If any test fails, record the failure and classify the observation appropriately. An RCD that fails the 5x test (does not trip within 40 ms) is typically C2 (potentially dangerous). An RCD that trips at half-rated current may be C3 (improvement recommended) if it is causing nuisance tripping, or C2 if the overly sensitive operation is likely to cause occupants to bypass the device.

12 · Testing Guide

Common RCD Testing Issues

Several common issues can affect RCD test results or cause confusion during testing.

Background earth leakage

Connected equipment (LED lighting, electronic controllers, IT equipment) can contribute background earth leakage current. This adds to the test current, which may cause the RCD to trip at the half-rated test or give faster-than-expected trip times. If you suspect background leakage, disconnect downstream equipment and retest.

Testing from the wrong circuit

When testing an RCBO, the test instrument must be connected to a circuit protected by that specific RCBO. Testing from a circuit on a different RCBO or one not protected by the device under test will not apply the test current through the correct sensing toroid and the device will not trip.

Worn RCD contacts

Over time, repeated tripping (including test button use and instrument testing) wears the RCD contacts. Worn contacts can increase the trip time, eventually causing the device to fail. RCDs have a limited mechanical life — typically 10,000 operations. Devices in high-use locations or those that experience frequent nuisance tripping may need more frequent replacement.

Not resetting between tests

The RCD must be reset (switched back on) between each test. If you attempt to test an already-tripped RCD, the test current has no effect because the circuit is already disconnected. Ensure the RCD is fully reset and the supply is restored before each subsequent test.

EICR and EIC forms capture all RCD test data

Elec-Mate's digital EICR and EIC forms have dedicated fields for every RCD test — trip times at 1x and 5x on both half-cycles, half-rated pass/fail…

Try it free for 7 days
Download on the App StoreGet it on Google Play

How to Test an RCD — Step by Step

Step-by-step RCD testing procedure per BS 7671 and BS EN 61008/61009, from push-button test through to full instrument testing at multiple current levels.

1

Complete all preceding tests

RCD testing is test 7 in the GN3 sequence. Before testing RCDs, ensure continuity, insulation resistance, polarity, earth fault loop impedance, and prospective fault current tests have all been completed satisfactorily. The circuit must be energised and safe for live testing.

2

Press the RCD test button (mechanical check)

Press the test button on the front of the RCD. The device should trip immediately, disconnecting the supply. Reset the RCD. This confirms the mechanical trip mechanism works. If the test button does not trip the RCD, the device is faulty and must be replaced — do not proceed with instrument testing.

3

Test at half-rated current (must NOT trip)

Set your MFT to the 0.5x test mode. Apply the half-rated current (15 mA for a 30 mA RCD) on the positive half-cycle (0 degrees). The RCD must NOT trip. Repeat on the negative half-cycle (180 degrees). The RCD must NOT trip on either half-cycle. If the RCD trips at half-rated current, it is overly sensitive.

4

Test at rated current (must trip within 300 ms)

Set the MFT to 1x test mode. Apply the rated current (30 mA for a 30 mA RCD) on the positive half-cycle. Record the trip time — it must be within 300 ms for a general-type device. Reset the RCD and repeat on the negative half-cycle. Record the worst-case (longest) trip time.

5

Test at five times rated current (must trip within 40 ms)

Set the MFT to 5x test mode. Apply five times the rated current (150 mA for a 30 mA RCD) on the positive half-cycle. Record the trip time — it must be within 40 ms for a general-type device. Reset and repeat on the negative half-cycle. Record the worst-case trip time. This is the most critical test for shock protection.

6

Record all results on the schedule of test results

Record the worst-case trip times for each test on the schedule of test results. Note the RCD type, rated residual operating current, and whether the half-rated test was passed (device did NOT trip). Elec-Mate validates all trip times automatically against BS 7671 requirements.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Validate RCD trip times automatically on site

Join 1,000+ UK electricians using Elec-Mate for on-site testing and certification. Auto-validated RCD trip times, voice test entry, EICR and EIC forms, 70+ calculators. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy