REGULATION GUIDE

Section 701 Bathrooms: Complete BS 7671 Bathroom Zones Guide

Everything you need to know about bathroom electrical installations under BS 7671. Zone definitions, IP ratings, supplementary bonding under Regulation 701.415.2, RCD protection, SELV, switching, socket outlets, and electric shower circuits.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

18 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

What are the electrical zones in a bathroom (BS 7671 Section 701)?

BS 7671 Section 701 divides a room with a bath or shower into Zone 0 (inside the bath/basin), Zone 1 (above it to 2.25 m) and Zone 2 (0.6 m beyond Zone 1). Equipment must meet a minimum IP rating for its zone — IPX7 in Zone 0, IPX4 in Zones 1 and 2 (IPX5 where water jets are used) per Reg 701.512.2. All circuits serving the location need 30 mA RCD additional protection (Reg 701.411.3.3), and supplementary equipotential bonding (Reg 701.415.2) is required unless the conditions for omitting it are met. Socket-outlets are prohibited within 2.5 m horizontally of the Zone 1 boundary (shaver units to BS EN 61558-2-5 and SELV sockets excepted) per Reg 701.512.3.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Section 701 of BS 7671:2018+A4:2026 defines four zones in bathrooms (Zone 0, Zone 1, Zone 2, and outside zones) with specific equipment and IP rating requirements for each.
  • 2Supplementary bonding may be omitted under Regulation 701.415.2 only where all final circuits comply with automatic disconnection (411.3.2), all have 30mA RCD additional protection (415.1.1), and all extraneous-conductive-parts are connected to the protective equipotential bonding (411.3.1.2).
  • 3All low voltage circuits serving the location — and any passing through Zones 1 or 2 — must have 30mA RCD additional protection per Regulation 701.411.3.3, regardless of earthing system.
  • 4Only SELV at a nominal voltage not exceeding 12V AC rms or 30V ripple-free DC is permitted in Zone 0, with the safety source installed outside Zones 0, 1, and 2.
  • 5Equipment in Zone 1 must have a minimum rating of IPX4; equipment in Zone 0 must be rated at least IPX7.
01 · Regulation Guide

Section 701: Bathrooms and Special Locations

Section 701 of BS 7671:2018+A4:2026 covers the particular requirements for locations containing a bath or shower. It is one of the most frequently examined and most commonly encountered special locations in domestic electrical work.

The underlying principle is straightforward: a person in contact with water has significantly reduced body resistance, making them more vulnerable to electric shock. BS 7671 addresses this by defining zones of increasing risk around baths and showers, then restricting what equipment and wiring may be installed in each zone.

Section 701 applies to the electrical installation in locations containing a fixed bath or shower and to the surrounding zones. Per Regulation 701.1, it does not apply to emergency facilities such as emergency showers used in industrial areas or laboratories.

This guide covers zone definitions, IP rating requirements, supplementary bonding under Regulation 701.415.2, RCD protection, SELV, switching devices, socket outlets, and electric shower circuits.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Regulation Guide

Zone Definitions: Zone 0, Zone 1, Zone 2, and Outside Zones

BS 7671 defines the zones in a bathroom or shower room. The zones are measured from the bath, shower basin, or (for showers without a basin) the fixed water outlet. Zone dimensions are illustrated in Figures 701.1 (plan) and 701.2 (elevation) of BS 7671.

Zone Requirements at a Glance (Section 701)

ZoneMin. IP ratingPermitted supply
Zone 0IPX7SELV ≤ 12V AC / 30V DC
Zone 1IPX4 (IPX5 water jets)LV with 30mA RCD; SELV ≤ 25V AC / 60V DC
Zone 2IPX4 (IPX5 water jets)LV with 30mA RCD; shaver / SELV sockets
Outside zonesNone from S.701LV with 30mA RCD; sockets > 2.5m from Zone 1

IP minimums per Reg 701.512.2; 30mA RCD additional protection per Reg 701.411.3.3; Zone 0/switch SELV limits per Reg 701.512.3; Zone 1 SELV/PELV equipment limit per Reg 701.55.

Zone 0

The interior of the bath or shower tray. For showers without a tray, Zone 0 is the area of the floor up to 0.1m above the floor level, within the horizontal extent of Zone 1. Only SELV at a maximum of 12V AC rms or 30V ripple-free DC is permitted. The safety source must be outside Zones 0, 1, and 2. Equipment must be rated at least IPX7.

Zone 1

Above the bath or shower basin, bounded by the finished floor and the higher of 2.25m or the highest fixed shower head. Horizontally it extends to the plane circumscribing the basin, or 1.2m from the centre of the fixed water outlet for showers without a basin (in which case there is no Zone 2). Equipment must be at least IPX4 and only fixed, permanently connected current-using equipment suitable for the zone is permitted. SELV up to 25V AC rms or 60V ripple-free DC is allowed with the source outside Zones 0, 1, and 2.

Zone 2

Extends 0.6m horizontally beyond Zone 1, from the finished floor level up to 2.25m. Equipment must be rated at least IPX4. Fixed current-using equipment, luminaires, and shaver supply units (BS EN 61558-2-5) are permitted. Switches are only permitted if they form part of fixed current-using equipment suitable for the zone.

Outside Zones

Beyond the zones and above the Zone 1/2 height. Normal installation rules apply, subject to the requirement that all circuits serving the location have 30mA RCD additional protection. Socket outlets may be installed here provided they are more than 2.5m horizontally from the boundary of Zone 1. Switchgear, accessories, and general equipment are permitted.

The ceiling above a bath is classified as outside the zones provided it is above the Zone 1 height (the higher of 2.25m or the highest fixed shower head). A luminaire on a ceiling higher than that boundary is outside the zones — but the same fitting falls within Zone 1 or 2 if the ceiling is lower, and must then meet the IPX4 minimum. See our IP rating guide for decoding the IP code when selecting bathroom fittings.

03 · Regulation Guide

IP Rating Requirements per Zone

IP (Ingress Protection) ratings define the degree of protection equipment provides against solid objects and water. In bathroom zones, the minimum IP rating requirements are:

  • Zone 0 — IPX7 minimum: protection against temporary immersion in water (up to 1m depth for 30 minutes). Only SELV equipment rated IPX7 or higher may be installed.
  • Zone 1 — IPX4 minimum: protection against splashing water from any direction. Where water jets are used for cleaning purposes, IPX5 is required (protection against low-pressure water jets).
  • Zone 2 — IPX4 minimum: same as Zone 1. Again, IPX5 where water jets are used for cleaning. In most domestic bathrooms, IPX4 is sufficient.
  • Outside zones: no specific IP requirement from Section 701, though good practice dictates at least IPX1 in any room subject to steam and condensation.

The second digit of an IP code describes protection against water. The relevant codes for bathroom work decode as follows:

CodeWater protection (second digit)
IPX4Splashing water from any direction (Zones 1 and 2 minimum)
IPX5Low-pressure water jets from any direction (where jets used for cleaning)
IPX7Temporary immersion (Zone 0 minimum)

IP codes are defined in BS EN 60529; an “X” means the solid-object digit is not specified.

The IP rating must be maintained after installation — this means cable entries, mounting screws, and enclosure seals must all be intact. A luminaire rated IPX4 at the factory loses its rating if the installer drills an unsealed cable entry. The suitability of equipment for its location in terms of IP rating is itself an item inspectors verify under Regulation 701.512.2.

04 · Regulation Guide

Supplementary Bonding: Regulation 701.415.2

Supplementary equipotential bonding in bathrooms has been one of the most debated topics in the 18th Edition. Regulation 701.415.2 allows supplementary bonding to be omitted if specific conditions are met.

Conditions for Omitting Supplementary Bonding (701.415.2)

  • All final circuits of the location comply with the requirements for automatic disconnection of supply according to Regulation 411.3.2 (fault protection).
  • All final circuits of the location have additional protection by an RCD in accordance with Regulation 415.1.1 (rated residual operating current not exceeding 30mA).
  • All extraneous-conductive-parts of the location are effectively connected to the protective equipotential bonding according to Regulation 411.3.1.2 — meaning the main protective bonding is in place and compliant.

If supplementary bonding is required (because the above conditions are not met), it must connect together the terminals of the protective conductors of each circuit supplying the location and all extraneous-conductive-parts within the location. This includes metal pipework (hot, cold, gas, central heating), metal baths, metal waste pipes, structural steelwork, and any other metallic part that could introduce a potential.

The minimum cross-sectional area depends on what the conductor connects (Section 544). A supplementary bonding conductor between two extraneous-conductive-parts must be at least 2.5mm² where sheathed or mechanically protected, or 4mm² where not (Regulation 544.2.3). A conductor connecting an exposed-conductive-part to an extraneous-conductive-part must be at least half the cross-sectional area of the relevant circuit protective conductor, again subject to a 4mm² minimum where mechanical protection is absent (Regulation 544.2.2). Always verify the main bonding and earth fault loop impedance before deciding to omit supplementary bonding.

05 · Regulation Guide

RCD Protection Requirements

Regulation 701.411.3.3 requires that all circuits serving the bathroom location are protected by an RCD with a rated residual operating current (IΔn) not exceeding 30mA. This applies to every circuit type — lighting, power, shower, heated towel rail, underfloor heating, extractor fan, and any other circuit serving the bathroom.

  • Type AC, A, or F RCD? — for most bathroom circuits, a Type AC or Type A RCD is suitable. If the circuit supplies equipment with electronic controls that may produce DC residual currents (such as some modern shower units with electronic switching), a Type A RCD may be required. The general requirement for Type A is found in Regulation 531.3.3.
  • Shared circuits — if a lighting circuit serves both a bathroom and other rooms, the entire circuit must be 30mA RCD-protected. This is why many modern consumer units use RCBOs on bathroom lighting circuits, to avoid nuisance tripping affecting other rooms.
  • Additional protection — the 30mA RCD provides additional protection against direct contact and is not a substitute for basic protection (insulation) or fault protection (automatic disconnection within the required time).

In a modern dual-RCD or RCBO consumer unit, most circuits are already 30mA RCD-protected. On older installations with a main switch only, upgrading the consumer unit may be the most practical way to achieve compliance.

06 · Regulation Guide

SELV (Separated Extra-Low Voltage)

SELV (Separated Extra-Low Voltage) is a protective measure permitted in all bathroom zones and is the only electrical supply permitted in Zone 0. The requirements are:

  • Zone 0: SELV not exceeding 12V AC rms or 30V ripple-free DC. The safety source (transformer) must be installed outside Zones 0, 1, and 2.
  • Zone 1: SELV not exceeding 25V AC rms or 60V ripple-free DC. The safety source must be installed outside Zones 0, 1, and 2.
  • Zones 2 and outside: SELV up to 50V AC or 120V DC is permitted as per the general SELV requirements of Section 414.

SELV circuits must have protective separation from all other circuits, achieved through a safety isolating transformer conforming to BS EN 61558-2-6 or equivalent source of safety supply. Live parts of SELV circuits in Zones 0 and 1 must not be accessible — even at extra-low voltage.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
07 · Regulation Guide

Switching Devices and Accessories

Regulation 701.512.3 restricts the installation of switchgear and accessories in bathroom zones:

  • Zone 0: no switchgear or accessories may be installed. The only exceptions throughout Section 701 are switches and controls incorporated in fixed current-using equipment suitable for that zone, and insulating pull cords of cord-operated switches.
  • Zone 1: only switches of SELV circuits supplied at a nominal voltage not exceeding 12V AC rms or 30V ripple-free DC may be installed, with the safety source located outside Zones 0, 1 and 2 (Regulation 701.512.3). Switches that are an integral part of fixed equipment suitable for the zone remain permitted.
  • Zone 2: switchgear, accessories incorporating switches and socket-outlets must not be installed, with two exceptions in Regulation 701.512.3 — switches and socket-outlets of SELV circuits (safety source outside Zones 0, 1 and 2), and shaver supply units complying with BS EN 61558-2-5. Switches that are an integral part of fixed equipment suitable for the zone remain permitted.
  • Outside zones: all switchgear and accessories permitted (subject to normal rules). Pull-cord switches are commonly used at ceiling level, with the switch mechanism outside the zones and the insulating cord hanging into the room.

Ceiling-mounted pull-cord switches are the standard solution for bathroom lighting in domestic properties. The switch mechanism is at ceiling level (outside the zones) and the cord is an insulating medium.

08 · Regulation Guide

Socket Outlets in Bathrooms

Socket outlets are not permitted in Zones 0, 1, or 2. Regulation 701.512.3 further prohibits socket-outlets within a distance of 2.5m measured horizontally from the boundary of Zone 1. A socket-outlet may therefore only be installed beyond that 2.5m line, and must have 30mA RCD additional protection.

In most domestic bathrooms, this 2.5m clearance cannot be achieved, so socket outlets are not installed. The exceptions permitted in Zone 2 or outside the zones are:

  • Shaver supply units: units conforming to BS EN 61558-2-5 (incorporating an isolating transformer) may be installed in Zone 2 or outside the zones. These are not socket outlets — they provide galvanic isolation.
  • SELV socket outlets: socket outlets supplied by SELV may be installed in Zone 2 or outside the zones, provided the voltage does not exceed the limits for that zone.

Large hotel bathrooms and en-suites in large houses may have sufficient distance from Zone 1 to accommodate a socket outlet. Always measure carefully and document the measurement on the certificate.

09 · Regulation Guide

Electric Shower Circuits

Electric showers are one of the highest-demand fixed appliances in a domestic installation. At 230V, the design current is simply the rated power divided by the voltage, so a typical 8.5–11kW shower draws roughly 37–48A. The circuit must comply with both the general requirements of BS 7671 and the specific requirements of Section 701.

Indicative Shower Loads at 230V

RatingApprox. currentTypical device
8.5 kW~37 A40 A
9.5 kW~41 A45 A
10.5 kW~46 A50 A
11.0 kW~48 A50 A

Indicative only. The protective device and cable size must be calculated for the actual installation method, length and grouping, and verified against the manufacturer’s instructions and BS 7671 Appendix 4 current-carrying capacities.

  • Dedicated circuit: an electric shower must be on its own dedicated circuit from the consumer unit. Cable is commonly 10mm² for shorter runs and 16mm² where length, grouping or thermal insulation reduce the effective current-carrying capacity — always size it from the calculation rather than a rule of thumb. See our electric shower installation guide for worked sizing.
  • RCD protection: mandatory 30mA RCD protection per Regulation 701.411.3.3.
  • Local isolation: a 45A or 50A double-pole isolator switch should be installed outside the zones (or outside the bathroom), accessible to the user.
  • Cable routing: the cable within the bathroom should ideally be routed outside the zones or, if crossing zones, should be of sufficient IP rating or enclosed in trunking with appropriate IP rating.

Size shower cables accurately

Use Elec-Mate's cable sizing calculator to determine the correct cable size for electric shower circuits, accounting for installation method, grouping…

Try it free for 7 days
Download on the App StoreGet it on Google Play
10 · Regulation Guide

Testing and Certification

Bathroom installations require the same testing as any other circuit, plus particular attention to:

  • Continuity (Regulation 643.2) — confirm the continuity of any supplementary bonding conductors and protective conductors. Where supplementary bonding is relied upon, the resistance between simultaneously accessible exposed- and extraneous-conductive-parts must be low enough that the touch voltage stays within safe limits.
  • RCD operation (Regulation 643.8) — the 30mA RCDs providing additional protection on bathroom circuits must operate within the required times. Verification is by visual inspection and testing of effective automatic disconnection.
  • Insulation resistance (Regulation 643.3.2, Table 64) — a 500V DC test, minimum 1.0 MΩ for circuits up to 500V. Pay attention to moisture in bathroom environments; test when the room is dry.
  • Verification of IP ratings — inspect all equipment in zones to confirm the IP rating is appropriate and has not been compromised during installation.

An EIC or Minor Works Certificate must be issued. On EICRs, common observations include missing supplementary bonding (where required), incorrect IP ratings, socket outlets within zones, and absent or non-functional RCD protection.

11 · Regulation Guide

For Electricians: Bathroom Work Essentials

Bathroom electrical work is Part P notifiable (unless a like-for-like replacement of accessories on the same circuit). Every new circuit, new shower installation, or consumer unit change affecting bathroom circuits requires either self-certification through a competent person scheme or Building Control notification.

Common pitfalls on bathroom installations include:

IP Rating Compromised During Install

Drilling cable entries into IPX4 fittings without resealing. Using non-rated connectors inside zone-rated enclosures. Always use manufacturer-supplied grommets and seals.

Zone Miscalculation

Measuring zones from the wrong reference point. For a bath, Zone 1 is measured from the outer edge of the bath rim. For a shower without a tray, it is 1.2m from the fixed water outlet.

Complete bathroom certificates on site

Elec-Mate's digital certificates include bathroom-specific fields and zone diagrams. Complete your EIC or Minor Works on your phone immediately after…

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions About Section 701 Bathroom Regulations

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Certify Bathroom Installations on Your Phone

Join 1,000+ UK electricians using Elec-Mate for digital EIC and Minor Works certificates with bathroom zone diagrams and supplementary bonding records. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy