INSTALLATION GUIDE

Heat Pump Electrical Requirements: ASHP Circuits, Controls and MCS

Air source heat pumps require a dedicated circuit sized to the compressor input, typically 32A to 63A. This guide covers ASHP circuit sizing, DNO notification, immersion backup circuits, UFH zone controls wiring, MCS certification, and the Boiler Upgrade Scheme grant.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

14 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

What electrical supply does an air source heat pump need?

A domestic ASHP needs a dedicated circuit sized to the compressor electrical input (not the thermal output) — typically a 16A circuit on 2.5mm² for a 5–8kW unit, rising to 32–40A on 6mm² for 16–20kW units. Most run on single-phase 230V. Add an immersion backup circuit (usually 16A) and controls wiring, then test and certify the work to BS 7671:2018+A4:2026 and issue an EIC.

Always size from the manufacturer’s electrical data sheet — rated current, maximum current and starting current all matter. Check the DNO supply fuse has spare capacity before connecting.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1An air source heat pump (ASHP) requires a dedicated circuit sized to the compressor electrical input — typically 32A to 63A single-phase for a 5kW to 16kW output heat pump.
  • 2Heat pumps do not export to the grid, so DNO G99 approval (for export above 3.68kW) does not apply. However, some DNOs require notification for large single-phase loads — check with the relevant DNO.
  • 3An immersion heater backup circuit (typically 16A on a 2.5mm cable) is often included in the heat pump installation to provide domestic hot water when the heat pump is in defrost mode or under service.
  • 4UFH (underfloor heating) manifold wiring for a heat pump system involves low-voltage wiring between zone valves, room thermostats, and the heat pump controller — a task that requires careful coordination with the plumber.
  • 5MCS (Microgeneration Certification Scheme) certification is required for the heat pump installer for the homeowner to access the Boiler Upgrade Scheme (BUS) grant — currently up to £7,500 for an ASHP.
01 · Installation Guide

Heat Pump Electrical Requirements: What UK Electricians Need to Know

Air source heat pumps (ASHPs) are the central technology in the UK's heat decarbonisation programme. Government grant funding (the Boiler Upgrade Scheme), rising gas prices, and the heat pump installation target of 600,000 per year by 2028 mean that heat pump electrical work is a significant and growing opportunity for UK electricians.

The electrician's role in a heat pump installation typically covers: the dedicated circuit from the consumer unit to the outdoor unit, the immersion heater backup circuit to the hot water cylinder, the controls wiring for UFH zone valves and room thermostats, and the testing and certification of all electrical work under BS 7671:2018+A4:2026.

This guide covers circuit sizing, DNO notification, immersion backup circuits, UFH controls wiring, MCS certification and the BUS grant, and the testing and certification requirements for heat pump electrical installations.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Installation Guide

Circuit Sizing for Air Source Heat Pumps

The dedicated circuit for an ASHP must be sized for the compressor electrical input, not the thermal output. The COP (Coefficient of Performance) determines the relationship between thermal output and electrical input:

Heat output (COP ~3)Electrical inputIndicative circuitCable (T&E)
5kW – 8kW1.7kW – 2.7kW16A RCBO2.5mm²
10kW – 12kW3.3kW – 4kW20A – 25A RCBO4mm²
16kW – 20kW5.3kW – 6.7kW32A – 40A RCBO6mm²

Indicative only. Confirm the conductor size against the actual run length and installation method — a long run to an outdoor unit can force the next size up on voltage drop, and a high compressor starting current may need a time-delay device at the consumer unit.

Always request the electrical specification sheet from the heat pump manufacturer before sizing the circuit. The rated current, maximum current, and starting current are all relevant. Heat pump compressors draw a high inrush at start-up, so check the inrush figure against the protective device characteristic. Use the cable sizing calculator to confirm the cable size for the actual run length from the consumer unit to the outdoor unit position.

Size heat pump circuits and quote electrical packages

Elec-Mate's cable sizing calculator and quoting app help UK electricians design and price heat pump electrical packages.

Try it free for 7 days
Download on the App StoreGet it on Google Play
03 · Installation Guide

DNO Notification for Heat Pump Installations

Heat pumps consume electricity — they do not generate or export. This means that the DNO notification requirements that apply to solar PV and battery storage (G98, G99) do not directly apply. However, there are still DNO considerations:

  • Supply fuse capacity — the existing DNO supply fuse (typically 60A, 80A, or 100A) must have adequate capacity for the additional ASHP load. For a house with an existing 60A fuse, adding a 10kW ASHP (4kW electrical input) on top of the existing heating, hot water, and general loads may approach or exceed the fuse capacity during a cold snap. Assess the maximum demand carefully.
  • DNO load notification — some DNOs require notification of new large loads connected to the LV network. Check the relevant DNO's guidance for your region. EDF Energy, National Grid, and UKPN all have self-connection criteria — large single-phase loads over 11kVA may require notification.
04 · Installation Guide

Immersion Heater Backup Circuit

Heat pump cylinders include a 3kW immersion heater element as a backup. The electrical installation for the immersion heater must include:

  • Dedicated circuit — a 16A circuit on 2.5mm twin and earth from the consumer unit to the cylinder position, with a switched fused connection unit (SFCU) adjacent to the cylinder. The SFCU allows local isolation for maintenance.
  • Anti-Legionella cycle — the heat pump controller typically manages a weekly anti-Legionella cycle at 60°C, activating the immersion heater. This must be enabled during commissioning — confirm with the heat pump engineer that the anti-Legionella function is active and that the immersion element is correctly wired to the controller relay output.
  • Labelling — label the SFCU and the consumer unit MCB/RCBO clearly: "Immersion Heater — Heat Pump Backup". This helps the homeowner and future electricians understand the function of the circuit.
05 · Installation Guide

UFH Manifold and Zone Controls Wiring

Where the heat pump heats the property via underfloor heating (wet UFH), the controls wiring is a significant element of the electrical installation:

  • Room thermostats — one per heating zone (typically one per room or floor). The thermostat signals demand to the manifold zone valve actuator or to the heating controls hub. Wire according to the heat pump manufacturer's controls schematic — wiring conventions vary between brands.
  • Manifold zone valve actuators — motorised actuators (typically 24V or 230V) fitted to the manifold ports. They open or close to allow or prevent flow to each zone based on the room thermostat signal. Actuators must be wired in accordance with the manifold manufacturer's wiring diagram.
  • Heat pump enable signal — when at least one zone calls for heat, a demand signal (volt-free contact or specific signal type depending on the heat pump brand) is sent to the heat pump controller to start the compressor. Coordinate the wiring of this signal with the heat pump installer.

The controls wiring for a heat pump UFH system is low-voltage and is excluded from the BS 7671 EIC scope in terms of circuit testing, but the mains supply to the controls hub or room thermostats (if mains-powered) is included in the EIC scope.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · Installation Guide

MCS Certification and the Boiler Upgrade Scheme

The Boiler Upgrade Scheme (BUS) provides a grant of up to £7,500 for an ASHP installation (2024/25 rates — check GOV.UK for current rates). To access the grant:

  • MCS-certified installer — the heat pump installer must be MCS-certified and must install an MCS-registered heat pump product. The electrician sub-contractor does not need to be MCS-certified — their role is to supply the EIC for the electrical work.
  • EPC requirement — the property must have an Energy Performance Certificate (EPC) with a rating of A to D (not E, F, or G) to be eligible for the BUS grant. The EPC must be current (less than 10 years old). If the property has a low EPC rating, insulation improvements may be required before the heat pump installation proceeds.
  • Grant application — the MCS-certified installer applies for the BUS grant on behalf of the homeowner before installation begins. The grant is deducted from the installation cost — the homeowner pays the net price.
07 · Installation Guide

Testing and Certification

The electrical installation for a heat pump must be inspected and tested as part of initial verification under BS 7671:2018+A4:2026 Chapter 64. Carry out the dead tests before energising, then the live tests, recording the results on the Schedule of Test Results. The test sequence for the dedicated ASHP circuit:

TestBS 7671 referenceWhat good looks like
Continuity of conductors / CPCReg 643.2Low, stable end-to-end reading on the protective conductor from the MET to the heat pump enclosure earth terminal.
Insulation resistanceReg 643.3, Table 64Tested at 500V DC for a 230/400V circuit; minimum 1.0 MΩ. Disconnect the heat pump at the local isolator so its electronics do not influence or suffer from the test.
PolarityReg 643.6Correct polarity confirmed at the local isolator and at the heat pump supply terminals.
Earth fault loop impedance (Zs)Reg 643.7.3Measured Zs at the heat pump supply terminals within the maximum permitted for the protective device and disconnection time.
RCD additional protectionReg 643.8Where a 30mA RCD/RCBO provides additional protection, it disconnects within 300ms at rated residual operating current for a general non-delay type.
Functional testReg 643.10Energise and verify the isolator, controls and compressor operate correctly — the compressor starts and runs as intended.

An Electrical Installation Certificate must be issued covering all new circuits. The EIC should note the heat pump model, the dedicated circuit rating, and the local isolator position. A copy of the EIC is provided to the MCS-certified heat pump installer for inclusion in the commissioning documentation.

08 · Installation Guide

For Electricians: Growing Your Heat Pump Business

Heat pump installations are a growing market and the electrical package — dedicated circuit, immersion backup, and controls wiring — is typically worth £500 to £1,500 per installation as a sub-contract element. Building relationships with MCS-certified heat pump installers generates recurring referrals.

Check Supply Capacity First

Before agreeing to connect the heat pump, check the DNO supply fuse rating and the existing consumer unit maximum demand. If the supply fuse is undersized for the additional ASHP load, a supply fuse upgrade is required — this involves the DNO and takes time. Flag this on the survey to avoid programme delays.

Issue EIC Promptly

The heat pump installer needs the EIC to complete their MCS commissioning documentation and to register the BUS grant. A prompt EIC — issued the same day using the EIC Certificate app — makes you the preferred electrical sub-contractor for heat pump installers who care about their customer experience.

Quote and certify heat pump electrical installations

Join 1,000+ UK electricians using Elec-Mate for heat pump circuit sizing, professional quoting, and on-site EIC certification.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions About Heat Pump Electrical Requirements

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Quote and Certify Heat Pump Electrical Installations

Elec-Mate gives UK electricians cable sizing, professional quoting, and on-site EIC certification for heat pump electrical sub-contract work. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy