Replacing the consumer unit is frequently the centrepiece of a retrofit project. A modern consumer unit with individual RCBOs provides RCD protection to every circuit — significantly reducing the risk of electric shock and fire even on older wiring that may have minor insulation deterioration. The consumer unit change guide covers the full process in detail.
In older properties, the consumer unit change often reveals additional issues that must be addressed:
1Tails May Need Upgrading
Older properties may have 16mm² tails or smaller. Modern consumer units with higher rated main switches may require 25mm² tails. The DNO meter tails from the cutout to the meter may also need upgrading — this work must be carried out by the DNO or their appointed contractor.
2Nuisance Tripping on Old Circuits
Adding RCD protection to circuits with deteriorating insulation can cause nuisance tripping. Insulation resistance below 1 MΩ may be acceptable without RCD protection but will cause an RCD to trip. This is actually a benefit — it reveals circuits that need attention — but the customer must be informed before the work begins.
3SPD Requirements
BS 7671 now requires a surge protection device (SPD) to be fitted as part of a consumer unit change unless a risk assessment concludes it is not necessary. The SPD protects sensitive electronic equipment from transient overvoltages. In older properties with equipment earthing that may be less than ideal, an SPD is particularly valuable.