OUTBUILDING SUPPLY GUIDE

Outbuilding Electrical Supply: Garage, Shed, and Workshop

Supplying an outbuilding with electricity requires the right cable route (SWA underground or overhead at minimum 3.5m — 6m where vehicles pass), a consumer unit in the outbuilding, correct TT earthing, and RCD protection at both ends. This guide covers every aspect of outbuilding electrical supply.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

12 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

What do I need to supply electricity to an outbuilding?

Supplying a detached outbuilding usually means a buried steel-wire-armoured (SWA) cable from the house, its own small consumer unit in the outbuilding, RCD protection, and careful attention to earthing — a TT arrangement with a local earth electrode is often used rather than exporting a PME earth to a building with extraneous-conductive-parts. The circuit is sized for the outbuilding load, and the work is designed, tested and certified to BS 7671.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1An outbuilding supply requires a dedicated circuit from the main dwelling consumer unit — either via buried armoured cable (SWA) at 0.5m depth in gardens, or overhead cable at minimum 3.5m clearance (6m over driveways and vehicle movement areas — BS 7671 Reg 709.521.1.8).
  • 2Overhead cable spans must account for wind loading and mechanical tension — catenary wire support is required for spans over approximately 3m.
  • 3The outbuilding should have its own consumer unit, providing local overcurrent protection, isolation, and RCD protection for all circuits within the outbuilding.
  • 4Where the outbuilding supply is a TT system (no metallic earth connection from the main building), an earth electrode is required at the outbuilding and the circuit must be RCD protected.
  • 5All outbuilding electrical supplies are notifiable under Part P of the Building Regulations, as they involve a new circuit from the dwelling consumer unit.
  • 6BS 7671 Regulation 421.1.7 (A4:2026) recommends arc fault detection devices (AFDDs) for single-phase AC socket-outlet circuits up to 32A — AFDD+RCBO combinations in the outbuilding consumer unit address both the fire risk (arc fault) and earth leakage protection requirements in one device.
01 · Outbuilding Supply Guide

Outbuilding Electrical Supply: Options and Considerations

Supplying electricity to a detached garage, shed, summerhouse, home office, or workshop is one of the most common domestic electrical jobs. The installation must comply with BS 7671 for the cable routing, earthing, and protection arrangements, and is notifiable under Part P of the Building Regulations.

The two primary routes for the supply cable from the dwelling to the outbuilding are underground (buried armoured cable) and overhead (catenary-supported cable). The choice depends on the distance, ground conditions, obstacles, and aesthetic preferences. Underground is the preferred option for most domestic installations because it is hidden, protected from UV degradation and storm damage, and does not require maintaining clearance heights.

In addition to the supply cable, the installation requires a consumer unit in the outbuilding for local protection and control, appropriate earthing arrangements, and RCD protection at both ends of the supply. Getting these right from the outset saves the customer problems later — particularly as homeowners increasingly use outbuildings as home offices and workshops with significant electrical loading.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Outbuilding Supply Guide

Armoured Cable (SWA) Underground Route

Steel Wire Armoured (SWA) cable buried underground is the standard and preferred method for supplying outbuildings. The armour provides mechanical protection against accidental damage and, when correctly terminated, provides the earth continuity path.

  • Cable selection

    2-core SWA (live, neutral, with armour as earth) or 3-core SWA (live, neutral, dedicated CPC plus armour). 3-core is preferred because it provides a dedicated earth conductor — the armour is then bonded at both ends as an additional earth path but the 3rd core provides the primary CPC. Conductor size depends on the maximum demand of the outbuilding and the cable run length.

  • Burial depth

    Minimum 0.5m in gardens and open ground; 0.45m under paved areas; 0.6m under driveways. Cable tiles (protective tiles placed above the cable) and warning tape at approximately 150mm above the cable are required. Record the cable route with accurate dimensions from fixed reference points on an as-installed drawing.

  • Entry into outbuilding

    The cable enters the outbuilding via a suitable weatherproof entry point — typically a conduit sleeve through the wall or floor, sealed against moisture ingress. The cable should rise inside the outbuilding to the consumer unit via conduit or trunking on the wall to protect it from mechanical damage.

03 · Outbuilding Supply Guide

Overhead Cable Route

Where underground cable is not practical — for example, where the garden is paved and digging would be very disruptive, or where the outbuilding is in a position that makes underground routing difficult — an overhead cable route can be used.

  • Minimum height: 3.5m above ground level

    For areas accessible to pedestrians only. The cable must be at a height where a person cannot reach it and where tall garden equipment (ladder, long-handled tools) is unlikely to contact it.

  • Minimum height: 6m over driveways and vehicle movement areas

    Where vehicles can pass under the cable — including vans, lorries, and delivery vehicles — BS 7671 Regulation 709.521.1.8 requires a minimum height of not less than 6m above ground. If existing support heights cannot achieve this clearance, supports must be relocated or the conductor raised to comply.

  • Catenary wire support

    For spans over approximately 3m, the cable must be supported by a catenary wire (a separate steel wire tensioned between the two buildings) to prevent the cable sagging below the minimum height under its own weight and under wind and ice loading. Self-supporting aerial cables (with a built-in supporting messenger wire) are an alternative that simplifies installation.

Overhead cables are more susceptible to UV degradation and storm damage than buried cables. XLPE-insulated SWA cable or purpose-made aerial bundled cable is suitable for overhead use; PVC-insulated cable degrades faster in UV exposure. Overhead cable routes should be inspected periodically for sag, damage, and vegetation contact.

04 · Outbuilding Supply Guide

Consumer Unit in the Outbuilding

Every outbuilding with a permanent electrical supply should have its own consumer unit. This provides local isolation, overcurrent protection for the outbuilding's circuits, and a convenient point for switching off all power to the outbuilding.

  • Main switch: Double-pole isolating switch rated at the incoming supply current. This provides isolation of all circuits in the outbuilding without returning to the main dwelling.
  • Circuit protection: Individual MCBs or RCBOs for each outbuilding circuit (lighting, socket ring or radial, EV charger if applicable, workshop equipment). RCBOs are preferred for outbuilding installations as they provide individual RCD protection without nuisance tripping affecting other circuits. For workshop and garage socket-outlet circuits, BS 7671 Regulation 421.1.7 (A4:2026) recommends AFDD protection — AFDD+RCBO combination devices are available and address both arc-fault fire risk and RCD requirements in a single device.
  • Enclosure type: Metal consumer units are required for consumer units in dwellings (post-2016 Amendment 4 to BS 7671). For outbuildings that are not classified as dwellings, plastic enclosures are technically permitted, but metal enclosures are recommended for fire containment in all cases.
  • Location: The consumer unit should be mounted in a position that is dry, accessible for maintenance, and not subject to mechanical damage or flooding. It should be within 2m of the incoming cable entry point to minimise unprotected cable length inside the outbuilding.
05 · Outbuilding Supply Guide

Earthing — TT System and Earth Electrode

Earthing is one of the most critical aspects of an outbuilding supply. The earthing arrangement for the outbuilding depends on whether there is a continuous metallic earth connection from the main building.

TN System (Metallic Earth Path)

If the supply cable has a metallic armour (SWA) that is bonded to earth at both ends, and the armour resistance is adequate, the outbuilding can be treated as a TN system. The armour provides the earth fault return path.

  • Earth electrode not mandated (but recommended)
  • Earth fault loop impedance (Zs) must be checked and within limits
  • 30mA RCD protection required for socket-outlet circuits (Reg 411.3.3) and lighting circuits in domestic premises (Reg 411.3.4)

TT System (No Metallic Earth Path)

If the outbuilding earth is not connected to the main building earth via a metallic path (overhead cable without separate earth, or where armour earth path is not relied upon), the outbuilding is a TT installation.

  • Earth electrode mandatory at the outbuilding
  • Electrode resistance measured and compliance confirmed by calculation: Ra × IΔn ≤ 50V (Reg 411.5.3) — for a 30mA RCD this gives a maximum Ra of 1,667Ω
  • RCD protection mandatory for all circuits (not just sockets)

In practice, it is good practice to install an earth electrode at every outbuilding regardless of the earthing system type. This provides an additional earth reference, reduces earth fault loop impedance, and ensures the outbuilding has a reliable earth connection even if the main supply cable earth path develops a fault.

For TT installations, compliance of the earth electrode is confirmed by calculation under BS 7671 Regulation 411.5.3: the electrode resistance Ra (in ohms) multiplied by the RCD rated residual operating current IΔn must not exceed 50V. For a 30mA RCD this gives a maximum permissible Ra of 1,667Ω — confirming that compliance depends on the RCD rating selected, not a fixed resistance target. Record the measured Ra on the EIC schedule of test results.

Record earth electrode test results on site

Elec-Mate's EIC Certificate app includes earth electrode resistance recording in the test results schedule.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · Outbuilding Supply Guide

RCD Protection Requirements for Outbuildings

RCD protection is required at two levels for outbuilding supplies:

  • At the main consumer unit (source protection)

    The outbuilding supply circuit at the main consumer unit should be connected to an RCD-protected way — either an RCBO in the main consumer unit, or an RCD section with the outbuilding circuit MCB on the protected side. This protects the supply cable from the main building to the outbuilding.

  • At the outbuilding consumer unit (local protection)

    All circuits within the outbuilding must be individually RCD protected at 30mA. For TT system installations, this is a mandatory requirement under BS 7671 Regulation 411.5. For TN system installations, 30mA RCD protection is required for all socket-outlet circuits (rated ≤32A) under Regulation 411.3.3 — there is no documented-risk-assessment exception where the outbuilding is ancillary to a dwelling. Regulation 411.3.4 (A4:2026) separately mandates 30mA RCD additional protection for AC lighting circuits in domestic premises, so outbuilding lighting circuits also require 30mA RCD protection where the outbuilding serves a domestic dwelling. Using RCBOs for each outbuilding circuit is best practice — it provides selective protection so that a fault on one circuit does not de-energise the whole outbuilding.

07 · Outbuilding Supply Guide

Part P Notification for Outbuilding Supplies

An outbuilding supply is notifiable under Part P of the Building Regulations in England because it involves a new circuit from the dwelling consumer unit. This applies to:

  • New supply to a detached garage
  • New supply to a garden shed or workshop
  • New supply to a summerhouse or garden office
  • Upgrading or extending an existing outbuilding supply circuit

Register with an approved competent person scheme to self-certify and issue the Electrical Installation Certificate on site. The certificate should cover the supply circuit from the main consumer unit to the outbuilding consumer unit, with a separate schedule for the outbuilding internal circuits. Include the earth electrode resistance test result if a TT earth system is used.

08 · Outbuilding Supply Guide

For Electricians: Outbuilding Supply in Practice

Outbuilding supply jobs are excellent revenue opportunities. A properly specified outbuilding supply — correct cable sizing, TT earthing, RCBOs per circuit, metal consumer unit, and professional certification — demonstrates expertise and commands a professional price.

Cable Sizing and Voltage Drop

Long cable runs to remote outbuildings cause voltage drop. Use the cable sizing calculator to confirm the SWA cable size meets both current-carrying capacity and voltage drop requirements for the run length.

EIC Certificate on Site

Issue your Electrical Installation Certificate for the outbuilding supply on site before you leave. Include all test results — continuity, IR, polarity, Zs, RCD operation, and earth electrode resistance.

Frequently Asked Questions About Outbuilding Electrical Supply

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Certificate Outbuilding Supplies On Site

Elec-Mate lets UK electricians complete EICs for outbuilding supply installations on their phone. Cable sizing, voltage drop, and certification — all in one app. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy