Earth Loop Impedance Too High? How to Find the Cause and Fix It
When Zs exceeds the BS 7671 maximum for the protective device, the circuit cannot be guaranteed to disconnect safely during an earth fault. This guide explains why Zs goes high, how to identify loose connections, long cable runs, and undersized CPCs, and what to do about it.
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer — DP Electrical
Key Takeaways
1Earth fault loop impedance (Zs) must be low enough that the protective device (MCB, fuse, or RCD) disconnects the supply within the maximum disconnection time specified by BS 7671 — 0.4 seconds for socket circuits and 5 seconds for fixed equipment circuits.
2The most common causes of high Zs readings are loose connections at terminals, long cable runs with undersized conductors, corroded earth connections, and high-impedance supply earthing arrangements.
3BS 7671 Table 41.3 and Table 41.4 list the maximum Zs values for each type and rating of protective device — these tables are essential reference for every electrician.
4If the Zs at the furthest point of a circuit exceeds the BS 7671 maximum for the protective device, the circuit must be treated as non-compliant — typically a C2 (Potentially Dangerous) observation on an EICR.
5Elec-Mate's Zs calculator looks up the maximum permitted earth loop impedance for any MCB, RCBO, or fuse type and rating, and compares your measured value against it instantly on site.
01 · Troubleshooting
What Is Earth Fault Loop Impedance?
Earth fault loop impedance (Zs) is the total impedance of the path that earth fault current takes when a live conductor comes into contact with an earthed part. This path starts at the transformer winding, runs through the phase conductor to the point of the fault, through the fault itself, through the CPC (circuit protective conductor) back to the distribution board, through the main earthing terminal, through the means of earthing (supply company earth or earth electrode), and back to the transformer.
The reason Zs matters is simple: when an earth fault occurs, the fault current must be large enough to operate the protective device (MCB, fuse, or RCD) within the maximum disconnection time specified by BS 7671. The lower the Zs, the higher the fault current, and the faster the protective device trips. If Zs is too high, the fault current is too low, and the protective device may not trip at all — leaving the fault energised and creating a risk of electric shock and fire.
Zs is made up of two components: Ze (the external earth fault loop impedance — everything from the transformer to the consumer unit) and R1+R2 (the impedance of the circuit phase conductor and CPC from the consumer unit to the point of measurement). The formula is Zs = Ze + R1+R2.
Free download
Get the BS 7671 A4:2026 Cheat Sheet — free
Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.
Every regulation change summarised
New model forms (EIC + MEIWC)
Free PDF — no subscription
02 · Troubleshooting
Maximum Zs Values per BS 7671
BS 7671:2018+A4:2026 sets maximum Zs values for each type and rating of protective device. These values ensure that in the event of an earth fault, the protective device will disconnect the supply within the required time — 0.4 seconds for circuits supplying socket outlets and portable equipment, and 5 seconds for circuits supplying fixed equipment.
Type B MCB (most domestic circuits): Maximum Zs ranges from 13.68 ohms (6 A) down to 0.86 ohms (50 A). Common values: 6 A = 7.28 ohms, 10 A = 4.37 ohms, 16 A = 2.73 ohms, 20 A = 2.19 ohms, 32 A = 1.37 ohms, 40 A = 1.09 ohms (all at 0.4s disconnection).
Type C MCB (inductive loads): Maximum Zs values are lower because Type C MCBs require higher fault currents to trip magnetically. 6 A = 3.64 ohms, 10 A = 2.19 ohms, 16 A = 1.37 ohms, 32 A = 0.68 ohms (at 0.4s disconnection).
30 mA RCD (additional protection): Maximum Zs of 1667 ohms. This very high limit means that RCD protection effectively resolves most Zs compliance issues for earth fault protection — but overcurrent protection via the MCB must still be adequate.
When comparing your measured Zs against the tabulated maximum, apply the 80% rule. The BS 7671 tabulated values assume conductors at their maximum operating temperature. When you test a circuit that is not carrying load (cold), the conductor resistance is lower. To account for this, multiply the tabulated Zs by 0.8 — your measured (cold) value must be below this reduced figure. For example, the 32 A Type B maximum of 1.37 ohms becomes 1.10 ohms for comparison with cold test results.
Zs calculator — instant lookup on site
Select the protective device type and rating, and Elec-Mate's Zs calculator shows the BS 7671 maximum earth loop impedance.
When your Zs reading exceeds the BS 7671 maximum for the protective device, the fault lies somewhere in the earth fault loop. The cause could be in the external supply (high Ze), in the circuit wiring (high R1+R2), or both. Here are the most common causes, starting with the most frequently encountered.
Loose or Corroded Connections
Every connection in the earth fault loop adds resistance. A loose terminal, a corroded earth clamp, a poorly made joint, or an oxidised connection at the main earthing terminal can add enough impedance to push Zs above the maximum. This is the single most common cause of unexpectedly high Zs readings — and the simplest to fix.
Long Cable Runs
The longer the cable run, the higher the R1+R2 component of Zs. A circuit running 30 metres in 2.5 mm squared twin and earth will add approximately 0.67 ohms to the Zs. On a 32 A Type B MCB (maximum Zs 1.37 ohms at operating temperature, 1.10 ohms cold), that 0.67 ohms consumes more than half the available budget. Add a Ze of 0.50 ohms and you are already at 1.17 ohms — over the cold limit.
Undersized CPC
In twin and earth cable, the CPC is one size smaller than the line and neutral conductors. The CPC in 2.5 mm squared cable is 1.5 mm squared; the CPC in 1.5 mm squared cable is 1.0 mm squared. The CPC often contributes more resistance per metre than the line conductor. On long runs, this smaller CPC is the limiting factor for Zs compliance.
High External Earth Fault Loop Impedance (Ze)
The Ze is determined by the supply company infrastructure and the earthing arrangement. TT installations have inherently high Ze because the earth path includes the consumer earth electrode and the general mass of earth. Even TN-C-S supplies can have elevated Ze if the PEN conductor is long or undersized. If the Ze is high, there is less room for R1+R2 before Zs exceeds the limit.
Poor Main Earthing Arrangement
A corroded main earth clamp on the water pipe, a broken or missing main bonding conductor, a loose connection at the main earthing terminal, or an earth electrode in dry or sandy soil can all add significant impedance to the earth fault loop. Always check the main earthing arrangement when you find high Zs readings across multiple circuits.
04 · Troubleshooting
Loose Connections: The Most Common Culprit
In the majority of cases where Zs readings are marginally above the BS 7671 maximum, the cause is one or more loose or high-resistance connections in the earth fault loop. Every terminal, joint, and clamp in the path adds a small amount of resistance. When several connections are slightly loose or corroded, the cumulative effect can be enough to push Zs over the limit.
Main earthing terminal: Check that the main earth conductor is securely connected and the terminal is clean and tight. Corrosion at this point affects every circuit in the installation.
Distribution board earth bar: Check every CPC connection on the earth bar. Loose earth connections at the board are extremely common, especially in older installations where the earth bar screws have worked loose over time.
Socket and accessory terminals: Every socket, switch, and junction box on the circuit has earth terminals. A single loose earth connection in a socket on a radial circuit breaks the earth continuity to every point downstream.
Supply earth connection: On TN-S installations, check the earth clamp on the cable sheath. On TN-C-S installations, check the supply company earth terminal. Corrosion or looseness at these points elevates Ze for the entire installation.
The fix is straightforward: re-make the connection. Clean the terminal, strip back to bright copper if the conductor is tarnished, tighten to the manufacturer's recommended torque, and retest. A single re-tightened connection can reduce Zs by 0.1 to 0.5 ohms — often enough to bring a marginal circuit back into compliance.
05 · Troubleshooting
Long Cable Runs: When Distance Is the Problem
Conductor resistance is proportional to length. On long cable runs — common in large houses, converted barns, commercial units, and circuits feeding outbuildings — the R1+R2 component of Zs can be too high for the protective device, even with perfect connections and a healthy supply earth.
Consider a radial socket circuit using 2.5 mm squared twin and earth cable running 25 metres from the distribution board to the furthest socket. The R1+R2 for 2.5/1.5 mm squared cable is approximately 22.4 milliohms per metre (at 20 degrees Celsius), giving a total R1+R2 of 0.56 ohms. With a Ze of 0.35 ohms (typical for a TN-C-S supply), the Zs at the furthest point is 0.91 ohms — which passes for a 32 A Type B MCB. But extend that run to 40 metres and the R1+R2 becomes 0.90 ohms, giving a Zs of 1.25 ohms — which exceeds the 1.10 ohm cold limit.
Solutions for long cable runs include:
Increase the cable size: Using 4.0 mm squared instead of 2.5 mm squared reduces R1+R2 and brings Zs back within limits. This is the most common design solution for long runs.
Add a separate CPC: Running a separate, larger CPC alongside the twin and earth cable reduces R2. For example, a 4.0 mm squared separate CPC in parallel with the 1.5 mm squared CPC in the cable significantly lowers the R2 component.
Use a lower-rated MCB: A 20 A Type B MCB has a maximum Zs of 2.19 ohms instead of 1.37 ohms for a 32 A. If the circuit loading permits, reducing the MCB rating extends the allowable cable length significantly.
Relocate the distribution board: In some cases (new builds, extensions), positioning a sub-distribution board closer to the load reduces cable lengths and therefore R1+R2 for individual circuits.
Try Elec-Mate free for 7 days
16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.
The circuit protective conductor (CPC) — the earth wire — is often the weakest link in the earth fault loop. In standard twin and earth cable, the CPC is one size smaller than the line and neutral conductors. This smaller cross-section means higher resistance per metre, and R2 often contributes more to Zs than R1.
For 2.5 mm squared twin and earth cable, the CPC is 1.5 mm squared. The R1+R2 per metre is made up of approximately 7.41 milliohms (R1, the 2.5 mm squared line conductor) plus approximately 12.10 milliohms (R2, the 1.5 mm squared CPC) — the CPC contributes 63% of the total circuit impedance. If you used a 2.5 mm squared CPC instead, the R1+R2 would drop from 19.51 to 14.82 milliohms per metre — a 24% reduction.
On circuits where high Zs is caused by the CPC size, the solution is to install a supplementary CPC of adequate size alongside the existing cable. This additional earth conductor runs in parallel with the existing CPC, reducing the combined R2 and therefore the overall Zs. The supplementary CPC must be correctly connected at both ends (at the distribution board earth bar and at the accessory earth terminal) and must be adequately sized per BS 7671 Table 54.7.
07 · Troubleshooting
How to Fix High Earth Loop Impedance
The approach to fixing high Zs depends on which component of the earth fault loop is causing the problem. Start by measuring Ze at the origin of the installation and R1+R2 for the circuit. This tells you whether the issue is in the external supply, the circuit wiring, or both.
Measure Ze at the consumer unit. If Ze is higher than the supply company declared value, check the main earth connection. For TN-S, check the sheath clamp. For TN-C-S, check the supply company earth terminal. Clean and re-tighten if necessary.
Measure R1+R2 for the faulty circuit. Use the continuity of ring final circuit test (for rings) or end-to-end continuity test (for radials) to determine R1+R2. Compare with the calculated value based on cable size and length. If measured R1+R2 is significantly higher than calculated, there is a high-resistance connection in the circuit.
Check all connections. Inspect and re-tighten every terminal on the circuit — at the board, at each accessory, and at any junction boxes. A single loose earth connection can add 0.2 to 0.5 ohms.
If connections are sound and R1+R2 is inherently high (long cable run, small CPC), consider upgrading the cable, adding a supplementary CPC, or reducing the MCB rating if the load permits.
If Ze is inherently high (TT installation, long service cable), ensure all circuits are RCD-protected and verify Zs is within the RCD operating limits. Consider improving the earth electrode arrangement.
After completing any remedial work, retest Zs at the furthest point of the circuit and record the new reading on the schedule of test results. Issue the appropriate certificate for the remedial work — an Electrical Installation Certificate or Minor Works Certificate depending on the scope of work.
Record Zs readings by voice — hands-free on site
With Elec-Mate's voice test entry, speak your earth loop impedance readings and the app fills in the schedule of test results.
Supplementary equipotential bonding is sometimes proposed as a solution to high Zs, but it is important to understand what it does and does not achieve. Supplementary bonding connects exposed-conductive-parts (metal pipework, metallic baths, radiators) to the circuit protective conductor, reducing the touch voltage in the event of an earth fault. It does not reduce Zs or increase fault current — it protects by ensuring that all metalwork in the area rises to the same potential during a fault.
Under BS 7671 Regulation 415.2, supplementary bonding can be used as an additional protective measure in locations of increased risk (such as bathrooms). However, it is not a substitute for adequate Zs. The circuit must still meet the disconnection time requirements, or alternative measures (such as RCD protection) must be provided.
In practice, if Zs is too high for the MCB to disconnect within the required time, the recommended approach is:
First, fix the root cause — tighten connections, upgrade cable, or improve the earthing arrangement.
If the root cause cannot be fully resolved, ensure the circuit is protected by a 30 mA RCD or RCBO, which will provide earth fault disconnection at much lower fault currents.
Apply supplementary bonding in locations of increased risk as an additional measure — never as the sole protective measure.
Record all supplementary bonding on the EICR or EIC and note the reason for its installation. Elec-Mate's AI fault diagnosis tool can recommend the appropriate protective measures based on your measured Zs, the protective device type, and the installation characteristics.
Frequently Asked Questions About High Earth Loop Impedance
Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.
Fantastic app for electricians
I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.
Absolutely amazing
I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.
Trusted by electricians across the UK
Real feedback from real sparks
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer
Sole Trader · DP Electrical
“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”
Nathan Perry
Electrician · NP Electrical Services
“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”
Jake Pizey
3rd Year Apprentice · Apprentice
7-Day Free Trial — Cancel Anytime, No Hassle
Check Zs Limits Instantly on Site
Zs calculator, voice test entry, AI fault diagnosis, and digital EICR certificates. Join 1,000+ UK electricians using Elec-Mate. 7-day free trial, cancel anytime.
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer, DP Electrical
From £6.99/mo after trial — less than a coffee a week
or download the app
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents
1,000+ electricians · From £6.99/mo after trial
We use cookies to improve the app and measure what works. Cookie Policy