Electrical Maintenance Contracts: PPM, Testing Schedules and 2026 Pricing Guide
A well-structured electrical maintenance contract protects your commercial client and ensures legal compliance across their electrical installation, emergency lighting, and fire alarm systems. This guide covers the difference between planned preventative maintenance (PPM) and reactive maintenance, what testing is required and how often (EICR, PAT, BS 5266, BS 5839), what to include in a contract, and 2026 pricing from £500 to £5,000 per year.
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer — DP Electrical
Key Takeaways
1Electrical maintenance contracts for commercial properties fall into two categories: planned preventative maintenance (PPM), which follows a schedule to prevent failures, and reactive maintenance, which responds to faults as they occur. Most contracts combine both.
2A comprehensive PPM schedule for a commercial property includes fixed wire testing (EICR), portable appliance testing (PAT), emergency lighting tests (monthly, 6-monthly, and annual as required by BS 5266), and fire alarm tests (weekly call point test, monthly functional test, 6-monthly and annual tests as required by BS 5839).
3EICRs for commercial premises should be conducted every five years for most occupancies, though some higher-risk environments require more frequent inspection. BS 7671 recommends the frequency based on installation type and usage.
4Annual maintenance contract pricing for commercial properties typically ranges from £500 to £1,500 per year for small offices and retail units, £1,500 to £3,500 for medium commercial buildings, and £3,500 to £5,000+ for larger premises with complex electrical systems, emergency lighting, and fire alarm infrastructure.
5A well-written electrical maintenance contract protects both the contractor and the client. It should define the scope of work, frequency of visits, response times for reactive callouts, documentation and certification requirements, price adjustment mechanisms, and termination terms.
01 · Commercial Guide
Planned Preventative Maintenance vs Reactive Maintenance
Electrical maintenance for commercial properties falls into two categories: planned preventative maintenance (PPM) and reactive maintenance. Understanding the difference is essential for designing a maintenance contract that meets the client's operational needs and legal obligations.
Planned preventative maintenance (PPM) — scheduled visits at fixed intervals to inspect, test, and service electrical systems before faults develop. Includes fixed wire testing (EICR), portable appliance testing (PAT), emergency lighting tests, fire alarm tests, and general inspection of switchgear, distribution boards, and earthing. PPM reduces unplanned downtime and maintains legal compliance.
Reactive maintenance — responding to reported faults, circuit failures, equipment failures, and electrical emergencies. Reactive works cannot always be predicted or prevented by PPM alone. A maintenance contract should define the response times for different levels of urgency: emergency (e.g., loss of power to critical systems — 2-hour response), urgent (e.g., circuit failure — next working day), and routine (e.g., a faulty socket — within 5 working days).
Combined contracts — most commercial clients benefit from a contract that includes both PPM and reactive provision. PPM is typically priced as a fixed annual fee; reactive callouts are charged at an agreed labour rate (typically the contractor's standard or discounted rate for contract clients) plus materials.
Free download
Get the BS 7671 A4:2026 Cheat Sheet — free
Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.
Every regulation change summarised
New model forms (EIC + MEIWC)
Free PDF — no subscription
02 · Commercial Guide
PPM Schedule: What Needs Testing and When
A comprehensive PPM schedule for a typical commercial property includes multiple types of inspection and testing, each with its own frequency. The following schedule reflects best practice for a medium-sized commercial building.
Weekly — fire alarm call point test (rotate through call points one per week); visual check of emergency exit signs and luminaires. These are typically carried out by the building's own staff, not the maintenance contractor.
Monthly — emergency lighting functional test (brief duration, all luminaires); fire alarm monthly test and inspection; visual inspection of distribution boards (door seals, cable entry, labelling, no evidence of overheating).
Six-monthly — emergency lighting one-hour discharge test; fire alarm six-monthly inspection (all detectors tested in rotation, panel inspection, battery check); portable appliance testing for high-risk equipment (construction, catering, portable power tools).
Annually — emergency lighting full rated duration test (three hours for most systems under BS 5266); fire alarm annual inspection and test; portable appliance testing for standard office equipment; general electrical installation inspection; RCD testing.
Every 3–5 years — full EICR (fixed wire test) of the electrical installation. Frequency depends on occupancy type and previous EICR findings.
03 · Commercial Guide
Fixed Wire Testing (EICR) for Commercial Properties
The Electrical Installation Condition Report (EICR) is the formal document recording the findings of a periodic inspection and test of the fixed electrical installation. It is the cornerstone of any commercial electrical maintenance programme.
What is included in a commercial EICR — inspection of the main earthing and bonding, consumer units and distribution boards, wiring systems (condition, containment, fixings), electrical accessories and fittings, switchgear and controls, and testing of earth fault loop impedance, insulation resistance, RCD operation, polarity, and continuity. A schedule of test results is completed for every circuit.
Recommended frequency — offices: every five years; industrial: every three years; educational: every five years; catering: every one to three years; licensed premises: every five years; medical locations: every one to five years depending on location type. Higher-risk or older installations should be inspected more frequently.
Outcome: Satisfactory or Unsatisfactory — an EICR is classified as Satisfactory or Unsatisfactory. C1 (immediate danger) and C2 (potentially dangerous) observations result in an Unsatisfactory report. C3 (improvement recommended) observations result in a Satisfactory report but indicate remedial works that should be considered. Use the Elec-Mate EICR app to complete and issue commercial EICRs on site.
04 · Commercial Guide
Portable Appliance Testing (PAT) in Commercial Properties
PAT testing verifies that portable electrical appliances are safe for use. It is a key component of any commercial electrical maintenance programme and is required to demonstrate compliance with the Electricity at Work Regulations 1989.
What PAT testing involves — visual inspection of the appliance, plug, and cable; earth continuity test (class I appliances); insulation resistance test; and sometimes a substitute leakage test. Results are recorded on labels applied to the appliance and in a test register.
Test frequency by environment — construction sites and catering: every 3 months; industrial: annually; offices (portable appliances): every 2 to 4 years; offices (IT equipment, low use): every 4 years or less. The IET Code of Practice for In-Service Inspection and Testing of Electrical Equipment provides recommended intervals for each equipment type and environment.
Documentation — a PAT test register recording each appliance, its test results, the date of test, and the retest date. Failed appliances must be removed from service immediately and either repaired and retested or destroyed. The register must be maintained and available for inspection.
05 · Commercial Guide
Emergency Lighting Tests Under BS 5266
Emergency lighting is a life-safety system. Its maintenance is governed by BS 5266-1, which specifies a clear hierarchy of tests that must be carried out and recorded. These tests are a standard component of any commercial electrical maintenance contract.
Monthly functional test — simulate failure of the normal supply and verify each emergency luminaire and exit sign illuminates. Duration is the brief period recommended by the manufacturer (typically 30 seconds to 1 minute). Record which luminaires were tested and any failures. Restore normal supply and check luminaires recharge.
Six-monthly one-hour discharge test — simulate failure of normal supply and maintain discharge for one hour. Verify all luminaires maintain output throughout. Record results. Allow full battery recharge before restoring normal operation.
Annual full rated duration test — simulate failure and maintain for the full rated duration of the luminaires (typically three hours for maintained systems). All luminaires must maintain required light output throughout. Any failing luminaires must be replaced before the installation is returned to service.
Log book requirement — BS 5266-1 requires a log book recording all tests, any luminaire failures, remedial works, and the date of each test. The log book must be kept on site and presented to the responsible person (building owner or manager) and inspectors on request.
Record emergency lighting tests with Elec-Mate
Use Elec-Mate to record emergency lighting test results, generate compliant certificates, and maintain a digital log for each commercial property.
Fire alarm system testing is governed by BS 5839-1 (fire detection and fire alarm systems in buildings). Electrical contractors who include fire alarm testing in their maintenance contracts must understand the requirements of this standard.
Weekly call point test — test one manual call point per week, rotating through all call points over the cycle. The alarm signal must be generated at the control panel. This is typically carried out by building staff and recorded in the fire alarm log book.
Monthly inspection — a more thorough check of the control panel, battery levels, and system indicators. Testing of remaining call points not tested in weekly rotation.
Six-monthly inspection — inspection and test by a competent person: all detectors tested, all call points tested, sounders checked, panel inspection, standby battery test, and check of all linked systems (door holders, ventilation shutdown, etc.). Record all findings.
Annual inspection — comprehensive inspection by a specialist. For Category L (automatic detection) systems, this should be carried out by a firm registered with NSI or BAFE. Includes detector sensitivity testing, full system function test, and a detailed inspection report.
07 · Commercial Guide
What to Include in an Electrical Maintenance Contract
A well-drafted maintenance contract protects both the contractor and the client. It defines expectations, prevents disputes, and ensures legal compliance is maintained throughout the contract term.
Scope of works — a precise description of which systems, areas, and equipment are covered. Explicitly state any exclusions (e.g., specialist equipment, tenant areas, roof plant). Ambiguity in scope is the most common source of contract disputes.
Visit schedule — dates or frequency of scheduled PPM visits, what is carried out on each visit, and who the contractor will liaise with on site. Include provisions for rescheduling and notice periods for access.
Documentation requirements — what reports, certificates, and records will be provided after each visit. Specify formats (PDF, original paper certificates), timescales for delivery (e.g., within 5 working days), and who retains originals.
Reactive callout provision — response time tiers (emergency, urgent, routine), hours of cover (standard hours only, or 24/7), hourly rate for reactive callouts, call-out charge, and materials charging mechanism.
Price and payment terms — annual PPM fee, payment schedule (monthly, quarterly, or annual in advance), price review mechanism (e.g., annual RPI increase capped at 5%), and invoicing terms for reactive works.
Termination provisions — notice period (typically 3 months), termination for cause, and what happens to outstanding scheduled visits or active reactive works at termination.
08 · Commercial Guide
Electrical Maintenance Contract Pricing (£500–£5,000+ per Year)
Pricing an electrical maintenance contract requires understanding both the direct costs of the work and the overhead and margin required for the contract to be commercially viable. The following ranges are indicative for 2026.
Small office or retail unit (up to 500m²) — £500 to £1,500 per year. Annual EICR (every 5 years, amortised), annual PAT, monthly emergency lighting test, and quarterly fire alarm test. Reactive callout rate typically £65 to £85/hr.
Medium commercial building (500m² to 2,000m²) — £1,500 to £3,500 per year. Multiple distribution boards, larger emergency lighting installation, fire alarm system, more extensive PAT requirements, and more frequent EICR cycle.
Large commercial premises (2,000m²+) — £3,500 to £5,000+ per year. Complex HV/LV distribution, generator systems, UPS, large emergency lighting and fire alarm installations, and more frequent inspection requirements. Some large premises justify higher annual costs.
Reactive callout charges — typically charged separately. Contract clients often receive a discounted rate (10 to 20 per cent below standard) as an incentive for the contract. Emergency callouts outside standard hours are charged at the agreed out-of-hours rate.
09 · Commercial Guide
For Electricians: Managing Maintenance Contracts Efficiently
Maintenance contracts are a reliable source of recurring revenue for electrical businesses. Managing them efficiently — with good documentation, scheduled reminders, and professional certificates — protects both the business and the client.
Certify Every Maintenance Visit
Every maintenance visit should produce a certificate or inspection report. EICRs, minor works certificates, and PAT test registers are all evidence of compliance. Use the Elec-Mate EICR app to complete and issue certificates on the day of the visit. Never leave a site without documentation.
Invoice Contracts and Reactive Works Clearly
Maintenance contracts often involve separate invoices for the annual fee and for reactive callout works. Use the Elec-Mate quoting and invoicing app to issue professional invoices for both elements, with clear itemisation that satisfies commercial clients' accounts payable requirements.
Manage maintenance contracts with Elec-Mate
Join 1,000+ UK electrical contractors using Elec-Mate for EICR certificates, quoting, invoicing, and job management.
Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.
Fantastic app for electricians
I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.
Absolutely amazing
I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.
Trusted by electricians across the UK
Real feedback from real sparks
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer
Sole Trader · DP Electrical
“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”
Nathan Perry
Electrician · NP Electrical Services
“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”
Jake Pizey
3rd Year Apprentice · Apprentice
7-Day Free Trial — Cancel Anytime, No Hassle
Manage Your Maintenance Contracts with Elec-Mate
Join 1,000+ UK electrical contractors using Elec-Mate for EICR certificates, PAT records, professional invoicing, and job management. 7-day free trial.
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer, DP Electrical
From £6.99/mo after trial — less than a coffee a week
or download the app
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents
1,000+ electricians · From £6.99/mo after trial
We use cookies to improve the app and measure what works. Cookie Policy