#1 · Insulation Resistance86% get this wrong
What might cause an insulation resistance reading to gradually increase during testing?
Answer: Absorption of current by the insulation (polarisation)
Why people miss it: When the test voltage is first applied, the dielectric draws a charging and polarisation current. As the insulation polarises, that current falls away — so the displayed resistance climbs. Most candidates pick options suggesting a fault or instrument error, but a gradually rising reading is normal behaviour on sound insulation, especially on long cable runs.
#2 · Earth Fault Loop Impedance76% get this wrong
What correction factor should be applied to measured Zs values?
Answer: Multiply by 1.2 for thermoplastic (1.04 for thermosetting)
Why people miss it: Conductors are tested cold but operate hot, and resistance rises with temperature. To compare a cold site reading against the maximum values (which assume operating temperature), the measured value is corrected upward — 1.2 for 70°C thermoplastic insulation. Candidates muddle this with the alternative "0.8 rule" applied to the tabulated limit; both express the same physics from opposite ends.
#3 · Earth Fault Loop Impedance74% get this wrong
What is the typical maximum Ze for a TT system?
Answer: 21 Ω
Why people miss it: TN values (0.35 Ω and 0.8 Ω) are drilled into everyone; the TT figure is not. 21 Ω is the conventional maximum for a stable TT earth electrode — and the reason TT protection leans on RCDs rather than overcurrent devices for shock protection.
#4 · Bonding & Continuity74% get this wrong
What is the minimum CSA for supplementary bonding conductors?
Answer: 4 mm² (where not mechanically protected)
Why people miss it: Supplementary bonding sizing has two tiers — 2.5 mm² is acceptable with mechanical protection, 4 mm² without. Candidates who memorise a single number get caught whichever way the question is framed. The full sizing logic is in Section 544.
#5 · RCD Testing71% get this wrong
What is the maximum permissible standing earth leakage for a 30 mA RCD protected circuit?
Answer: 10 mA — one third of the rated residual current
Why people miss it: The rule of thumb is that standing (protective conductor) leakage should not exceed one third of IΔn to avoid nuisance tripping — 10 mA on a 30 mA device. Candidates guess at half (15 mA) or the full rating; the one-third convention is the one guidance uses.
#6 · Insulation Resistance70% get this wrong
What effect does temperature have on insulation resistance readings?
Answer: Higher temperatures typically result in lower readings
Why people miss it: Insulation resistance falls as temperature rises — roughly halving for every 10°C in many materials. It is the mirror image of conductor resistance (which rises with temperature), and that inversion is exactly the trap the wrong options exploit.
#7 · Periodic Inspection70% get this wrong
What is the recommended inspection interval for cinemas?
Answer: 1 year
Why people miss it: Places of public entertainment carry short recommended intervals — one year for cinemas — because of occupancy risk. Candidates who only remember "10 years domestic, 5 years commercial" lose this mark; the special-premises table is worth a dedicated revision pass.
#8 · Insulation Resistance70% get this wrong
When testing a complete installation, what is the likely reading if all circuits pass individually?
Answer: Lower than the individual readings, due to parallel paths
Why people miss it: Insulation resistances in parallel combine like resistors in parallel — the whole-installation reading is always lower than the best individual circuit. A 200 MΩ circuit and a 100 MΩ circuit together read about 67 MΩ. Candidates expecting the "sum" or the lowest single value miss it.
#9 · Safe Isolation & Instruments67% get this wrong
What is the recommended minimum CAT rating for test equipment used on LV installations?
Answer: CAT III
Why people miss it: Overvoltage category ratings describe where an instrument can safely be used. Fixed LV installation work calls for CAT III as the minimum (CAT IV at the origin/supply side). CAT II instruments belong on plug-connected equipment, not distribution boards.
#10 · Earth Fault Loop Impedance65% get this wrong
What causes the difference between measured Zs and calculated Zs values?
Answer: Temperature — conductors are cooler when tested than the values assume
Why people miss it: Calculated Zs (Ze + R1+R2 corrected to operating temperature) will typically exceed a live measured Zs on a cold circuit — and parallel earth paths through bonding can pull the measured figure lower still. Understanding which direction the difference runs, and why, is what the question is really testing.