EICR OBSERVATION CODE

EICR Code C3 — Improvement Recommended

C3 means the installation departs from current BS 7671 — but neither danger nor potential danger is present. Unlike C1 and C2, a C3 does NOT make the EICR "unsatisfactory". This guide explains the exact decision boundary, the most common C3 observations on UK reports, and how to write a C3 that the responsible person will actually act on.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

9 min readUpdated 2026-05-18Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1C3 means "Improvement recommended." The installation departs from current BS 7671 but does not create danger or potential danger — neither C1 nor C2 applies.
  • 2C3 observations do NOT make the overall EICR assessment "unsatisfactory". A report with only C3 observations remains "satisfactory" overall.
  • 3C3 shall NOT be used where C1 or C2 evidence exists — the inspector cannot downgrade for convenience or commercial reasons.
  • 4Common C3 territory: pre-A4 wiring that pre-dates current requirements but was compliant when installed; "old colours" cables; non-A4 model form artefacts; older but functional consumer units.
  • 5A well-written C3 still recommends specific improvement work — vague "could be improved" notes have no remedial value and undermine the report.
  • 6C3 observations don't trigger the 28-day PRS Regs remedial window in rented properties — but a landlord may still choose to address them at the next maintenance opportunity.
01 · EICR Observation Code

What C3 Means

C3 is defined as "Improvement recommended." The classification applies where an observed condition departs from the current edition of BS 7671 in a way that an improvement would address, but the departure does not create danger or potential danger.

C3 keeps the EICR "satisfactory"

Unlike C1 and C2, a C3 observation does not change the overall report assessment. An EICR with only C3 observations is recorded as "satisfactory" — the responsible person is informed of potential improvements but no urgent action is required.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · EICR Observation Code

The C3 Decision Rule (Strict)

BS 7671 / GN3 are unusually explicit about when C3 can be used. The rule reads as an acceptance criterion:

Cannot use C3 if evidence supports C1 or C2

C3 ("Improvement recommended") shall be attributed only where C1 ("Danger present") or C2 (potentially dangerous / non-compliant) do not apply. Practitioners shall not use C3 if evidence supports C1 or C2 classifications.

This is to stop commercial pressure (or politeness) from softening serious findings into reassuring "improvement" recommendations. Every inspector encounters the temptation: "the report looks better with no C2s." The acceptance criterion makes that downgrade professional misconduct.

03 · EICR Observation Code

Genuine C3 Observations

Conditions where C3 is the correct classification — improvement is genuinely recommended but no danger, present or potential, exists:

  • Wiring installed under a previous edition of BS 7671 that remains safe, but uses now-superseded methods (e.g. older colour codes in industrial wiring where a clear ID label is present and circuits are functional).
  • A consumer unit with spare ways but no AFDD where AFDDs are recommended (not required) under A4:2026.
  • A pre-A4 EICR-compliant installation that does not yet meet the A4:2026 schedule of test results columns — the existing test results remain valid, but the new format would be an improvement at the next inspection cycle.
  • Use of older but compliant Type AC RCDs in installations where Type A is now generally preferred (outside medical locations where Type AC is explicitly prohibited).
  • A circuit identification chart not in the latest A4:2026 model form layout, but accurate and legible.
  • Cable management arrangements that meet older standards (BS EN 50085-2-1) but not the latest IET Code of Practice recommendations on fire-rated sealing.

Record test results hands-free on site

AI board scanner, voice test entry, and automatic BS 7671 validation — finish the certificate before you leave the property. From £6.99/mo.

Try the certificate tools free
Download on the App StoreGet it on Google Play
04 · EICR Observation Code

NOT C3 — These Are C2

These observations are sometimes mis-classified as C3 but should be C2 because the condition is potentially dangerous, not merely a "departure from current standards":

  • Missing main protective bonding to extraneous-conductive-parts — C2 (potentially dangerous under fault conditions), not C3.
  • Plastic consumer unit in HMO escape route — C2 (combustibility / Regulation 421.1.201 with HMO context), not C3.
  • Missing RCD on a socket-outlet circuit intended for general use — C2 (potential shock risk per Regulation 411.3.3), not C3.
  • Damaged but contained cable sheath — C2 (degraded protection, foreseeable progression to exposed conductors), not C3.
  • Borrowed neutral across separate final circuits — C2 (potential for unexpected energisation during isolation), not C3.

The downgrade temptation

If you find yourself reaching for C3 to "keep the report satisfactory," the chances are high that the evidence supports C2. Re-read the acceptance criterion: C3 shall not be used where evidence supports C1 or C2.

05 · EICR Observation Code

How to Write a C3 That Gets Acted On

C3 observations don't trigger the legal remedial timeline that C1/C2 trigger — so the responsible person can choose to ignore them. A well-written C3 helps them make an informed decision rather than dismissing the recommendation:

  • State the specific BS 7671:2018+A4:2026 regulation the installation departs from.
  • Describe the practical benefit of the improvement (e.g., "fitting a Type A RCD would extend protection against DC fault current components from modern electronic loads").
  • Note the typical timeline for addressing the improvement (e.g., "at the next scheduled maintenance opportunity, or sooner if the consumer unit is replaced for any other reason").
  • Avoid vague language like "this could be improved" — name the specific improvement.
  • Where the C3 relates to a pre-A4 installation, note that the previous edition was complied with at the time of installation — this avoids implying the original installer was non-compliant.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Write better C3 observations

Elec-Mate's digital EICR app auto-suggests the correct regulation cite for each C3 observation and lets you save reusable wording. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy