TESTING GUIDE

Insulation Resistance Testing: BS 7671 Procedure and Minimum Values

A complete guide to insulation resistance (IR) testing for UK electricians. Covers test voltages, the ≥1 MΩ minimum value, how to test new circuits, precautions on live circuits, and what Regulation 643.3 requires.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,600+ UK electricians

10 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

The short answer

What is the minimum insulation resistance value?

For a standard 230V/400V circuit, BS 7671 requires a minimum insulation resistance of 1.0 MΩ, tested at 500V DC; SELV and PELV circuits are tested at 250V DC with a 0.5 MΩ minimum (Table 64). The test is required by Regulation 643.3 as a dead test, with the supply isolated and sensitive equipment disconnected. A low or steadily falling reading points to moisture, damaged insulation or a wiring fault.

1,600+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5

Key takeaways

  1. 01Insulation resistance (IR) testing verifies that the insulation of conductors is intact and is not leaking current to earth or between conductors. BS 7671 Regulation 643.3 sets out the requirements.
  2. 02The test voltage applied depends on the circuit nominal voltage: 250V DC for SELV and PELV circuits, 500V DC for circuits up to and including 500V (most domestic and commercial circuits), and 1000V DC for circuits above 500V.
  3. 03The minimum acceptable insulation resistance value depends on circuit type. For SELV and PELV circuits (tested at 250V DC) the minimum is 0.5 MΩ. For circuits up to and including 500V — including all standard 230V domestic and 400V commercial circuits (tested at 500V DC) — the minimum is 1 MΩ. Guidance Note 3 goes further for new work: on a new installation, any value below 20 MΩ should be investigated.
  4. 04For new circuits, IR testing is carried out on the dead circuit before connection to the supply. All luminaires and appliances should be disconnected — many electronic devices are damaged by IR test voltages.
  5. 05On live circuit EICR work, IR testing requires safe isolation of the circuit under test and disconnection of sensitive electronic equipment before applying the test voltage.

01 · Testing Guide

Check Your Insulation Resistance Reading

Type the reading from your tester and get the verdict against the BS 7671 minimum for the test voltage — free, no sign-up.

Insulation Resistance Interpreter

What your reading means — BS 7671 Table 64 plus what it says about the installation

The value shown on the tester

Optional — a sharp fall matters even when the current reading passes

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Testing Guide

Why Test Insulation Resistance?

Insulation resistance (IR) testing is one of the fundamental verification tests required by BS 7671:2018+A4:2026 as part of both the initial inspection and testing of a new installation and the periodic inspection and testing of an existing installation (EICR). The purpose of the test is to verify that the insulation surrounding the conductors is in good condition and is providing adequate electrical separation between live conductors and between live conductors and earth.

Over time, electrical insulation degrades due to heat, moisture, mechanical damage, UV exposure, and chemical attack. As insulation degrades, its resistance decreases. At very low insulation resistance values, significant leakage current can flow through the insulation under normal operating conditions, causing energy loss, heating of the conductor insulation, and — if the leakage path is to earth — operation of residual current devices. In severe cases, low insulation resistance can lead to ignition of the insulation and electrical fire.

IR testing detects these problems before they become dangerous. A single IR test of a circuit takes only a few minutes and provides a quantitative measure of insulation health that can be compared against the minimum value required by BS 7671 Regulation 643.3 and tracked over successive EICR intervals to identify progressive deterioration.

03 · Testing Guide

Test Voltages — 250V, 500V, and 1000V DC

The test voltage for insulation resistance testing is specified in BS 7671 Table 64. Using the correct test voltage is essential — too low a voltage may not reveal insulation weaknesses, while too high a voltage can damage sensitive equipment.

250V DC

Used for SELV and PELV circuits with a nominal voltage up to 50V AC. Minimum IR value: 0.5 MΩ. Applies to extra-low voltage circuits such as fire alarm wiring, security systems, and ELV lighting.

500V DC

Used for circuits up to and including 500V nominal, with the exception of SELV and PELV. This covers all standard UK domestic and commercial circuits (230V single phase, 400V three phase). Minimum IR value: 1 MΩ. This is the most commonly used test voltage for electricians.

1000V DC

Used for circuits above 500V nominal. Minimum IR value: 1 MΩ. Rarely used in routine domestic or commercial electrical work; more common in industrial installations. Note these are still low voltage circuits — BS 7671 Part 2 defines low voltage as up to 1000V AC, so “above 500V” here does not mean high voltage.

The test voltage is applied for a minimum period sufficient for the reading to stabilise. For most modern digital instruments, this stabilisation is indicated by a steady display. The traditional recommendation is to apply the test for 1 minute, but follow your instrument manufacturer's guidance.

04 · Testing Guide

Minimum Acceptable Values — ≥1 MΩ

BS 7671 Table 64 sets the minimum acceptable insulation resistance values. For circuits up to 500V (tested at 500V DC), the minimum is 1 MΩ. This is a regulatory minimum, not a design target.

BS 7671 Table 64 — at a glance

Minimum insulation resistance and DC test voltage by circuit type

Circuit
Test voltage
Min IR
SELV & PELV
250 V DC
0.5 MΩ
Up to & incl. 500 V
500 V DC
1.0 MΩ
Above 500 V
1000 V DC
1.0 MΩ

Per BS 7671:2018+A4:2026 Table 64, Regulation 643.3.2. A pass at the minimum is not a target — Guidance Note 3 says to investigate any new installation reading below 20 MΩ.

  • Sound new installation — Guidance Note 3 treats 20 MΩ as the investigation point on new work: below that, subdivide the installation and test circuits individually to find the cause, even though 1 MΩ would technically conform to the Regulations.
  • Older installation — judge in context — Guidance Note 3 is explicit that assessing a reading depends on the age and type of installation, the length of cable involved, and the environmental conditions. A value that would prompt investigation on new work can be acceptable in context on an existing installation, but a downward trend across successive inspections should be recorded and monitored.
  • Failure — below the Table 64 minimum — the circuit fails the test. Before coding it on an EICR, confirm the reading is a genuine insulation fault rather than a connected electronic device that was not disconnected.

Remember that IR values can be temporarily reduced by moisture and humidity — a wet morning can cause surface tracking on cable insulation in outdoor or poorly ventilated locations. Where IR is borderline due to suspected moisture, allow the installation to dry out and retest before condemning the wiring.

05 · Testing Guide

Testing New Circuits — Step by Step

For a new circuit, IR testing is carried out before connection to the supply. Here is the correct procedure:

  1. 1Disconnect all equipment — remove all luminaires, disconnect all appliances, and remove or disconnect electronic equipment from the circuit. Leave switches in the closed (on) position so the switch wiring is included in the test.
  2. 2Link L and N at the board — at the consumer unit, link the line and neutral terminals of the circuit together so both conductors are tested simultaneously. The CPC (earth) is left separate.
  3. 3Test L+N to E — connect the IR tester between the linked L+N conductors and the earth (CPC). Apply 500V DC and record the reading.
  4. 4Test L to N — remove the link and test between L and N to check insulation between the two live conductors.
  5. 5Record results — note the measured IR value, the test voltage, and the circuit designation on the schedule of test results.
  6. 6Discharge before touching — as noted in Guidance Note 3, the cable capacitance holds the test voltage as residual charge that persists after the tester is removed and can cause a shock. Confirm the instrument has completed its discharge cycle before touching any conductors or reconnecting equipment.

In the app

Complete IR test records on your phone

Elec-Mate's EIC and EICR apps capture insulation resistance readings for every circuit, flag readings below the BS 7671 minimum…

In the app

Record test results hands-free on site

AI board scanner, voice test entry, and automatic BS 7671 validation — finish the certificate before you leave the property. From £6.99/mo.

06 · Testing Guide

Live Circuit Precautions for EICR Work

When carrying out IR testing as part of an EICR on an occupied installation, additional precautions are required:

  • Safe isolation first — always carry out safe isolation of the circuit before applying the IR test voltage. This is a legal requirement under the Electricity at Work Regulations 1989. Use an approved voltage indicator (GS38 compliant) before and after isolation to confirm the circuit is dead.
  • Warn occupants — inform the building occupants that circuits will be isolated and equipment may be disconnected during testing. Agree on a programme of isolation to minimise disruption.
  • Identify and protect sensitive equipment — before isolating each circuit, identify all connected equipment. Do not apply IR test voltages to circuits with connected surge protective devices, LED drivers, motor drives, or any equipment with electronic components unless those components are physically disconnected.
  • Identify and disconnect AFDDs — under the A4:2026 redraft of Reg 421.1.7, arc fault detection devices are now required on single-phase AC final circuits supplying socket-outlets rated up to 32 A in high rise residential buildings, houses in multiple occupation, purpose-built student accommodation and care homes, and recommended for the same circuits in all other premises. Expect to meet them far more often on A4:2026 boards. Their internal electronics are vulnerable to 500V DC test voltages. Check for AFDDs alongside SPDs before applying any test voltage.

Residual Charge — Shock Hazard

Guidance Note 3 explicitly flags residual charge as a shock hazard, not merely an instrument feature. IR testing charges cable capacitance to the full test voltage (500V DC or higher). This charge can persist after the tester is disconnected and the circuit may remain live to touch until it is fully discharged. Always confirm that the instrument has completed its automatic discharge cycle — and verify with an approved voltage indicator — before touching conductors or reconnecting equipment.

07 · Testing Guide

Regulation 643.3 Explained

BS 7671:2018+A4:2026 Regulation Group 643.3 is the primary requirement governing insulation resistance testing, and it splits into three parts.

643.3.1 says what to measure: the insulation resistance shall be measured between live conductors, and between live conductors and the protective conductor connected to the earthing arrangement. During that second measurement, line and neutral may be connected together — which is why the standard site method is to link L and N and test the pair to earth.

643.3.2 sets the pass criterion, and its wording is precise: the result is satisfactory where the main switchboard and each distribution circuit, tested separately with all its final circuits connected but with current-using equipment disconnected, is not less than the appropriate value in Table 64. The circuit wiring stays connected; the current-using equipment comes off. Note also that BS 5839-1 sets more specific requirements for fire detection and fire alarm system wiring.

643.3.3 is the part redrafted by A4:2026, and it deals with connected equipment that is likely to influence the measurement or be damaged by the test. It sets a two-stage sequence, not an either/or. First, the Table 64 test is applied prior to the connection of that equipment. Then, following connection of the equipment, a 250V DC test is applied between live conductors and the protective conductor connected to the earthing arrangement — and that reading must be at least 1 MΩ, not the 0.5 MΩ some assume from the 250V row of Table 64. A note to the regulation warns that manufacturer instructions may still recommend disconnecting particular equipment even for the 250V DC test.

The Table 64 values are the minimum for compliance with BS 7671. Where the inspector considers that a reading — although above the minimum — represents a deteriorating condition warranting monitoring, that observation should be recorded on the EICR.

08 · Testing Guide

For Electricians: Practical IR Testing Tips

Efficient insulation resistance testing requires a systematic approach. Here are practical tips from experienced inspection electricians:

Always Check for SPDs Before Testing

Surge protective devices (SPDs) are required under the A4:2026 redraft of Regulation 443.4.1 where the consequence of a transient overvoltage could be serious injury to or loss of human life, failure of a safety service as defined in Part 2, or significant financial or data loss. For all other cases, protection shall be provided unless the owner of the installation declares it is not required. A4:2026 deleted the old risk assessment method in Regulation 443.5 and Annex A443 — so on new work the default is that an SPD is fitted, and you will meet them far more often. Before applying any IR test voltage, check the consumer unit, distribution board, and sub-boards for SPDs and disconnect them from the circuit. An SPD left in circuit drags the reading down and can falsely condemn a sound installation. Also check for arc fault detection devices (AFDDs), which Reg 421.1.7 now requires on socket-outlet final circuits up to 32 A in high rise residential buildings, HMOs, purpose-built student accommodation and care homes, and recommends elsewhere. AFDDs contain electronics that are equally vulnerable to 500V DC test voltages and must be disconnected before testing.

Test by Section on Large Installations

On large commercial or industrial installations, test one section at a time and record the reading for each section. This makes it easier to identify which section has a low reading, rather than testing the entire installation as a single unit and getting a low combined result that is difficult to investigate.

Frequently Asked Questions About Insulation Resistance Testing

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-day free trial

Record IR Test Results and Complete EICRs on Your Phone

Elec-Mate automatically checks IR readings against the BS 7671 minimum and generates professional test schedules on site. Join 1,600+ UK electricians. 7-day free trial.

Start your free trial

From £6.99/mo after the trial — no charge until day 8.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in one tap — no calls, no hassle
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play
Certificate types
19Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists

1,600+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy