SPECIAL INSTALLATION

Marina Electrical Installations: BS 7671 Section 709 Guide

BS 7671 does cover marinas — Section 709. A PME earth must not reach the boat, every socket-outlet needs its own 30 mA RCD switching the neutral, sockets are IP44 minimum and at least 1 m above the highest water level. This guide sets out every Section 709 requirement, reg by reg.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

12 min readUpdated 2026-08-07Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

The short answer

What are the BS 7671 rules for marina electrical installations?

Marinas and similar locations are covered by BS 7671 Section 709. Because the ESQCR prohibit connecting a PME earthing facility to any metalwork in a boat (Reg 709.411.4), and socket-outlet protective conductors must not be connected to a PME earth (Reg 709.553.1.14), the berth supply is derived from a TT arrangement with a local electrode, a DNO TN-S supply, or an on-shore isolating transformer to BS EN 61558-2-4. Every socket-outlet must be protected individually by an RCD to Reg 415.1.1 (30 mA) that disconnects the neutral, must supply only one pleasure craft or houseboat, must be at least IP44 (IPX5 or IPX6 where AD5 or AD6 apply), and must sit at least 1 m above the highest water level — 300 mm on floating pontoons with additional splash protection. Equipment on or above a jetty or pontoon must also satisfy AE2, AF2 (AF3 with hydrocarbons) and AG2.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5

Key takeaways

  1. 01BS 7671 does apply to marinas — Section 709 covers circuits supplying pleasure craft and houseboats. It does not apply to electrical equipment on board ships (Reg 110.2(d)) or to the internal installation of a pleasure craft (Reg 709.1).
  2. 02The ESQCR prohibit connecting a PME earthing facility to any metalwork in a boat, and Reg 709.553.1.14 forbids connecting socket-outlet protective conductors to a PME earth. In practice the berth supply is TT with a local electrode, a DNO TN-S supply, or an isolating transformer.
  3. 03Every socket-outlet must be protected individually by an RCD to Reg 415.1.1 (rated residual operating current not exceeding 30 mA), and the device must disconnect all live conductors including the neutral (Reg 709.531.2).
  4. 04Every socket-outlet must meet at least IP44, rising to IPX5 (AD5, water jets) or IPX6 (AD6, water waves) — Reg 709.553.1.8. Other equipment on or above a jetty, wharf, pier or pontoon needs at least IP3X (Reg 709.512.2.1.2), plus AF2 corrosion resistance (AF3 where hydrocarbons are present) and protection against AG2 impact.
  5. 05Elec-Mate helps electricians complete certificates for special installations, with AI assistance for the specific BS 7671 Section 709 requirements.

01 · Special Installation

Does BS 7671 Apply to Marinas?

Yes. Marinas and similar locations are covered by Section 709, in Part 7 of BS 7671. The exclusion people confuse it with is electrical equipment on board ships, which BS 7671 does not cover (Regulation 110.2(d)); offshore installations are excluded by Regulation 110.2(e).

Section 709 is itself narrow. Regulation 709.1 states that its particular requirements apply only to circuits intended to supply pleasure craft or houseboats. They do not apply to the internal electrical installation of a pleasure craft — for those, see BS EN 60092-507 — and they do not apply to houseboats supplied directly from the public network. Everything else on the site is ordinary BS 7671 work.

The figures you came for

The six numbers that decide most marina design and inspection questions.

30 mA

Individual RCD on every socket-outlet, disconnecting the neutral

Reg 709.531.2

IP44

Minimum for every socket-outlet

Reg 709.553.1.8

1 m

Socket height above highest water level (300 mm on floating pontoons)

Reg 709.553.1.13

1 boat

Per socket-outlet — no splitting

Reg 709.553.1.11

4 max

Socket-outlets grouped in one enclosure

Reg 709.553.1.10

230 / 400 V

Nominal supply voltage, single-phase / three-phase

Reg 709.313.1.2

Why marinas get their own section

Regulation 709.512.2 spells out what Section 709 is guarding against: corrosive elements, movement of structures, mechanical damage, the presence of flammable fuel, and an increased risk of electric shock caused by the presence of water, reduction in body resistance, and contact of the body with Earth potential. Three practical consequences follow.

  • Water conducts, and a person in it is the better path. A fault that puts even a few volts into the water near a pontoon can incapacitate a swimmer. The risk is well documented in freshwater as well as salt water, and it is the reason the earthing restrictions in 709.411.4 and 709.553.1.14 exist.
  • The environment attacks the equipment. Salt spray corrodes terminals and enclosures, UV degrades sheaths, pontoon movement stresses connections, and condensation forms inside enclosures as temperatures swing. Section 709 answers this with explicit external-influence classifications rather than leaving it to judgement.
  • Everything moves. Regulation 709.521.1.6 requires cables to be selected and installed so that mechanical damage due to tidal and other movement of floating structures is prevented, and cable management systems to be installed so water can drain — by drainage holes and/or by mounting the equipment on an incline.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Special Installation

BS 7671 Section 709: Reg-by-Reg

Section 709 of BS 7671:2018+A4:2026 applies to installations in marinas and similar locations for the supply to pleasure craft and houseboats. Use this as your on-site checklist.

RegulationRequirement
709.313.1.2Nominal supply voltage for the supply to pleasure craft or houseboats shall be 230 V AC single-phase or 400 V AC three-phase.
709.313.1.101Where a fixed on-shore isolation transformer is used, equipment conforming to BS EN 61558-2-4 shall be used, and the PE of the supply to the transformer shall not be connected to the earth terminal in the socket-outlet supplying the vessel.
709.410.3.5Obstacles and placing out of reach (Section 417) shall not be used as protective measures.
709.410.3.6Non-conducting location (Reg 418.1) and earth-free local equipotential bonding (Reg 418.2) shall not be used.
709.411.4The ESQCR prohibit connection of a PME earthing facility to any metalwork in a boat. This does not preclude PME as the means of earthing for other purposes, such as permanent buildings on the site.
709.512.2.1.1Equipment on or above a jetty, wharf, pier or pontoon: IPX4 for water splashes (AD4), IPX5 for water jets (AD5), IPX6 for water waves (AD6).
709.512.2.1.2At least IP3X against the ingress of small objects (AE2).
709.512.2.1.3Suitable for atmospheric corrosive or polluting substances (AF2); AF3 applies if hydrocarbons are present.
709.512.2.1.4Protected against medium-severity impact (AG2), by position, by local or general mechanical protection, or by equipment rated at least IK08 to BS EN 62262.
709.521.1.7Underground distribution cables buried deep enough to avoid damage unless given additional mechanical protection; the note gives 0.5 m as the depth generally considered a minimum.
709.521.1.8All overhead conductors insulated; at least 6 m above ground where vehicles move and 3.5 m elsewhere. Poles and supports located or protected against foreseeable vehicle movement.
709.531.2Socket-outlets protected individually by an RCD to Reg 415.1.1, disconnecting all live conductors including the neutral. The same applies to final circuits for fixed connection to houseboats.
709.533Each socket-outlet protected by an individual overcurrent protective device to Chapter 43; likewise each fixed connection supplying a houseboat.
709.537.2.1.1At least one means of isolation in each distribution cabinet, disconnecting all live conductors including the neutral; one isolating switching device for a maximum of four socket-outlets.
709.553.1.8Socket-outlets to BS EN IEC 60309-2 up to 63 A and BS EN IEC 60309-1 above 63 A; at least IP44, or IPX5/IPX6 where AD5/AD6 apply.
709.553.1.9Every socket-outlet located as close as practicable to the berth supplied, and installed in the distribution board or in separate enclosures.
709.553.1.10A maximum of four socket-outlets grouped together in one enclosure, to avoid the hazard of long connection cords.
709.553.1.11One socket-outlet shall supply only one pleasure craft or houseboat.
709.553.1.12In general, single-phase socket-outlets rated 200–250 V, 16 A shall be provided; higher ratings where greater demands are envisaged.
709.553.1.13Socket-outlets at least 1 m above the highest water level; on floating pontoons or walkways only, this may reduce to 300 mm with appropriate additional splash protection.
709.553.1.14Socket-outlet protective conductors shall not be connected to a PME earthing facility.

These requirements sit on top of the rest of BS 7671. Section 700 puts it plainly: the particular requirements of each Part 7 section supplement or modify the general requirements, and the absence of any reference excluding a part, chapter, section or regulation means the corresponding general regulation still applies.

One A4:2026 housekeeping point worth knowing if you are working from an older copy: Figures 709.1 and 709.2 were deleted, and the connection arrangements are now shown in Figures A709.1 to A709.4.

03 · Special Installation

Earthing: Keeping a PME Earth Away From the Boat

The earthing arrangement is the most consequential decision in a marina design, and the rule is narrower than it is often described. BS 7671 does not say "TT is mandatory". It says, at Regulation 709.411.4, that the ESQCR prohibit the connection of a PME earthing facility to any metalwork in a boat — and at Regulation 709.553.1.14, that socket-outlet protective conductors shall not be connected to a PME earthing facility.

The hazard behind those two regulations is the broken PEN conductor. In a PME (TN-C-S) system the DNO's combined neutral and earth conductor provides the earth reference. If it breaks, neutral current finds another route to earth — and at a marina that route runs through the water. That is what puts voltage into the water around the berths.

Three compliant ways to supply a berth

ArrangementHow it satisfies 709.411.4 / 709.553.1.14
TT with a local electrodeThe berth supply takes its earth reference from an electrode on site rather than from the DNO PEN conductor. The most common solution, and the reason RCDs do the fault-protection work.
DNO TN-S supplyWhere the distributor provides a genuine TN-S supply with a separate protective conductor, there is no PME earthing facility to connect to the boat.
Isolating transformerA fixed on-shore transformer to BS EN 61558-2-4 (Reg 709.313.1.101). Its supply PE must not be connected to the earth terminal in the socket-outlet supplying the vessel.

The on-shore parts of the site — office, workshop, chandlery — may stay on the PME supply. Regulation 709.411.4 expressly says the prohibition does not preclude the use of a PME earthing facility as the means of earthing for other purposes, such as the installations of permanent buildings.

Sizing the electrode on a TT berth supply

The earth electrode resistance must be measured and recorded. Regulation 411.5.3(b) gives the criterion for an RCD used for fault protection: RA × IΔn must not exceed 50 V, where RA is the sum of the resistances of the earth electrode and the protective conductor connecting it to the exposed-conductive-parts. With a 30 mA RCD that puts the arithmetic limit at about 1667 Ω — a number no one should design to. Aim far lower so the reading stays stable through dry summers and corroding connections; Regulation 411.5.3 is also met where the earth fault loop impedance satisfies the maximum values in Table 41.5.

04 · Special Installation

Shore Supply and Distribution

The shore power system takes the incoming supply and distributes it to individual berths via supply pillars (also called feeder pillars or service pedestals) on the pontoons or jetty.

Socket ratings and connector standards

Regulation 709.553.1.12 sets 16 A single-phase at 200–250 V as the general default, with higher ratings where greater demands are envisaged. Regulation 709.553.1.8 fixes the connector standard by rating.

RatingSupplyConnector standardTypical craft
16 ASingle-phaseBS EN IEC 60309-2The default provision under 709.553.1.12; smaller yachts and motor cruisers
32 ASingle-phaseBS EN IEC 60309-2Larger vessels with higher demand
63 AThree-phaseBS EN IEC 60309-2 (up to and including 63 A)Large craft and superyachts
> 63 AThree-phaseBS EN IEC 60309-1Superyachts and commercial vessels

Pillars and sub-mains

  • Supply pillars. A pillar carries CEE socket-outlets, an individual overcurrent device and RCD per socket, isolation, and a meter where required. Regulation 709.553.1.10 caps an enclosure at four socket-outlets, and 709.537.2.1.1 allows one isolating switching device per four socket-outlets — so a four-way pillar is the natural unit. The pillar itself must satisfy the external-influence classifications in 709.512.2, which in practice means a corrosion-resistant body such as GRP or marine-grade stainless steel.
  • Distribution boards and sub-mains. Each sub-main to a pillar needs overcurrent protection and isolation at the main board, and must be sized for the maximum demand of that pillar, allowing for voltage drop on what can be very long runs to the end of a pontoon.
  • Positioning. Regulation 709.553.1.9 requires every socket-outlet to be as close as practicable to the berth it supplies. Long connection cords are exactly the hazard the section is trying to design out.

The flexible cable from pillar to boat is normally the owner's. H07RN-F with matching CEE plug and connector is the standard choice. Marina operators should inspect these visually and refuse damaged cables — a cracked sheath on a trailing lead undoes every other measure on this page.

In the app

Design marina distribution with Elec-Mate calculators

Cable sizing, voltage drop, maximum demand, and prospective fault current — all the calculations you need for marina distribution design, on your phone.

05 · Special Installation

IP Ratings and External Influences

Regulation 709.512.2 classifies equipment installed on or above a jetty, wharf, pier or pontoon against four external-influence codes — water (AD), solid foreign bodies (AE), corrosive or polluting substances (AF) and impact (AG). Socket-outlets then carry a separate, higher minimum of their own under 709.553.1.8.

InfluenceConditionMinimum protectionRegulation
Water (AD)Splashes (AD4) / jets (AD5) / waves (AD6)IPX4 / IPX5 / IPX6709.512.2.1.1
Solid bodies (AE)Small objects (AE2)IP3X709.512.2.1.2
Corrosion (AF)Atmospheric corrosive or polluting substances (AF2); hydrocarbons present (AF3)AF2 / AF3709.512.2.1.3
Impact (AG)Medium-severity mechanical impact (AG2)AG2, or IK08 equipment709.512.2.1.4
Socket-outletsAll positions; AD5 or AD6 where applicableIP44, or IPX5 / IPX6709.553.1.8

Read those two rows together and the practical floor for a pontoon becomes clear: IP3X for solid bodies plus at least IPX4 for water on general equipment, and IP44 on every socket-outlet however sheltered it looks. Specifiers commonly select a single combined rating such as IP66 to satisfy both digits at the exposed end of a pontoon.

What the classifications mean on site

  • AF2 and AF3 (Reg 709.512.2.1.3). Equipment on or above a jetty, wharf, pier or pontoon must be suitable for atmospheric corrosive or polluting substances. Where hydrocarbons are present — a fuel pontoon, for instance — the requirement steps up to AF3. Material choice, coatings and gasket integrity all have to satisfy the applicable class.
  • AG2 impact (Reg 709.512.2.1.4). Boat hooks, mooring lines, fenders and vessel movement are all foreseeable. The regulation gives three routes: choose a position that avoids reasonably foreseeable impact, provide local or general mechanical protection, or install equipment rated at least IK08 to BS EN 62262.
  • Corrosion-resistant materials. Enclosures, fixings and cable management should be marine-grade — Grade 316 stainless, GRP, or equivalent. Standard galvanised steel will not last in salt spray.
  • The rating is only as good as the last gland. An IP66 enclosure is worth nothing once a gasket has perished or a gland is loose. Unused knockouts must be sealed with IP-rated blanking plugs, not tape or silicone, which degrade under UV and salt.

In the app

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

06 · Special Installation

RCD Requirements: Individual Protection Is Mandatory

Regulation 709.531.2 requires that socket-outlets be protected individually by an RCD having the characteristics specified in Regulation 415.1.1 — a rated residual operating current not exceeding 30 mA. The device selected must disconnect all live conductors, including the neutral. The same requirement applies to final circuits intended for fixed connection to houseboats.

Two parts of that sentence are routinely missed on site. The first is “individually”: unlike a domestic board, RCDs may not be shared between socket-outlets. The second is the neutral — an ordinary single-pole-switched RCBO does not satisfy 709.531.2.

  • Why individual devices. An earth fault on one boat trips only that berth. Everything else keeps its shore power, including refrigeration, battery chargers and bilge pumps on vessels that have nothing wrong with them.
  • RCD type. Regulation 531.3.3 restricts Type AC to serving fixed equipment where it is known that the load current contains no DC components — which a socket-outlet supplying a boat is not. Type A is therefore the working minimum, and Type B or Type F may be appropriate where inverters or variable-speed equipment on board can produce smooth DC or mixed-frequency residual currents.
  • RCBOs. Combining the individual overcurrent device required by 709.533 and the individual RCD required by 709.531.2 in one four-module-wide space suits a pillar well — provided the device switches the neutral.
  • Verification. Regulation 643.8 requires the effectiveness of automatic disconnection by RCDs to be verified with test equipment to BS EN 61557-6. Its note deems effectiveness verified where the RCD disconnects within the stated time on an alternating current test at rated residual operating current (IΔn) — 300 ms maximum for a general, non-delay type.

Keeping a PME earth away from the boat and putting an individual 30 mA RCD on every socket-outlet are the two halves of the same defence. One without the other leaves a real gap.

07 · Special Installation

Cable Management and Routing

Section 709 is unusually specific about wiring systems. Regulation 709.521.1.4 lists what is suitable for marina distribution circuits; Regulation 709.521.1.5 then bans four of them from the pontoon itself. Getting the second list wrong is a common EICR observation.

Suitable for distribution circuits (709.521.1.4)Shall not be used on or above a jetty, wharf, pier or pontoon (709.521.1.5)
Underground cablesCables in free air suspended from or incorporating a support wire — for example installation methods 35 and 36 in Table 4A2
Overhead cables or overhead insulated conductorsNon-sheathed cables in cable management systems
Copper conductors with thermoplastic or elastomeric insulation and sheath, in an appropriate cable management system chosen for movement, impact, corrosion and ambient temperatureCables with aluminium conductors
Mineral insulated cables with an outer covering to BS EN 60702-1Mineral insulated cables
Cables with armouring and serving of thermoplastic or elastomeric material — the SWA family
Other cables and materials no less suitable than the above

Note the trap in row four: mineral insulated cable with an outer covering is expressly suitable for a marina distribution circuit, and expressly prohibited on or above the pontoon. Aluminium conductors are out on the pontoon regardless of termination method.

Routing, movement and drainage

  • Movement (Reg 709.521.1.6). Cables must be selected and installed so that mechanical damage due to tidal and other movement of floating structures is prevented. Where pontoon sections are joined, the crossing needs enough slack and flexibility to take the movement; a rigid route will work-harden and fracture.
  • Drainage (Reg 709.521.1.6). Cable management systems must be installed to allow water to drain, by drainage holes and/or by installing the equipment on an incline. A trunking run that holds water is a defect, not a detail.
  • Underground (Reg 709.521.1.7). Bury deep enough to avoid damage from, for example, heavy vehicle movement, unless additional mechanical protection is provided. The note gives 0.5 m as the depth generally considered a minimum.
  • Overhead (Reg 709.521.1.8). All overhead conductors must be insulated, at least 6 m above ground in any area subject to vehicle movement and 3.5 m elsewhere, with poles and supports sited or protected against foreseeable vehicle movement.
  • The boat tail. The flexible lead from pillar to craft is H07RN-F with CEE plug and connector. It must not trail in the water; hooks or guides on the pontoon edge keep it above the waterline. Cracked sheaths, exposed conductors and corroded pins take a cable out of service.

08 · Special Installation

Inspection and Testing of Marina Installations

BS 7671 sets no fixed interval. Regulation 652.1 requires the frequency of periodic inspection and testing to be determined having regard to the type of installation and equipment, its use and operation, the frequency and quality of maintenance, and the external influences to which it may be subjected — taking account of the results and recommendations of previous certificates and condition reports. Applied to a marina, every one of those factors points the same way, and industry practice settles on a maximum of one year.

Annual

Full EICR of the fixed installation, with RCD, earth electrode and insulation resistance testing.

Monthly

Visual checks of pillars, cables and connections; RCD test-button operation.

After storms

Inspection after any flooding, extreme tide or severe weather event.

  • Annual EICR. Periodic inspection and testing under Chapter 65, with specific attention to Section 709: insulation resistance, RCD verification to Regulation 643.8, earth electrode resistance, earth fault loop impedance, and visual inspection of every enclosure, cable route and connection. Regulation 653.1 requires an Electrical Installation Condition Report based on the model in Appendix 6.
  • Monthly visual inspection. Supply pillars for physical damage, water ingress, corrosion and loose connections; supply cables for damage; RCD test buttons; earth electrode connections for corrosion.
  • After severe weather. Storms, flooding and extreme tides move pontoons and stress everything crossing a joint. A visual inspection afterwards is not optional in practice.

Observations should cite Section 709 by regulation. The recurring ones on marina EICRs are shared rather than individual RCDs (709.531.2), a socket-outlet protective conductor connected to a PME earthing facility (709.553.1.14), IP integrity lost through damaged enclosures or missing glands (709.553.1.8 and 709.512.2.1.1), prohibited wiring systems on the pontoon (709.521.1.5), and corroded earth electrode connections.

Elec-Mate simplifies marina EICR documentation — record all test results on site using voice entry, let the AI flag Section 709 non-compliance, and send the completed EICR to the marina operator before you leave.

In the app

Complete marina EICRs on your phone

Elec-Mate handles special installations including Section 709 marinas. AI board scanner, voice test entry, automatic observation code classification…

Frequently Asked Questions About Marina Electrical Installations

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-day free trial

Certify Special Installations on Your Phone

Join 1,000+ UK electricians using Elec-Mate for digital certificates, AI fault diagnosis, and BS 7671 calculators. Handles special installations including marinas. 7-day free trial.

Start your free trial

From £6.99/mo after the trial — no charge until day 8.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in one tap — no calls, no hassle
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play
Certificate types
16Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy