RCD (Residual Current Device) testing verifies that every RCD in an electrical installation — whether RCCB (Residual Current Circuit Breaker), RCBO (Residual Current Breaker with Overcurrent protection), or socket-outlet RCD — operates correctly at the specified current levels and within the required trip times. RCDs provide additional protection against electric shock by detecting small leakage currents to earth and disconnecting the supply before a lethal shock can occur.
RCD testing is test number seven in the GN3 testing sequence, performed after all dead tests and the other live tests (earth fault loop impedance and prospective fault current). It is a live test that requires the circuit to be energised and deliberately injects fault current through the earth path.
The test procedure involves applying specific multiples of the rated residual operating current (IΔn) and verifying that the device trips within the required time — or, in the case of the half-rated test, does NOT trip. The tests must be performed on both the positive and negative half-cycles of the supply waveform to verify correct operation under all conditions.
A4:2026 introduced an important change to Reg 643.3: regardless of RCD type (AC, A, F, B etc.), an alternating current test at rated residual operating current (IΔn) shall be used to verify the effectiveness of the RCD. This means the 1x IΔn effectiveness test is always performed as an AC sinusoidal test, even for Type A, F, or B devices. Where your MFT has a type selector, select Type AC for the 1x IΔn effectiveness test; instruments without a type selector can only perform Type AC tests and this remains compliant for the effectiveness verification.