TESTING GUIDE

Electrical Inspection Checklist: What to Check

A thorough visual inspection is the foundation of every EICR and EIC. This checklist covers every area you need to check: consumer unit, earthing and bonding, labelling, cable condition, accessories, and special locations. Use it with Elec-Mate's digital inspection tool to ensure nothing is missed.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

11 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Visual inspection is the first stage of any electrical inspection and must be carried out before any testing takes place -- it identifies defects that could make testing dangerous or give misleading results.
  • 2The consumer unit is the single most important item to inspect thoroughly: condition of enclosure, correct protective devices, labelling, adequate cable connections, signs of overheating, and compliance with current standards.
  • 3Earthing and bonding defects are the most safety-critical findings -- missing or inadequate main bonding, deteriorated earth connections, and incorrect earthing arrangements can result in C1 (Danger Present) classifications.
  • 4Every circuit and protective device must be correctly labelled and identified -- this is a regulatory requirement under BS 7671 and a common C3 observation on older installations.
  • 5BS 7671:2018+A4:2026 (Regulation 411.3.4) now requires 30mA RCD additional protection for all AC lighting circuits in domestic premises -- check that lighting circuits are RCD-protected when inspecting domestic consumer units.
  • 6BS 7671:2018+A4:2026 (Regulation 421.1.7) recommends the installation of arc fault detection devices (AFDDs) on AC final circuits to mitigate the risk of fire from arc faults -- absence of AFDDs on new or rewired domestic circuits is worth noting as a recommendation.
  • 7Elec-Mate provides a structured digital inspection checklist that ensures nothing is missed, with AI-assisted observation code classification and automatic schedule of inspections generation.
01 · Testing Guide

Why Inspection Matters

Visual inspection is the foundation of every electrical assessment, whether you are carrying out an EICR on an existing installation or certifying new work with an EIC. It is not a formality or a tick-box exercise -- it is the stage where many of the most significant safety defects are identified.

BS 7671 Section 621 requires that initial verification of every new installation begins with a careful visual inspection. Chapter 65 (Section 651) requires the same for periodic inspection and testing. The visual inspection must be carried out before any instruments are connected, for two critical reasons: first, testing a circuit with a visible defect (damaged insulation, loose connections, exposed conductors) can cause a fault or injury; second, test results from a circuit with a visual defect may be misleading and give false confidence about the safety of the installation.

A thorough visual inspection requires knowledge, experience, and systematic attention to detail. You need to know what to look for, what the current standards require, and how to classify your findings correctly using the observation code system. This guide provides a comprehensive checklist covering every area of a domestic and commercial electrical inspection.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Testing Guide

Visual Inspection Items

The visual inspection covers every visible part of the fixed electrical installation. Work through the installation systematically, starting at the origin (intake position and main switch) and working outwards to the final circuits and endpoints. Here are the key items to check:

  • Intake position and meter -- condition of the service head and meter tails, adequacy of the main earthing terminal, condition of the meter enclosure, and accessibility of the main switch for emergency isolation.
  • Presence of safety devices -- confirm that RCDs, MCBs, RCBOs, AFDDs, and SPDs are present where required by the current edition of BS 7671. Check that device ratings are appropriate for the circuits they protect.
  • Cables and conductors -- look for visible damage, deterioration, discolouration (signs of overheating), incorrect support intervals, inadequate mechanical protection, and cables installed in thermal insulation without appropriate derating.
  • Accessories and equipment -- check every socket outlet, switch, junction box, and item of fixed equipment for damage, signs of overheating, secure fixings, and correct polarity (where visible).
  • Fire stopping -- where cables pass through fire-resistant walls, floors, and ceilings, the penetrations must be sealed with appropriate fire stopping material. Missing fire stopping is a common finding, particularly in converted properties.

Document every observation as you go. Do not rely on memory -- by the time you have inspected 30 circuits across a large property, you will not remember the details of the first five. Use a structured checklist or digital inspection tool that captures each finding in real time.

03 · Testing Guide

Consumer Unit Inspection

The consumer unit (or distribution board) is the single most important item to inspect during any electrical assessment. It houses the protective devices for every circuit, it is the point where earthing and bonding are connected, and its condition directly affects the safety of the entire installation.

  • Enclosure condition -- check for damage, signs of overheating (discolouration, melted plastic), water ingress, and adequate IP rating for the location. From January 2016, consumer units installed in domestic premises must be constructed of non-combustible material (typically metal).
  • Protective devices -- confirm correct type (MCB, RCBO, RCD, AFDD), correct rating for the circuit, correct type characteristic (B, C, or D for MCBs), and that devices are from a reputable manufacturer and properly type-tested.
  • Cable connections -- where safe to do so (with the installation isolated), check for loose connections, signs of overheating at terminals, incorrect cable stripping lengths, and adequate conductor insulation within the enclosure.
  • Spare ways and blanking plates -- all unused ways must be fitted with blanking plates to maintain the IP rating of the enclosure. Missing blanking plates expose live busbars and are a safety hazard.
  • Circuit chart and labelling -- a circuit chart must be displayed inside or adjacent to the consumer unit, clearly identifying every circuit and its associated protective device. Check that the chart is accurate and legible.

When inspecting a consumer unit, also note its age and type. Older rewirable fuse boards, early MCB boards without RCD protection, and plastic consumer units in domestic premises are all common observations that may require recommendations for upgrade.

Two A4:2026 requirements are particularly relevant at the consumer unit. First, Regulation 411.3.4 now mandates 30mA RCD additional protection for AC final circuits supplying luminaires in domestic premises -- check that lighting circuits are RCD-protected, not just socket circuits. Second, Regulation 421.1.7 recommends the installation of arc fault detection devices (AFDDs) on AC final circuits to mitigate the risk of fire from arc fault currents. Absence of AFDDs on a new or recently rewired domestic installation is worth recording as a recommendation, though the regulation uses advisory rather than mandatory language.

04 · Testing Guide

Earthing and Bonding Inspection

Earthing and bonding are the primary means of protection against electric shock from indirect contact (touching a conductive part that has become live due to a fault). Defects in the earthing and bonding system are the most safety-critical findings an inspector can make.

  • Main earthing terminal -- verify that the main earthing terminal is present, in good condition, and correctly connected to the means of earthing (supply cable sheath for TN-C-S, earth electrode for TT systems). Check that the earthing conductor is the correct size (minimum 16mm2 copper for TN systems, 25mm2 for buried electrode connections).
  • Main protective bonding -- bonding conductors must connect all extraneous-conductive-parts to the main earthing terminal. This includes incoming metal water pipe, incoming metal gas pipe, and any other metallic services entering the building. Minimum 10mm2 copper for most domestic installations (6mm2 where the main supply protective conductor is 16mm2 or less).
  • Supplementary bonding -- required in some locations (notably bathrooms, though this may be relaxed where all circuits in the room have RCD protection and the main bonding is confirmed satisfactory). Check connections and conductor size.
  • Earthing arrangement type -- identify and record the earthing arrangement (TN-C-S, TN-S, or TT). This determines the maximum Zs values for every circuit and affects the type of earth fault protection required.

Missing main bonding is one of the most commonly reported C1 (Danger Present) or C2 (Potentially Dangerous) observations. In older properties, it is common to find that bonding was never installed, that bonding conductors have been disconnected during plumbing or gas work, or that plastic replacements to metal pipes have broken the bonding continuity. Always trace the bonding conductors to confirm they are continuous and correctly connected.

05 · Testing Guide

Labelling and Identification

BS 7671 requires that every circuit is identified at the distribution board and that appropriate warning and safety notices are displayed. Labelling is a frequent source of C3 (Improvement Recommended) observations on older installations and is often overlooked even on new work.

  • Circuit identification -- every circuit must be identified at the distribution board with a durable, legible label. The labelling must match the circuit chart and clearly describe the circuit purpose and the area it serves.
  • RCD test notice -- "This installation, or part of it, is protected by a device which automatically switches off the supply if an earth fault develops. Test quarterly by pressing the button marked 'T' or 'Test'."
  • Dual supply warning -- required where the installation is fed from more than one source (for example, mains and a generator, or mains and solar PV with battery storage). The notice warns that the installation has more than one source of supply.
  • Periodic inspection notice -- must state the recommended date of the next periodic inspection and test.
  • Earthing arrangement label -- identifying the type of earthing arrangement (TN-C-S, TN-S, or TT) at the main earthing terminal.

Missing or incorrect labelling is classified as C3 in most circumstances. However, if the absence of labelling creates a genuine safety risk -- for example, no dual supply warning on an installation with solar PV, or no circuit identification on a large commercial distribution board where incorrect isolation could cause danger -- a higher classification may be appropriate.

06 · Testing Guide

Cable Condition and Routes

Assessing cable condition is a critical part of the visual inspection. Cables are the arteries of the installation, and their condition directly affects safety. Look for the following:

  • Insulation condition -- look for cracking, brittleness, discolouration (indicating overheating or UV degradation), mechanical damage, and exposed conductors. Old rubber-insulated cables (common in pre-1960s installations) are particularly prone to insulation breakdown.
  • Cable support -- cables must be adequately supported at the intervals specified in the IET On-Site Guide. Unsupported cables are subject to strain at connections, can be damaged by contact with sharp edges, and may sag into contact with hot surfaces.
  • Mechanical protection -- cables in locations where they are vulnerable to mechanical damage must be protected (conduit, trunking, or appropriate cable type). Check that protection is continuous and that cables are not exposed at entry points.
  • Thermal insulation -- cables installed in or passing through thermal insulation must be derated or oversized. Check loft spaces where insulation is laid over cables -- this is a very common finding in domestic properties.
  • Prescribed zones -- cables concealed in walls should be installed within the prescribed zones defined in BS 7671 Regulation 522.6.202 (within 150mm of an angle formed by two adjoining walls, or vertically/horizontally from any accessory) or protected by an RCD with a rated residual operating current not exceeding 30mA (Table 52.1).

Cable condition assessment requires access to as much of the installation as possible. Loft spaces, underfloor areas, ceiling voids, and risers should all be accessed and inspected where safely achievable. Any areas that cannot be accessed should be recorded as limitations on the inspection report.

Record test results hands-free on site

AI board scanner, voice test entry, and automatic BS 7671 validation — finish the certificate before you leave the property. From £6.99/mo.

Try the certificate tools free
Download on the App StoreGet it on Google Play
07 · Testing Guide

Accessories and Fixed Equipment

Every accessible accessory and item of fixed equipment should be visually inspected. This includes socket outlets, switches, fused connection units, junction boxes, light fittings, extractor fans, water heaters, and any other fixed electrical equipment.

  • Physical condition -- check for cracked or broken faceplates, loose mounting, discolouration from overheating, and evidence of arc damage. Damaged accessories with exposed live parts are classified as C1 or C2.
  • Correct installation -- check that accessories are appropriate for their location (IP rating for bathrooms and outdoor locations), correctly oriented, and securely fixed. Socket outlets in bathrooms are a common finding -- they must comply with the requirements of BS 7671 Section 701.
  • Signs of overheating -- discoloured or melted plastic around terminals is a clear indicator of a loose connection or overloaded circuit. This is a potentially dangerous defect (C2) that requires investigation.
  • Suitability for use -- check that accessories are appropriate for the expected use. A 13A socket outlet used to supply a fixed appliance that should be on a fused connection unit, or a domestic light switch used in a commercial environment, are examples of unsuitable accessories.

When inspecting accessories, open a sample of socket outlets and switches (where safe to do so with the circuit isolated) to check the internal connections. Loose terminals, insufficient conductor insulation stripped, and excessive bare conductor visible are common internal defects that are not visible from outside.

08 · Testing Guide

Special Locations

BS 7671 Part 7 identifies specific locations that require additional protective measures beyond the general requirements. During an inspection, pay particular attention to these areas:

  • Bathrooms (Section 701) -- check zone compliance for all equipment, IP ratings, supplementary bonding (if required), RCD protection, and the absence of socket outlets in zones 0, 1, and 2 (unless specifically permitted, such as shaver sockets to BS EN 61558-2-5).
  • Gardens and outdoor areas (Section 714) -- check IP ratings for all outdoor equipment, RCD protection, cable burial depth and mechanical protection, and the suitability of equipment for the outdoor environment.
  • Swimming pools and hot tubs (Section 702) -- these are high-risk special locations with very specific zone requirements, equipment restrictions, and bonding requirements.
  • Electric vehicle charging (Section 722) -- check that the EV charger installation complies with the dedicated requirements of Section 722, including protective measures, cable sizing, and isolation provisions.

Special locations require knowledge of the specific Part 7 requirements. If you are unsure about the requirements for a particular special location, refer to BS 7671 Part 7 before carrying out the inspection. Recording an incorrect finding (or missing a genuine defect) in a special location can have serious safety consequences.

09 · Testing Guide

Recording Your Findings

Every observation must be recorded clearly, with the correct observation code and sufficient detail for the client (and any future electrician) to understand the finding and its significance:

  • C1Danger present -- risk of injury exists. Immediate remedial action required. The person responsible for the installation must be informed immediately, and the danger should be made safe before leaving site if possible.
  • C2Potentially dangerous -- requires urgent remedial action. The defect does not present an immediate danger but could become dangerous under fault conditions or through deterioration.
  • C3Improvement recommended -- the installation does not comply with the current edition of BS 7671 but was likely compliant when installed. No immediate safety risk but improvement would enhance safety.
  • FIFurther investigation -- the inspection has identified a potential issue that requires further investigation to determine its nature and classification. This is not a classification of the defect itself but a flag that more work is needed.

For each observation, record: the location (room or area), the specific item or circuit affected, a clear description of the defect, the applicable regulation from BS 7671 (where relevant), and the classification code. Vague descriptions like "earthing inadequate" are unhelpful -- specify exactly what is inadequate and where. For example: "Main protective bonding conductor to incoming water pipe missing at point of entry (Reg 411.3.1.2) -- C2."

10 · Testing Guide

Elec-Mate for Electrical Inspections

Elec-Mate provides a structured digital inspection workflow that ensures nothing is missed and every finding is recorded professionally:

Structured Inspection Checklist

Work through every item on the Schedule of Inspections with a digital checklist on your phone. Tap compliant, non-compliant, or N/A for each item. Non-compliant items automatically prompt you to add an observation with the correct classification code.

AI Observation Classification

Describe the defect in plain language and Elec-Mate suggests the appropriate classification code (C1, C2, C3, or FI) with the relevant BS 7671 regulation reference. Built-in guidance helps you classify borderline findings correctly.

Automatic Report Generation

Your inspection findings, test results, and observations are compiled into a professional EICR or EIC automatically. Export as a PDF and send to the client from site. Every certificate is stored in the cloud for future reference.

Never Miss an Inspection Item

Structured digital inspection checklist with AI-assisted observation classification. Complete the full Schedule of Inspections on your phone.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions About Electrical Inspections

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Inspect with Confidence

Digital inspection checklist, AI observation classification, and automatic EICR generation. Join 1,000+ UK electricians using Elec-Mate on every inspection. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy