ESSENTIAL GUIDE

RCD Types Explained
Type AC, A, B, F — Which Do You Need?

Choosing the wrong RCD type leaves circuits unprotected. This guide explains every RCD type in detail — what each detects, where each is required by BS 7671, and how to select the right type for every circuit. From standard domestic installations to EV chargers and heat pumps.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

17 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Type AC detects only sinusoidal AC faults and is no longer suitable for most modern circuits. Type A (AC + pulsating DC) is now the standard for domestic and commercial installations under BS 7671 Regulation 531.3.3.
  • 2Type B RCDs detect smooth DC faults and are required for EV chargers without built-in DC detection, three-phase VFDs, and some solar PV inverters. Significantly more expensive (£150-£300) than Type A (£25-£50).
  • 3Type F RCDs protect against mixed-frequency faults from single-phase VFDs — used in heat pumps, inverter-driven air conditioning, and washing machines with variable-speed motors.
  • 4A4:2026 Regulation 411.3.4 (NEW): 30mA RCD protection is now mandatory for ALL domestic AC lighting circuits — any new or rewired domestic lighting circuit requires an RCBO or 30mA RCD. Unprotected lighting circuits are an EICR defect.
  • 530mA RCDs provide personal protection against electric shock. Regulation 411.3.3 applies to socket-outlets ≤32A; Regulation 411.3.4 (A4:2026) separately mandates 30mA protection for domestic luminaire circuits. 100mA and 300mA RCDs provide fire protection only.
  • 6Elec-Mate EICR and EIC forms capture RCD type for every circuit. The board scanner reads RCD/RCBO labels from photos. Schedule of tests validates trip times against BS 7671 limits.
01 · Essential Guide

Why RCD Type Matters

An RCD (Residual Current Device) detects an imbalance between the current flowing into a circuit through the line conductor and the current returning through the neutral conductor. If some current is leaking to earth — through a person, through damaged insulation, or through a fault — the RCD detects this imbalance and trips, disconnecting the circuit.

However, not all earth leakage currents are the same. Traditional electrical loads (heaters, incandescent lights, kettles) produce pure sinusoidal AC fault currents. But modern electronic equipment — EV chargers, variable-frequency drives, heat pumps, solar PV inverters, washing machines with inverter motors — can produce fault currents with DC components, pulsating waveforms, and mixed frequencies. An RCD designed to detect only sinusoidal AC will not trip on these non-standard fault waveforms, leaving the circuit unprotected.

BS 7671 Regulation 531.3.3 requires that the RCD type is selected with consideration of the waveform of the residual current likely to occur under fault conditions. This means the electrician must consider what equipment will be connected to each circuit and select an RCD type capable of detecting the fault currents that equipment could produce. Getting this wrong is not just a compliance issue — it is a safety issue that could result in a fatal electric shock or an undetected fire.

The four main RCD types are defined in BS EN 62423, and each has a specific symbol that is printed on the device front plate. Understanding these symbols and their meaning is fundamental to specifying and inspecting RCD protection.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Essential Guide

Type AC — Sinusoidal AC Faults Only

AC

Type AC RCD

Detects: Sinusoidal AC residual currents only (pure 50Hz waveform).

Symbol: A sine wave (~) printed on the device front plate.

Type AC is the most basic type of RCD. It detects and responds to sinusoidal AC residual currents — the type of fault current produced by simple resistive loads such as heaters, incandescent lights, and immersion heaters. It was the standard RCD type for decades and is still found in many existing installations.

However, Type AC cannot detect DC components in the fault current. Modern electronic equipment with rectifiers (diodes) can produce pulsating DC fault currents or smooth DC fault currents. If these DC components flow through the toroidal core of a Type AC RCD, they can saturate the core, reducing its sensitivity to AC faults as well. This means a Type AC RCD on a circuit supplying electronic equipment could fail to trip on any type of fault — AC or DC.

Type AC Is No Longer Suitable for Most Circuits

BS 7671 Regulation 531.3.3 effectively makes Type AC unsuitable for most circuits in modern installations because virtually every circuit now supplies equipment that could produce non-sinusoidal fault currents — LED lighting, electronic thermostats, USB charging outlets, modern appliances. Type A is the minimum standard for new installations.

If you find Type AC RCDs during an EICR inspection, they are not automatically a defect — they were compliant when installed. However, if the circuits they protect now supply electronic equipment (which is almost always the case), consider recommending an upgrade to Type A as a C3 (Improvement Recommended) observation.

03 · Essential Guide

Type A — AC + Pulsating DC (The Standard)

A

Type A RCD

Detects: Sinusoidal AC residual currents AND pulsating DC residual currents.

Symbol: A sine wave with a pulsating DC waveform below it, printed on the device front plate.

Type A is now the standard RCD type for the vast majority of domestic and commercial circuits. It detects all the fault waveforms that Type AC can detect (pure sinusoidal AC) plus pulsating DC residual currents — the type of fault current produced by equipment with single-phase rectifier circuits.

Pulsating DC fault currents are produced by any equipment that converts AC to DC using a half-wave or full-wave rectifier — which includes virtually every piece of modern electronic equipment: computers, laptop chargers, phone chargers, LED drivers, washing machine and dishwasher controllers, modern boiler controls, EV chargers in Mode 2, and many more. When a fault develops in this equipment, the fault current has a DC component that Type AC cannot detect.

BS 7671 Regulation 531.3.3 states that the type of RCD shall be selected based on the waveform of residual current likely to occur. Since almost every modern circuit supplies equipment with rectifiers, Type A is the minimum appropriate type for virtually all circuits. In practice, if you are installing a new consumer unit or specifying RCBOs for a new installation, Type A should be the default choice.

Type A RCBOs are readily available from all major manufacturers (Hager, Schneider, Siemens, MK, Wylex) at prices ranging from £25 to £50 per device. The cost premium over Type AC is minimal and well worth the additional protection.

04 · Essential Guide

Type B — AC + Smooth DC (For EV Chargers & VFDs)

B

Type B RCD

Detects: Sinusoidal AC, pulsating DC, AND smooth (pure) DC residual currents.

Symbol: A sine wave, a pulsating DC waveform, and a smooth DC line, printed on the device front plate.

Type B RCDs can detect all the fault waveforms that Type A detects, plus smooth (pure) DC residual currents. Smooth DC fault currents are produced by equipment with three-phase rectifiers or specific power electronic circuits — most notably some EV chargers, three-phase variable-frequency drives (VFDs), and certain solar PV inverter topologies.

The most common domestic application for Type B RCDs is EV charger installations where the charger does not have built-in 6mA DC residual current monitoring. BS 7671 Chapter 72 (Electric Vehicle Charging Installations) requires that the RCD protecting an EV charging circuit must be either:

  • Type A + 6mA DC detection — A Type A RCD/RCBO where the charger itself monitors for DC residual currents above 6mA and disconnects. Most modern domestic smart chargers (Zappi, Ohme, Pod Point, Easee) include this built-in DC detection, allowing a standard Type A RCBO to be used.
  • Type B RCD — Required if the charger does not have built-in DC detection. The Type B RCD detects the smooth DC fault currents directly, without relying on the charger electronics.

Type B RCDs are significantly more expensive than Type A devices — typically £150 to £300 compared to £25 to £50 for a Type A RCBO. This cost difference is why most EV charger manufacturers now build 6mA DC detection into their chargers, allowing the cheaper Type A option.

In commercial and industrial installations, Type B RCDs are required for circuits supplying three-phase VFDs, some welding equipment, and certain medical devices where smooth DC fault currents are possible.

EV Charger Certificate Specifies RCD Type

Elec-Mate's EV charger certificate form includes a dedicated field for RCD type selection — Type A with 6mA DC detection or Type B.

Try it free for 7 days
Download on the App StoreGet it on Google Play
05 · Essential Guide

Type F — For VFDs and Heat Pumps

F

Type F RCD

Detects: All Type A faults PLUS composite residual currents containing mixed frequencies from single-phase VFDs.

Symbol: The Type A symbol with an additional frequency symbol, printed on the device front plate.

Type F is a relatively new RCD type, defined in BS EN 62423, that fills a specific gap between Type A and Type B. It is designed for circuits supplying equipment with single-phase variable-frequency drives (VFDs) — also called inverters or variable-speed drives.

Single-phase VFDs are increasingly common in domestic and light commercial equipment:

  • Heat pumps — Air source and ground source heat pumps use VFDs to control compressor speed for optimal efficiency. A fault in the VFD can produce mixed-frequency residual currents that Type A cannot detect reliably.
  • Air conditioning units — Modern inverter-driven air conditioning uses the same VFD technology as heat pumps and produces the same types of fault current.
  • Washing machines with inverter motors — Premium washing machines from manufacturers such as Samsung, LG, and Bosch use direct-drive inverter motors instead of traditional induction motors.
  • Pool and spa pumps — Variable-speed pool pumps use VFDs for energy-efficient operation at different flow rates.

The residual currents produced by single-phase VFDs are complex — they contain DC components, pulsating components, and high-frequency components mixed together. A Type A RCD may not reliably detect these composite fault currents because the complex waveform can partially saturate the toroidal core in unpredictable ways. A Type B RCD would work but is unnecessarily expensive. Type F provides the specific detection capability needed for these fault waveforms at a cost between Type A and Type B (typically £60 to £100).

When specifying circuits for heat pump installations, always check the heat pump manufacturer's requirements — many now specify Type F or Type B RCD protection as a condition of their warranty.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · Essential Guide

RCBO vs RCD + MCB

There are two ways to provide RCD and overcurrent protection for a circuit: an individual RCBO (Residual Current Breaker with Overcurrent protection) for each circuit, or a shared RCD protecting a group of circuits with individual MCBs (the split-load arrangement).

RCBO (Per Circuit)

  • Excellent discrimination — A fault on one circuit trips only that circuit. Every other circuit remains energised and unaffected.
  • No cumulative leakage issues — Each RCBO monitors only its own circuit, eliminating nuisance tripping from combined standing leakage currents.
  • Easy fault diagnosis — When an RCBO trips, you know immediately which circuit has the fault.
  • Higher cost — Individual RCBOs cost more than MCBs. A full RCBO board costs approximately £60 to £150 more than a split-load equivalent.

RCD + MCBs (Split-Load)

  • Lower initial cost — Two RCDs and individual MCBs cost less than individual RCBOs for every circuit.
  • Poor discrimination — A fault on any circuit trips the shared RCD, disconnecting every circuit on that side of the board.
  • Cumulative leakage risk — The combined standing leakage from all circuits sharing one RCD can cause nuisance tripping, especially on larger installations.
  • Harder fault diagnosis — When the shared RCD trips, you must isolate circuits one by one to identify the faulty circuit.

For new domestic installations and consumer unit replacements, full RCBO boards are now the preferred choice among professional electricians. The additional cost is easily justified by the improved discrimination, reduced nuisance tripping, and better fault diagnosis. The time saved in call-backs alone often pays for the cost difference.

Board Scanner Reads RCD/RCBO Labels from Photos

Take a photo of any consumer unit and Elec-Mate's AI board scanner reads the RCD and RCBO labels — identifying the manufacturer, type (AC, A, B, or F)…

Try it free for 7 days
Download on the App StoreGet it on Google Play
07 · Essential Guide

30mA vs 100mA vs 300mA — Which Rating?

RCDs are manufactured with different rated residual operating currents (IΔn) for different protection purposes. The three most common ratings serve fundamentally different functions and are not interchangeable.

30mA

Personal Protection

Provides additional protection against electric shock. The 30mA threshold is below the level that causes ventricular fibrillation in most adults (approximately 50mA for prolonged exposure). Two separate A4:2026 regulations mandate 30mA protection:

  • Reg 411.3.3 — socket-outlets with a rated current not exceeding 32A. Exception: in non-dwellings a documented risk assessment may permit omission; this exception does NOT apply to dwellings.
  • Reg 411.3.4 (A4:2026 — NEW) — all AC final circuits supplying luminaires within domestic (household) premises. No risk-assessment exception; this is a mandatory 'shall' requirement for every domestic lighting circuit.

100mA

Fire Protection

Provides fire protection by detecting earth leakage currents that are too small to trip an MCB but large enough to generate heat. Often used as the main switch RCD in a split-load board or as a time-delayed upstream device for discrimination. Not suitable for personal protection against electric shock.

300mA

Fire Protection (High Leakage)

Fire protection for larger installations where cumulative earth leakage from multiple equipment items would cause nuisance tripping of a 100mA device. Required by Regulation 422.3.9 for installations in locations with a risk of fire. Not suitable for personal protection.

A4:2026 New Requirement — Domestic Lighting Circuits (Reg 411.3.4)

BS 7671:2018+A4:2026 Regulation 411.3.4 introduces a new mandatory requirement: within domestic (household) premises, additional protection by an RCD with a rated residual operating current not exceeding 30mA shall be provided for all AC final circuits supplying luminaires. This is distinct from Regulation 411.3.3 (socket-outlets) — there is no risk-assessment exception for lighting circuits in domestic premises.

Practical implication: Any new or rewired domestic lighting circuit requires an RCBO or a shared 30mA RCD. Existing domestic lighting circuits without 30mA RCD protection are an EICR defect against the current edition of BS 7671. This is the single most significant A4:2026 change affecting RCD specification on domestic installations.

The golden rule: where BS 7671 requires 30mA additional protection, you cannot substitute a higher-rated device. A 100mA RCD does not provide personal protection — a person receiving a 100mA shock for the 300ms trip time of the RCD is at serious risk of ventricular fibrillation.

TT Systems — RCD as Primary ADS

On TT earthing systems (common in rural properties, outbuildings, and older domestic installations), an RCD is not just additional protection — it is the primary means of automatic disconnection of supply (ADS). Because the earth fault loop impedance in a TT installation is dominated by the resistance of the earth electrode, it is typically too high for overcurrent devices (MCBs, fuses) to achieve the disconnection times required by BS 7671 Table 41.1. Per OSG Regulation 3.76, RCDs shall be provided in TT systems since high earth fault loop impedance to earth electrodes often prevents achieving disconnection by overcurrent devices alone. A 30mA RCD on a TT system permits a maximum Zs of 1,667Ω (per BS 7671 Table 41.5); a 100mA RCD reduces this to 500Ω. Confirm the earthing system before selecting RCD ratings on any installation.

08 · Essential Guide

Time-Delayed RCDs (Type S / Selective)

A time-delayed RCD, marked as Type S (for selective), has a built-in delay before it trips. The purpose is to achieve discrimination (selectivity) between RCDs installed in series, ensuring that only the device closest to the fault trips.

Consider a consumer unit with a 100mA Type S RCD as the main switch and individual 30mA RCBOs on each circuit. If an earth fault occurs, the 30mA RCBO on the faulty circuit should trip first. The 100mA Type S main switch should not trip because: (a) it is less sensitive (100mA vs 30mA), and (b) its deliberate time delay means the downstream device has time to trip first.

Trip Times for Time-Delayed (Type S) RCDs

At 1x IΔn130ms to 500ms (must trip within this range)
At 5x IΔn50ms to 200ms (must trip within this range)

Compare these with non-delayed RCDs: 300ms maximum at 1x IΔn and 40ms maximum at 5x IΔn. The Type S device has a wider time band that accommodates the intentional delay.

When testing Type S RCDs during an EICR, make sure your test instrument is set to the correct mode (Type S or selective). Testing a Type S device in non-delayed mode will give trip times that appear to exceed the standard limits, potentially leading you to fail a device that is actually performing correctly.

GN3 Field Protocol — Recording RCD Trip Times

GN3 (Guidance Note 3: Inspection & Testing) Regulation 2.32 requires that RCDs are tested at both 0% and 180% of rated residual operating current (IΔn). The longest trip time observed across both tests shall be recorded in column 28 of the Schedule of Test Results. Example: if the RCD trips in 80ms at 180% and 120ms at 0%, record 120ms.

Type B RCDs: GN3 Regulation 5.6 notes that carrying out the full suite of optional tests for a 30mA Type B RCD may require up to 12 trip operations. Plan the test sequence carefully to avoid exhausting mechanical operations during a single inspection.

Schedule of Tests Validates RCD Trip Times

Elec-Mate's schedule of test results validates every RCD trip time you enter against the correct BS 7671 limits — automatically distinguishing between…

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Get RCD Type Right Every Time

Elec-Mate captures RCD types on every certificate, validates trip times against BS 7671, and scans board labels from photos. Join 1,000+ UK electricians. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

Cookie Preferences

Manage your privacy settings

We use cookies to enhance your experience and analyse platform usage. Cookie Policy