METHOD STATEMENT

Method Statement for Electrical Fault Finding — UK Procedure

A working method statement for diagnosing electrical faults in occupied and operational UK installations. Covers the systematic dead-first diagnostic sequence, the narrow EAWR 1989 Regulation 14 justification for any live testing that follows, GS38-compliant instruments, PPE, documentation duties and the EICR observation outcomes (C1 / C2 / FI) that a fault-finding visit can generate.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

12 min readUpdated 2026-05-18Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Fault finding is high-risk because the defect mode is unknown at the start, so the method statement must assume the worst-case hazard until ruled out by inspection and test.
  • 2The default sequence is dead: gather symptoms, visually inspect, isolate, prove dead, then carry out continuity and insulation resistance tests under safe isolation before any live work is considered.
  • 3Live testing (voltage, Zs, RCD operating times, prospective fault current) is only justified under the Electricity at Work Regulations 1989 Regulation 14 "three-test" principle when the result genuinely cannot be obtained dead and the work is reasonable in the circumstances.
  • 4All test instruments and probes must be GS38-compliant, in date for calibration and confirmed working using a known live source or proving unit before and after each test sequence.
  • 5Working in occupied premises requires customer/tenant briefing, isolation planning that respects the occupier (lighting, heating, medical equipment, refrigeration) and a method for managing intermittent or repeat-visit faults.
  • 6Findings that reveal a live defect (broken CPC, lethal voltage on metalwork, exposed conductors) escalate to an EICR C1 or C2 with immediate make-safe action — fault finding does not pause for paperwork when danger is present.
01 · Method Statement

Scope of Work and Fault-Finding-Specific Risks

This method statement covers diagnostic fault-finding work on UK fixed electrical installations — domestic, commercial and light industrial — up to 1000 V AC. It applies to circuits supplied from a TN-S, TN-C-S (PNB) or TT system. It does not cover utility-side faults, HV work, or work on equipment where the manufacturer mandates a specific procedure.

Fault finding carries a different risk profile to a planned installation or a routine EICR. Five hazards dominate the method statement:

  • Unknown defect mode — the operative arrives without knowing whether the fault is a loose connection, a damaged cable, a failed protective device, a borrowed neutral or an exposed live conductor. The plan must assume the most dangerous credible cause first.
  • Testing partially-live installations — diagnosing whether a defect is dead or live often requires the supply to remain on for the initial symptom check, increasing exposure to live parts before any isolation can be performed.
  • Working in occupied premises — customers, tenants, staff, children and pets may be in the area; loss of power affects heating, lighting, fridges, medical equipment, fire alarm panels, cash tills and ICT systems.
  • Intermittent faults — symptoms may not be reproducible on the visit. Operatives may be tempted to leave the circuit live "to see if it recurs", which conflicts with EAWR 1989 unless properly justified.
  • Repeat testing under stress — multiple cycles of isolate, test, re-energise, retest increase the risk of an isolation step being missed. Each cycle must be treated as a fresh isolation per the safe isolation procedure.

When fault finding becomes an EICR

If a fault-finding visit uncovers a defect that meets BS 7671 / IET GN3 criteria for C1 (Danger Present), or one that cannot be diagnosed without further inspection (FI), the operative records the observation, makes safe, and escalates — even if no formal EICR was scoped.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

03 · Method Statement

Competence, PPE and Equipment

Fault finding shall only be carried out by an electrically competent person — typically a qualified electrician with current C&G 2391 (or equivalent) Inspection and Testing experience, registered with a Part P scheme provider (NICEIC, NAPIT, ELECSA, SELECT or equivalent). A second competent person is required where the assessed risk warrants it.

  • Voltage indicator — two-pole, fused, GS38-compliant, used with a proving unit (or known live source) immediately before and after each isolation, per the safe isolation procedure.
  • Multifunction tester (MFT) — in calibration (annually), with current test certificate available on request. Covers continuity, insulation resistance (250 V / 500 V / 1000 V), Zs, PFC and RCD operating time.
  • Insulated tools rated to at least 1000 V (BS EN 60900), in good condition, free of cracked or contaminated handles.
  • Insulated gloves rated and tested (where live work is justified), arc-rated face shield, flame-retardant clothing where assessed risk warrants.
  • Personal protective insulating mat where live work is unavoidable on a panel mounted at floor level.
  • Lock-off devices (one per padlock, padlocks unique to the operative), warning labels, "do not switch on" notices.
  • Torch (head torch preferred for hands-free work), thermal imaging camera where loose-connection / overheating faults are suspected.
  • Calibrated digital meter for current and voltage measurement under live conditions where the MFT cannot provide the reading.
04 · Method Statement

Systematic Fault-Finding Procedure

The method follows the IET GN3 / On-Site Guide diagnostic order: information, inspection, isolation, dead testing, then — only where justified — live testing. Working through this sequence in order minimises the time spent in proximity to live parts.

  1. Gather symptoms from the duty holder / occupier — when the fault appeared, what was happening at the time, what has been switched, whether the RCD/MCB tripped or the circuit just stopped working, whether the fault is intermittent.
  2. Review available documentation — previous EICR, last EIC or Minor Works for the affected circuit, schedule of test results, any known modifications. An old EICR observation often points straight at the defect.
  3. Conduct a non-intrusive visual inspection of the consumer unit, accessible accessories on the affected circuit and any visible cable runs. Look for: discolouration, scorch marks, melted plastic, water staining, rodent damage, missing covers, exposed conductors, evidence of DIY work.
  4. Plan isolation — identify the correct point of isolation, agree with the occupier what circuits will be affected and for how long, and assess any safety-critical loads (fire alarms, medical equipment, ICT, refrigeration). Issue advance notice where reasonably practicable.
  5. Isolate at the lowest practicable level (single MCB, RCBO, or whole circuit) and prove dead following the full safe isolation sequence: test voltage indicator on known live, test point of work, test voltage indicator on known live again. Lock off and label.
  6. Conduct dead tests in the BS 7671 / GN3 order: (a) continuity of protective conductors (R1 + R2 or R2), (b) ring final circuit end-to-end continuity if applicable, (c) insulation resistance line-to-line, line-to-neutral, lines-to-earth at 500 V DC (250 V where electronics are present), (d) polarity. Record every reading.
  7. Compare readings against design data and previous certificate values. Anomalies (an R2 that has doubled, an IR that has dropped from >299 MΩ to 0.2 MΩ) localise the fault.
  8. If the fault is now diagnosed dead, restore as much of the installation as can safely be energised, complete the make-good work under safe isolation, and re-test.
  9. If — and only if — the fault cannot be diagnosed dead, document the EAWR 1989 Regulation 14 justification, brief the second person where required, energise the supply under controlled conditions and carry out live tests: voltage, prospective fault current, earth fault loop impedance, RCD operating times.
  10. Capture all readings, photographs of the defect, and the diagnosis on the digital report. Issue a remedial quote or, where the work has been completed during the visit, issue a Minor Works Certificate or EIC for the new/altered circuit.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
05 · Method Statement

When Fault Finding Requires Live Work

Some diagnostic results — earth fault loop impedance (Zs), prospective fault current (PFC), RCD operating times under in-service conditions, supply voltage measurement at the point of utilisation — can only be obtained with the circuit energised. EAWR 1989 Regulation 14 accepts this in principle, but every live test must be justified, recorded and time-boxed.

  • Justification must be specific to the test — "I need a live Zs reading to compare against the design value to confirm the protective device will operate in disconnection time." Not generic.
  • Live work is carried out by a competent person, with a second competent person where the assessed risk warrants (working inside an energised distribution board, working above 230 V, working where contact with live parts is reasonably foreseeable).
  • GS38 probes only — finger barriers, exposed metal limited to specification, fused leads to limit prospective fault current at the probes.
  • Personal protective equipment (PPE) selected for the assessed arc flash and shock risk — minimum: insulated gloves (tested in date), face shield, FR clothing on enclosed equipment.
  • No live work where the test result is non-essential or could be obtained from a stored value (e.g. PFC from utility data, Zs from a maximum permitted value table when only confirming compliance not diagnosing fault).
  • See the dedicated live working method statement and working-near-live-mains hazard control for the controls that apply to the live portion of the visit.

Intermittent faults are not justification for leaving live

A fault that has not recurred during the visit is an FI (Further Investigation) outcome — not a reason to leave the circuit energised and unmonitored. Where the fault cannot be reproduced, document the symptoms, recommend a return visit with data-logging, and isolate the circuit if the diagnosed risk is high.

06 · Method Statement

Working in Occupied Premises

Almost all UK domestic and small commercial fault finding happens with the occupier present. The method statement must address occupier safety, business continuity and consent to isolate.

  • Brief the occupier on arrival — what the diagnostic process will involve, expected duration, which parts of the installation will be without power and for roughly how long.
  • Identify safety-critical loads before isolating — telecare alarms, oxygen concentrators, refrigerated medication, fire alarm panels in HMOs, emergency lighting, cash tills, ICT servers. Plan around them or warn before interruption.
  • Where children, vulnerable adults or animals are present, set a physical barrier around the workspace (consumer unit, accessory being worked on) — fault finding often involves leaving covers off temporarily.
  • Do not leave the supply restored to a known defective circuit while leaving the property unattended. If the diagnosis is incomplete at the end of the visit, isolate and lock off the affected circuit and brief the occupier.
  • Photograph any C1 condition or C2 condition before make-safe work, then again after, and retain the photographs against the report record.
07 · Method Statement

Documentation and EICR Outcomes

A fault-finding visit produces one or more of: a Minor Works Certificate (where a defect is repaired during the visit), an Electrical Installation Certificate (where a circuit has been replaced), an EICR observation (where the wider installation has been assessed) or an FI flag (where the diagnosis is incomplete). Whichever the outcome, the operative records the diagnostic findings against the customer record.

  • Every test reading captured at the point it was taken — not reconstructed from memory at the van. Digital tools (such as Elec-Mate) tie readings to the circuit, board and timestamp automatically.
  • Photographs of the defect before and after remedial work, geo-tagged where possible, retained against the job.
  • Customer brief — written record of what was diagnosed, what was repaired, what remains outstanding, and any recommendation for a return visit.
  • Where a C1 condition is found and made safe under isolation rather than repaired in full, the record includes the make-safe action, the time it was performed, who was notified, and the recommended follow-up.
  • Where an FI outcome is recorded, the record includes what investigation would resolve the uncertainty (data-logging, withdrawal of equipment for bench test, dismantling of fitting).
  • Minor Works Certificate or EIC issued for any new or altered circuit before the operative leaves site — not at the end of the week.

Make-safe always beats a perfect record

If a hazard is present and the choice is between completing paperwork to perfection or making safe immediately, make safe first. The paperwork can be finalised in the van. The danger cannot wait.

How to work through a fault-finding visit

A six-step working sequence aligned to IET GN3, the On-Site Guide and EAWR 1989. Use this as the checklist on the day and the audit trail afterwards.

1

Plan and brief

Receive the symptom report, review previous certificates, identify safety-critical loads in the property and agree the diagnostic window with the occupier. Confirm the second-person requirement based on the assessed risk.

2

Inspect non-intrusively

Walk the affected circuit, the consumer unit and any accessible accessories looking for visible defects — discolouration, scorch marks, exposed conductors, water ingress, DIY interventions — before opening any enclosure.

3

Isolate and prove dead

Identify the correct point of isolation, switch off, lock off, label, and prove dead with a GS38-compliant voltage indicator tested on a known live source immediately before and after the test at the point of work.

4

Carry out dead tests

Run the BS 7671 dead test sequence in order: continuity of protective conductors, ring final continuity (where applicable), insulation resistance at the appropriate test voltage, polarity. Record each reading against the circuit.

5

Live test where justified

Document the EAWR 1989 Regulation 14 justification, brief the second person, energise under controlled conditions and carry out only the live tests that cannot be obtained dead — typically Zs, PFC and RCD operating times.

6

Make safe, record and certify

Make the defect safe — repair where possible, isolate and lock off where not — capture all readings and photographs against the job, issue the appropriate certificate (Minor Works / EIC) or EICR observation code, and brief the occupier on outstanding work.

Frequently asked questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Generate a fault-finding RAMS in minutes

Elec-Mate's RAMS Generator produces a job-specific risk assessment and method statement for fault-finding visits, with EAWR 1989, BS 7671:2018+A4:2026 and GS38 referenced automatically. Pair it with the digital EICR tool to capture observations on the spot. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy