Cable Size for an Electric Shower (8.5 / 9.5 / 10.8 kW)
The most-asked UK domestic cable-sizing question after the EV charger. Short answer: 6 mm² twin-and-earth for most 8.5 kW units on short runs; 10 mm² for 9.5 kW and many 10.5/10.8 kW units. This guide walks the BS 7671 Section 701 + Appendix 4 process including RCD selection and the bathroom-zone implications.
For most UK domestic showers: 6 mm² twin-and-earth suits an 8.5 kW unit (≈37 A) on a short, well-ventilated run, while 9.5 kW (≈41 A) and 10.5–10.8 kW (≈46–47 A) units take 10 mm². Longer runs or cable in insulation can push you to 16 mm². Every shower also needs a 30 mA RCD (BS 7671 701.411.3.3) and a double-pole isolator outside the bathroom zones.
1,000+
UK electricians
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer — DP Electrical
Key Takeaways
1**8.5 kW shower (37 A)** — 6 mm² twin-and-earth typically suffices for short runs in good thermal conditions. Verify with BS 7671 Appendix 4 calculation.
2**9.5 kW shower (41 A)** — 10 mm² twin-and-earth is the standard UK practice; 6 mm² is borderline and typically fails voltage drop on longer runs.
3**10.5-10.8 kW shower (46-47 A)** — 10 mm² for short runs, possibly 16 mm² for longer runs depending on derating.
4Showers ARE in BS 7671 Section 701 (Locations Containing a Bath or Shower) — Regulation 701.411.3.3 requires 30 mA RCD protection on the shower circuit irrespective of cable size.
5A dedicated shower isolator (typically 45 A or 50 A double-pole) outside the bathroom zones is mandatory under Regulation 701.512.3 — switching arrangements within the location are restricted.
6The supply cable run from consumer unit to isolator and then to the shower terminal must satisfy current-carrying capacity (Iz), voltage drop (≤3% or 5% target), and disconnection time per Regulation 411.3.2 — all three checks always.
01 · Cable Sizing
The Short Answer
For a typical UK domestic electric shower installation, the cable size most often specified is:
**7.5 kW shower (~33 A) on short run** → 6 mm² twin-and-earth with 40 A MCB / RCBO.
**8.5 kW shower (~37 A) on short run** → 6 mm² twin-and-earth with 40 A protective device, voltage drop checked.
**9.5 kW shower (~41 A)** → 10 mm² twin-and-earth with 50 A protective device. 6 mm² typically too small.
**10.5-10.8 kW shower (~46-47 A)** → 10 mm² twin-and-earth with 50 A protective device on short runs; longer runs may need 16 mm².
**11 kW+ shower** → 10 mm² minimum, 16 mm² for longer runs or where grouping/temperature derating applies; verify with Appendix 4.
Always verify against the actual installation
These are starting points, not final answers. Every shower installation requires the full BS 7671 sizing calculation against the specific cable route, reference method, ambient temperature, grouping factor, and supply earthing arrangement. Use the calculator linked at the end of this guide or perform the calculation yourself.
Free download
Get the BS 7671 A4:2026 Cheat Sheet — free
Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.
Every regulation change summarised
New model forms (EIC + MEIWC)
Free PDF — no subscription
02 · Cable Sizing
Calculating Design Current
Design current (Ib) for an electric shower is the rated power divided by the nominal supply voltage. For UK domestic installations the nominal voltage is 230 V, so Ib (A) = rated power (W) ÷ 230.
**11.5 kW** → 11,500 ÷ 230 ≈ **50 A** → 50 A device → 10 mm² (16 mm² on long runs)
Electric showers operate at maximum power for the full duration of use — there is no diversity to apply, so Ib is the full nameplate current. The protective device is the next standard MCB / RCBO rating at or above Ib: typically 40 A for 7.5–8.5 kW, 45 A or 50 A for 9.5 kW, and 50 A for 10.5–11.5 kW. The cable column above is the usual UK starting point; every run must still pass the three checks in the next section against its own length, reference method and ambient temperature.
Confirm the voltage on site
Some supplies sit closer to 240 V, which lowers Ib slightly, while the worst case for voltage drop is the declared 230 V. Use the nameplate kW and 230 V for sizing — never assume the shower runs below its rating.
03 · Cable Sizing
The Three Cable Sizing Checks
Cable sizing for a shower (same as for any load) is a three-stage check. The cable size selected must satisfy all three:
**Current-carrying capacity (Iz)** — the cable must carry Ib continuously. Iz is read from BS 7671 Appendix 4 tables for the chosen cable type and reference method, adjusted by Ca (ambient temperature) and Cg (grouping).
**Voltage drop** — total voltage drop from origin to load must not exceed 3% for lighting or 5% for "other" circuits (Regulation 525). Designing to 3% is good practice for shower circuits.
**Disconnection time at calculated Zs** — under BS 7671:2018+A4:2026 the Table 41.1 maximum disconnection times (0.4 s for a 230 V TN circuit) apply to final circuits rated up to 63 A with socket-outlets, and up to 32 A supplying only fixed equipment (Regulation 411.3.2.2). A shower is fixed equipment above 32 A, so the 5 s TN limit of Regulation 411.3.2.3 applies — but the mandatory 30 mA RCD (Regulation 701.411.3.3) brings the actual disconnection time far below that anyway.
04 · Cable Sizing
Worked Example — 9.5 kW Shower, 12 m Run
A 9.5 kW shower installed in a first-floor bathroom, 12 m cable route from consumer unit (in the ground-floor under-stair cupboard) up to the shower isolator outside the bathroom and then through to the shower unit. TN-C-S (PME) supply.
**Design current** Ib = 9,500 / 230 = 41.3 A. Protective device: 45 A Type B MCB or 45 A 30 mA Type A RCBO.
**Cable selection trial** — 10 mm² twin-and-earth (6242Y), reference method 100 (clipped direct or laid in thermally insulating wall) — Iz from Appendix 4 = 64 A.
**Derating** — assume Ca = 1.0 (UK 30°C ambient), Cg = 1.0 (single circuit). Adjusted Iz = 64 A. Ib (41.3 A) < Iz (64 A) — passes.
**Voltage drop** — 10 mm² 6242Y voltage drop ≈ 4.4 mV/A/m. For 12 m at 41.3 A: 4.4 × 41.3 × 12 / 1000 = 2.18 V ≈ 0.95% of 230 V. Passes comfortably.
**Disconnection time** — verify Zs at the shower. On a 12 m run of 10 mm² with proper bonding, Zs at the shower is typically 0.3-0.5 Ω. Maximum permitted Zs for a 45 A Type B MCB at 5 s (Table 41.3): around 1.0 Ω with corrections. Passes — and the RCD provides additional protection bringing actual disconnection well within Section 701 requirements.
Try Elec-Mate free for 7 days
16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.
An electric shower is installed in a Section 701 location (a location containing a bath or shower), so the cable size is only half the job — the zone, RCD, IP-rating and bonding rules apply to the whole circuit. The headline requirements are below; the Section 701 bathrooms complete guide covers the zone geometry in full.
**Regulation 701.411.3.3** — additional protection by RCD with rated residual operating current not exceeding 30 mA shall be provided for all low voltage circuits in the location.
**Regulation 701.512.3** — switching, control and accessories in the location are restricted. The shower must have a dedicated isolator OUTSIDE the bathroom zones (typically a 45 A or 50 A double-pole switch in the airing cupboard, on the landing, or just outside the bathroom door). Zone accessory rules: Zone 0 — no switchgear or accessories whatsoever; Zone 1 — only switches of SELV circuits at <=12 V AC RMS or 30 V ripple-free DC (SELV source must be outside zones 0, 1 and 2); Zone 2 — no switches or socket-outlets except SELV (Section 414) and shaver supply units complying with BS EN 61558-2-5. Pull-cord insulating cords and switches incorporated in fixed current-using equipment suitable for the zone are exempt from these restrictions.
**Regulation 701.512.2** — electrical equipment in zones 1 and 2 must have minimum IP rating IPX4. The shower itself is normally rated to its installation position by the manufacturer.
**Cable concealment** — cable concealed in walls of the location at depth less than 50 mm must either be mechanically protected, run within Earthed metallic conduit / trunking, or be 30 mA RCD protected. The RCD requirement of 701.411.3.3 covers the shower circuit naturally.
**Regulation 411.3.4 (A4:2026) — bathroom lighting circuits** — in domestic premises, AC final circuits supplying luminaires must have additional 30 mA RCD protection (Regulation 411.3.4). When quoting for a new shower installation, check whether the consumer unit already provides RCBO or split-load RCD coverage for the bathroom lighting circuit. If lighting circuits are on an unprotected MCB, A4:2026 compliance requires an upgrade — this is a practical consequence that commonly affects shower installation quotes and should be identified at the initial survey stage.
**Supplementary bonding (Regulation 701.415.2)** — supplementary protective equipotential bonding is required in every room containing a bath or shower, connecting the protective conductor terminals of each circuit to accessible extraneous-conductive-parts (metallic water/waste pipes, central heating, accessible structural metalwork). Omission is only permitted when ALL three conditions are met: (d) all final circuits of the location comply with Regulation 411.3.2 automatic disconnection; (e) all final circuits have additional RCD protection per Regulation 415.1.1; and (f) all extraneous-conductive-parts are effectively connected to the main protective equipotential bonding per Regulation 411.3.1.2. Where any condition is not met, supplementary bonding is mandatory regardless of when the installation was carried out.
06 · Cable Sizing
Shower Isolator Selection
The shower isolator is the dedicated double-pole switch that disconnects both line and neutral from the shower unit. It sits between the consumer unit / RCBO and the shower itself. Selection:
**Current rating** — equal to or greater than the protective device rating. For a 45 A RCBO, use a 45 A or 50 A isolator. For a 50 A RCBO, use a 50 A or higher isolator. Standard UK fittings are 45 A and 50 A.
**Pole configuration** — double-pole (DP) — switches both line and neutral simultaneously. Single-pole isolators are not acceptable for a shower.
**Location** — outside the bathroom zones. Typical positions: airing cupboard, landing wall, hallway just outside the bathroom door.
**Pull-cord vs wall-switch** — both are acceptable. Pull-cord switches (BS 3676) are common above the bath where the user can reach them — note this is a different requirement from the BS 7671 Section 701 zone-3 restriction (no switching within the location).
**Mechanical interlock** — some installers prefer a locked-off / locked-on key isolator for maintenance scenarios. Not strictly required by BS 7671 but useful good practice.
07 · Cable Sizing
Common Shower Cable Sizing Mistakes
**Using 6 mm² for a 9.5 kW shower** — 6 mm² twin-and-earth has Iz around 47 A in the most favourable reference method. For a 41 A continuous load, this fails the voltage-drop check on most runs over 8-10 m. Default to 10 mm² for 9.5 kW unless the calculation explicitly justifies 6 mm².
**Not accounting for cable in roof insulation** — Reference Method 101 (cable in thermally insulating wall) gives lower Iz than the same cable clipped direct. Many real installations have part of the route in loft insulation — apply the correct reference method to the worst-case section.
**Forgetting the RCD** — Regulation 701.411.3.3 requires 30 mA RCD on every shower circuit. A 40 A Type B MCB with no RCD is non-compliant regardless of cable size.
**Omitting the dedicated isolator** — installing the shower directly from the consumer unit with no dedicated isolator outside the bathroom is non-compliant with Regulation 701.512.3.
**Mixing a 7.5 kW protective device with a 9.5 kW shower upgrade** — when upgrading the shower without upgrading the protective device, the old 40 A MCB may protect 6 mm² cable that is now overloaded by the 9.5 kW unit. Always re-check the whole circuit (cable, device and isolator) when changing the shower rating — the same discipline applies to the cooker circuit and the EV charger circuit.
Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.
Fantastic app for electricians
I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.
Absolutely amazing
I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.
Trusted by electricians across the UK
Real feedback from real sparks
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer
Sole Trader · DP Electrical
“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”
Nathan Perry
Electrician · NP Electrical Services
“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”
Jake Pizey
3rd Year Apprentice · Apprentice
7-Day Free Trial — Cancel Anytime, No Hassle
Size shower cables in seconds
Elec-Mate's Cable Sizing Calculator runs all three BS 7671 checks (Iz / voltage drop / Zs) and includes Section 701 zone reminders for bathroom installations. 7-day free trial.
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer, DP Electrical
From £6.99/mo after trial — less than a coffee a week
or download the app
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents
1,000+ electricians · From £6.99/mo after trial
We use cookies to improve the app and measure what works. Cookie Policy