DESIGN GUIDE

Electrical Design Guide: The BS 7671 Design Process

Good electrical design is the foundation of a safe, compliant installation. This guide walks through the entire BS 7671 design process — from assessing general characteristics and determining design current, through cable selection and correction factors, to protection coordination and voltage drop verification.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

15 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Every electrical installation must be designed in accordance with BS 7671 Part 3 (Assessment of General Characteristics) before any work begins — covering supply characteristics, load assessment, earthing arrangement, and external influences.
  • 2Cable selection involves a systematic process: determine design current (Ib), select protective device rating (In), apply correction factors (Ca, Cg, Ci, Cf), calculate tabulated current-carrying capacity (It), and verify from the tables in BS 7671 Appendix 4.
  • 3Protection coordination ensures that protective devices disconnect the supply within the required time for both overload (In >= Ib and I2 <= 1.45 x Iz) and fault conditions (the device operates within the maximum disconnection time for the circuit type).
  • 4Voltage drop must not exceed 3% for lighting circuits and 5% for other circuits (from the origin of the installation to the load) under BS 7671 Appendix 4.
  • 5Elec-Mate's AI Circuit Designer helps electricians with cable sizing, voltage drop calculations, and protection coordination — producing BS 7671 compliant designs on your phone.
01 · Design Guide

The BS 7671 Electrical Design Process

Every electrical installation — from a single additional socket to a full house rewire — requires a design. The design process is set out in BS 7671:2018+A4:2026 (the IET Wiring Regulations, 18th Edition with Amendment 4) and follows a structured sequence that ensures the completed installation is safe, functional, and compliant.

The design process is not just for large commercial installations. Even a domestic consumer unit upgrade or an additional circuit for an EV charger requires the designer to work through the same logical steps: assess the supply, determine the load, select the protection, size the cable, verify voltage drop, and confirm fault protection.

The design is documented on the Electrical Installation Certificate (EIC), which includes a section for design information. The designer signs the EIC to confirm that the installation has been designed in accordance with BS 7671.

The Design Sequence

  1. Assessment of general characteristics (Part 3)
  2. Determination of design current (Ib) for each circuit
  3. Selection of protective device type and rating (In)
  4. Cable selection — type, size, and installation method
  5. Verification of voltage drop
  6. Verification of earth fault loop impedance and disconnection time
  7. Verification of overload protection coordination
  8. Documentation on the EIC
Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Design Guide

Assessment of General Characteristics (Part 3)

Part 3 of BS 7671 requires the designer to assess the general characteristics of the installation before any detailed circuit design begins. This is the foundation of the entire design — if you get this wrong, everything that follows is compromised.

  • Supply characteristics (Chapter 31). Determine the nominal voltage (typically 230V single-phase or 400V three-phase in the UK), frequency (50Hz), prospective fault current at the origin (obtained from the DNO or measured), and the maximum demand of the installation.
  • Earthing arrangement. Identify the type of earthing system — TN-S, TN-C-S (PME), or TT. This is determined by the DNO and fundamentally affects the design of the earthing and bonding, the selection of protective devices, and the maximum earth fault loop impedance values.
  • External influences (Chapter 32). Assess environmental conditions: ambient temperature, presence of water, mechanical impacts, corrosive substances, vibration, and any other factors that affect the choice of equipment, cables, and installation methods.
  • Compatibility (Chapter 33). Consider electromagnetic compatibility, harmonic distortion, voltage fluctuations, and the compatibility of equipment with the supply characteristics.
  • Maintainability (Chapter 34). Design the installation to allow safe maintenance, inspection, and testing throughout its service life. Provide isolation and switching devices, clear labelling, and adequate access.

The assessment of general characteristics should be recorded and is part of the design documentation. It informs every subsequent design decision, from cable type to protective device selection.

03 · Design Guide

Determining Design Current (Ib)

The design current (Ib) is the current that the circuit is expected to carry under normal operating conditions. It is the starting point for selecting the protective device and sizing the cable.

  • Fixed loads: Ib = P / V (single-phase) or Ib = P / (1.732 x VL) (three-phase balanced). For example, a 9.5kW electric shower on a 230V supply: Ib = 9500 / 230 = 41.3A.
  • Socket circuits: Use diversity factors from the IET On-Site Guide. For a domestic ring circuit: 100% of the first 10A plus 40% of the remainder. A typical domestic ring has a design current of approximately 20A.
  • Lighting circuits: Sum the wattage of all connected light fittings and apply 66% diversity. For a circuit with 1,200W total connected load: Ib = (1200 x 0.66) / 230 = 3.4A.
  • Cooker circuits: 10A plus 30% of the remaining load plus 5A if a socket outlet is included. For a 12kW cooker: Ib = 10 + (0.3 x ((12000/230) - 10)) + 5 = 10 + 12.7 + 5 = 27.7A.

Getting the design current right is critical. An underestimated Ib could result in an undersized cable that overheats under normal load. An overestimated Ib wastes money on unnecessarily large cables and protective devices.

04 · Design Guide

Cable Selection and Sizing

Cable selection is the core of electrical design. The process involves determining the minimum cable size that can carry the design current safely, taking into account the installation conditions that reduce the cable's capacity.

The Cable Sizing Formula

It >= In / (Ca x Cg x Ci x Cf)

  • It — minimum tabulated current-carrying capacity required
  • In — rated current of the protective device
  • Ca — ambient temperature correction factor (Table 4B1)
  • Cg — grouping correction factor (Tables 4C1 to 4C5)
  • Ci — thermal insulation correction factor (Table 52.2)
  • Cf — semi-enclosed fuse factor (0.725 for BS 3036 fuses, 1.0 otherwise)

Once you have calculated It, refer to the current-carrying capacity tables in Appendix 4 of BS 7671 to find the cable size with a tabulated capacity equal to or greater than It. The table you use depends on the cable type (PVC, XLPE, MICC) and the installation method (clipped direct, in conduit, in trunking, in thermal insulation).

After selecting the cable size for current-carrying capacity, you must also verify that it meets the voltage drop limits and that the earth fault loop impedance at the extremity of the circuit is low enough for the protective device to disconnect within the required time.

Size cables instantly with Elec-Mate

Elec-Mate's cable sizing calculator applies all correction factors automatically, checks voltage drop…

Try it free for 7 days
Download on the App StoreGet it on Google Play
05 · Design Guide

Protection Coordination: Overload and Fault

Protection coordination ensures that the protective devices will operate correctly in both overload and fault conditions. There are two separate requirements that must both be satisfied:

Overload Protection

Two conditions must be met:

Condition 1: In >= Ib

The device rated current must be equal to or greater than the design current.

Condition 2: I2 <= 1.45 x Iz

The device effective operating current must not exceed 1.45 times the cable's current-carrying capacity. For MCBs where I2 = 1.45 x In, this simplifies to In <= Iz.

Fault Protection

The device must disconnect within:

0.4 seconds for final circuits up to 63A (TN systems)

0.2 seconds for final circuits up to 32A (TT systems)

5 seconds for distribution circuits

This is verified by checking the earth fault loop impedance (Zs) at the most remote point does not exceed the maximum value for the device.

The maximum earth fault loop impedance values for each device type (BS EN 60898, BS EN 61009, BS 88, BS 3036) and rating are given in the tables in BS 7671 Chapter 41. The measured or calculated Zs at the extremity of the circuit must not exceed these values. If it does, you need to either increase the cable size (to reduce the circuit impedance) or select a device with a higher fault current sensitivity.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · Design Guide

Voltage Drop Calculations

Voltage drop occurs because the cable has resistance — as current flows through the cable, some voltage is "lost" across the cable impedance. Excessive voltage drop can cause equipment to malfunction (lights dimming, motors overheating) and is limited by BS 7671.

  • Maximum voltage drop: 3% for lighting circuits (6.9V on 230V) and 5% for all other circuits (11.5V on 230V), measured from the origin of the installation to the load.
  • Formula: Voltage drop (V) = (mV/A/m x Ib x L) / 1000, where mV/A/m is from the cable tables, Ib is the design current, and L is the cable route length in metres.
  • If voltage drop exceeds the limit: increase the cable size (lower mV/A/m value) or reduce the cable route length. Cable size may need to be increased beyond what current-carrying capacity alone requires.
  • Worked example: A 32A radial circuit using 4mm2 T&E (clipped direct, mV/A/m = 11), design current 28A, cable length 25m. Voltage drop = (11 x 28 x 25) / 1000 = 7.7V. As a percentage: 7.7 / 230 x 100 = 3.35%. This is within the 5% limit for a socket circuit but would exceed the 3% limit if this were a lighting circuit.

Voltage drop is often the factor that determines cable size for long cable runs — even when the cable has adequate current-carrying capacity, it may not meet the voltage drop limit. Always check both criteria.

07 · Design Guide

Earthing and Bonding Design

The earthing and bonding arrangement is a fundamental part of the design. It provides the path for earth fault current to flow, enabling protective devices to disconnect the supply and preventing dangerous touch voltages on exposed metalwork.

  • Main earthing terminal — connects the installation earth to the means of earthing (DNO earth for TN systems, earth electrode for TT systems).
  • Main protective bonding conductors — connect incoming metallic services (gas, water, oil) to the main earthing terminal. Minimum size: 10mm2 for TN-S and TN-C-S, 6mm2 for TT (subject to the requirements of Table 54.8).
  • Circuit protective conductors (CPCs) — the earth conductor in each circuit cable. Size determined by the adiabatic equation or by Table 54.7 (minimum CPC size relative to the line conductor size).
  • Supplementary bonding — additional bonding between simultaneously accessible exposed-conductive-parts and extraneous-conductive-parts in specific locations (e.g., bathrooms under certain conditions).

The earthing arrangement must be designed to ensure that the earth fault loop impedance at every point in the installation is low enough for the protective devices to operate within the required disconnection times. For TT systems, where the earth fault loop impedance is inherently higher, RCD protection is essential to achieve adequate disconnection.

08 · Design Guide

Discrimination Between Protective Devices

Discrimination (also called selectivity) means that only the protective device nearest to the fault operates, leaving the rest of the installation energised. This is important for availability — a fault on one circuit should not disconnect the entire installation.

  • Between MCBs: discrimination is achieved when the upstream device has a higher rating and slower time-current characteristic than the downstream device. Generally, a ratio of 2:1 or higher in rated current provides adequate discrimination for most overcurrent conditions.
  • Between RCDs: discrimination requires the upstream RCD to have both a higher rated residual operating current (e.g., 100mA vs 30mA) and a time delay (Type S or selective RCD). Without a time delay, both RCDs will trip simultaneously.
  • RCBO boards: provide inherent discrimination for earth faults — only the RCBO on the faulty circuit trips, leaving all other circuits energised. This is the main advantage of a full RCBO consumer unit over a split-load RCD arrangement.

Good discrimination is essential for commercial and industrial installations where loss of power can have serious consequences. In domestic installations, a full RCBO board provides the best discrimination for the consumer — a single faulty circuit does not plunge the entire house into darkness.

09 · Design Guide

For Electricians: Design Tools in Elec-Mate

Electrical design requires calculations that are time-consuming to do by hand but essential for compliance. Elec-Mate puts these design tools on your phone, so you can complete the design on site and produce the certificate immediately.

AI Circuit Designer

Describe the circuit you need — "9.5kW shower, 18m cable run, clipped to joist, 3 other cables grouped" — and the AI calculates the design current, applies correction factors, selects the cable size, checks voltage drop, and verifies fault protection. All in seconds.

Calculators On Site

Cable sizing, voltage drop, adiabatic equation, maximum demand, prospective fault current — all the BS 7671 calculations you need, available on your phone, with results you can copy directly into the certificate.

Design circuits on your phone with AI

Join 1,000+ UK electricians using Elec-Mate's AI Circuit Designer and BS 7671 calculators. Cable sizing, voltage drop…

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions About Electrical Design

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

AI-Powered Electrical Design on Your Phone

Join 1,000+ UK electricians using Elec-Mate's AI Circuit Designer, cable sizing calculator, and BS 7671 design tools. Complete the design and certificate on site. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy