REGULATION DEEP-DIVE

Regulation 411: Automatic Disconnection of Supply Explained

ADS is the most important protective measure in BS 7671. This guide explains the principle, disconnection times, maximum Zs values for MCB types B/C/D, earthing system differences, practical loop impedance testing, and worked examples.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

18 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Automatic Disconnection of Supply (ADS) is the most widely used protective measure in BS 7671. It relies on a protective device (MCB, fuse, or RCD) disconnecting the circuit fast enough to prevent electric shock when a fault occurs.
  • 2Final circuits not exceeding 32A must disconnect within 0.4 seconds (Regulation 411.3.2.2). Distribution circuits and circuits exceeding 32A must disconnect within 5 seconds (Regulation 411.3.2.3).
  • 3The maximum earth fault loop impedance (Zs) depends on the type and rating of the protective device. A Type B 32A MCB has a maximum Zs of 1.37 ohms at 70 degrees C, while a Type C 32A MCB has a maximum Zs of 0.68 ohms.
  • 4TT systems cannot usually achieve ADS through overcurrent devices alone due to high earth fault loop impedance. An RCD is the standard protective device for TT installations (Regulation 411.5.2).
  • 5Always measure Zs at the furthest point of every circuit during initial verification. Compare the measured value against the maximum tabulated Zs for the protective device — if Zs is too high, the circuit will not disconnect fast enough.
01 · Regulation Deep-Dive

What is Automatic Disconnection of Supply?

Automatic Disconnection of Supply (ADS) is the protective measure described in Section 411 of BS 7671:2018+A4:2026. It is the most commonly applied protection against electric shock in UK electrical installations — virtually every circuit in a domestic or commercial installation relies on ADS.

The principle is straightforward: if a fault occurs that makes an exposed-conductive-part live (for example, a live conductor contacts a metal enclosure), the protective device must disconnect the supply fast enough to prevent a lethal electric shock. ADS is not a single device — it is a combination of earthing, protective conductors, and protective devices working together.

Understanding ADS is essential for every electrician. It determines how you select protective devices, how you size cables, how you design earthing arrangements, and what you test during initial verification and periodic inspection. If ADS fails, the consequence is a sustained touch voltage on metalwork that people can contact — a direct risk to life.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Regulation Deep-Dive

The ADS Principle Explained

Regulation 411.3.1.1 states that ADS requires the coordination of two elements:

  • An earth fault current path — a low-impedance path from the point of the fault, through the protective conductor, back to the source (transformer neutral). This path must have sufficiently low impedance to allow enough fault current to flow to operate the protective device. The total impedance of this path is the earth fault loop impedance (Zs).
  • A protective device that disconnects within the required time — an MCB, fuse, RCBO, or RCD that will operate within the maximum disconnection time specified by BS 7671 for the type of circuit and earthing system. The device must be selected so that the fault current flowing through the Zs path is sufficient to trip it within the required time.

The relationship is governed by Ohm's law. When a line-to-earth fault occurs, the fault current (If) equals the supply voltage (Uo) divided by the earth fault loop impedance (Zs):

If = Uo / Zs

Where Uo = 230V (nominal), Zs = total earth fault loop impedance in ohms

If the fault current (If) is high enough, the MCB or fuse trips within the required time. If Zs is too high, the fault current is too low, the device takes too long to trip, and the person touching the faulty equipment is exposed to a dangerous voltage for too long.

03 · Regulation Deep-Dive

Disconnection Times: 0.4s and 5s Rules

BS 7671 specifies maximum disconnection times in Regulation 411.3.2. The times differ depending on the type of circuit and the earthing system:

0.4 Seconds

Regulation 411.3.2.2 requires a maximum disconnection time of 0.4 seconds for final circuits not exceeding 32A in TN systems. This covers virtually all socket-outlet circuits, lighting circuits, and fixed equipment circuits in domestic and commercial installations. The 0.4-second time is based on the physiological effects of electric shock — at 230V touch voltage, 0.4 seconds is the threshold beyond which the risk of ventricular fibrillation becomes unacceptable.

5 Seconds

Regulation 411.3.2.3 permits a maximum disconnection time of 5 seconds for distribution circuits in TN systems. A distribution circuit supplies one or more distribution boards (sub-mains) rather than directly supplying current-using equipment. The longer time is permitted because the exposed-conductive-parts of distribution circuits are generally not accessible to the general public and because simultaneous contact with earth and a distribution conductor is less likely.

For TT systems, Table 41.1 in BS 7671 specifies a disconnection time of 0.2 seconds for final circuits not exceeding 32A, and 1 second for distribution circuits. These shorter times reflect the higher touch voltages that can occur in TT systems due to the earth electrode resistance.

Summary: Maximum Disconnection Times

SystemFinal circuits up to 32ADistribution circuits
TN-S / TN-C-S0.4s5s
TT0.2s1s
04 · Regulation Deep-Dive

Zs Values and MCB Types (B, C and D)

The maximum earth fault loop impedance (Zs) for a circuit depends on the type and rating of the protective device. BS 7671 Table 41.3 provides maximum Zs values for MCBs to BS EN 60898 and RCBOs to BS EN 61009. The values differ significantly between Type B, C, and D MCBs because of their different magnetic trip thresholds:

MCB Magnetic Trip Ranges

  • Type B — instantaneous trip between 3 and 5 times In. Used for resistive and lightly inductive loads (lighting, socket outlets, electric heating). Highest maximum Zs values because the lowest fault current is needed.
  • Type C — instantaneous trip between 5 and 10 times In. Used for moderately inductive loads (small motors, fluorescent lighting, air conditioning). Lower maximum Zs because a higher fault current is needed to trip magnetically.
  • Type D — instantaneous trip between 10 and 20 times In. Used for highly inductive loads (large motors, transformers, X-ray machines). Lowest maximum Zs because the highest fault current is needed. Rarely used in domestic installations.

Common Maximum Zs Values (0.4s, at 70 degrees C)

RatingType BType CType D
6A7.67 ohms3.83 ohms1.92 ohms
10A4.60 ohms2.30 ohms1.15 ohms
16A2.87 ohms1.44 ohms0.72 ohms
20A2.30 ohms1.15 ohms0.57 ohms
32A1.37 ohms0.68 ohms0.34 ohms
40A1.15 ohms0.57 ohms0.29 ohms

Values from BS 7671 Table 41.3. These are at conductor operating temperature (70 degrees C). When testing at ambient temperature, the measured Zs must not exceed 80% of these values.

The practical impact is significant. A 32A ring final circuit protected by a Type B MCB allows a maximum Zs of 1.37 ohms. If the same circuit were protected by a Type C MCB (which would be unusual for a ring circuit, but illustrates the point), the maximum Zs drops to 0.68 ohms — almost half. This is why Type B MCBs are the standard choice for domestic circuits: they offer the most headroom on earth fault loop impedance.

05 · Regulation Deep-Dive

ADS in TN-S, TN-C-S and TT Systems

The earthing system of the installation has a major impact on ADS. The earth fault loop impedance, the available fault current, and the choice of protective device all depend on whether the installation is TN-S, TN-C-S, or TT.

TN-S (Separate Neutral and Earth)

The supply has a separate earth conductor — typically the lead sheath or steel wire armour of the supply cable. The Ze (external earth fault loop impedance) is typically 0.35 to 0.8 ohms. ADS is straightforward in TN-S systems because the Ze is relatively low and predictable. The main concern is older TN-S supplies where the cable sheath may be deteriorating, increasing Ze over time.

TN-C-S (PME — Protective Multiple Earthing)

The supply neutral and earth are combined in a single PEN conductor, with the neutral earthed at multiple points throughout the network. The Ze is typically very low — 0.2 to 0.35 ohms — giving excellent ADS performance. PME is the most common supply arrangement for new-build domestic properties in the UK. The low Ze means most circuits will achieve ADS with MCBs alone. However, PME carries a specific risk: if the PEN conductor is lost (broken neutral), the installation metalwork can rise to a dangerous potential.

TT (Earth Electrode)

The installation has its own earth electrode — typically a driven rod. There is no metallic return path to the transformer; the fault current returns through the general mass of earth. The Ze is typically 20 to 200 ohms (or more), depending on soil conditions and electrode type. This high impedance means overcurrent devices (MCBs and fuses) cannot achieve ADS alone — the fault current is far too low to trip them within the required time. Regulation 411.5.2 requires an RCD as the protective device in TT systems. A 30mA RCD can achieve ADS with a Zs up to 1667 ohms, making it effective even with very high earth electrode resistance.

When carrying out an EICR, always confirm the earthing system type and measure Ze before assessing individual circuits. The earthing system determines whether ADS by overcurrent device alone is feasible or whether RCD protection is essential.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · Regulation Deep-Dive

Practical Testing with a Loop Impedance Tester

Earth fault loop impedance testing is a core part of both initial verification (Regulation 643.7) and periodic inspection. The test confirms that the Zs at the furthest point of each circuit is within the limits required for ADS.

Testing Procedure

  • Step 1 — Confirm safe to test. Earth fault loop impedance testing is a live test. Confirm that RCDs are in circuit (the test instrument may trip them — use a non-trip earth loop tester if needed, or temporarily bypass the RCD for the test with appropriate precautions).
  • Step 2 — Test at the furthest point. Connect the tester at the furthest point of the circuit. For a ring final circuit, test at each socket outlet — the highest reading is at the mid-point of the ring (the point electrically furthest from the origin in both directions). For a radial, test at the last point.
  • Step 3 — Record and compare. Record the measured Zs. If testing at ambient temperature (which is the normal case), the measured Zs must not exceed 80% of the maximum tabulated Zs (to allow for the conductor resistance increasing at operating temperature). Alternatively, multiply the measured (R1+R2) by the correction factor from Table I1 in the On-Site Guide and add to Ze.
  • Step 4 — Assess compliance. If the measured Zs (corrected for temperature) exceeds the maximum tabulated value, the circuit does not comply with Section 411. Investigate the cause — high R1+R2 (long cable run, undersized conductor), high Ze (supply earth issue), or poor connections.

Record Zs test results digitally

Elec-Mate's schedule of test results auto-validates your Zs readings against the maximum permitted values for the protective device.

Try it free for 7 days
Download on the App StoreGet it on Google Play
07 · Regulation Deep-Dive

Worked Examples

These examples demonstrate how to verify ADS compliance for common domestic circuits.

Example 1: Ring Final Circuit (32A Type B MCB)

Given: Ze = 0.35 ohms (TN-C-S supply). Ring circuit in 2.5mm² T&E, 60m total ring length. R1+R2 per metre from tables = 0.0246 ohms/m (at 20 degrees C).

Calculate R1+R2 for the ring: For a ring circuit, the R1+R2 at the mid-point = (total R1+R2) / 4 = (60 x 0.0246) / 4 = 1.476 / 4 = 0.369 ohms at 20 degrees C.

Correct for operating temperature: Multiply by 1.20 (correction factor for 70 degrees C PVC): 0.369 x 1.20 = 0.443 ohms.

Calculate Zs: Zs = Ze + R1+R2 = 0.35 + 0.443 = 0.793 ohms.

Compare: Maximum Zs for 32A Type B MCB = 1.37 ohms. 0.793 ohms is well within the limit. Circuit complies.

Example 2: Long Radial Circuit (20A Type B MCB)

Given: Ze = 0.72 ohms (TN-S supply, older area). Radial circuit in 2.5mm² T&E, 30m cable run. R1+R2 per metre = 0.0246 ohms/m.

Calculate R1+R2: 30 x 0.0246 = 0.738 ohms at 20 degrees C.

Correct for temperature: 0.738 x 1.20 = 0.886 ohms.

Calculate Zs: 0.72 + 0.886 = 1.606 ohms.

Compare: Maximum Zs for 20A Type B MCB = 2.30 ohms. 1.606 ohms is within the limit. Circuit complies — but with less headroom than Example 1. On a TN-S supply with higher Ze, long cable runs consume more of the available Zs budget.

Example 3: Failing Circuit (32A Type C MCB)

Given: Ze = 0.35 ohms. Ring circuit in 2.5mm² T&E, 60m total ring length. Type C MCB (incorrectly specified for a ring circuit).

Zs at 70 degrees C: 0.35 + 0.443 = 0.793 ohms (same as Example 1).

Compare: Maximum Zs for 32A Type C MCB = 0.68 ohms. 0.793 ohms exceeds the limit. Circuit does NOT comply. The Type C MCB needs a higher fault current to trip magnetically, but the circuit impedance is too high. Solution: change to a Type B MCB (maximum Zs = 1.37 ohms), or add RCD/RCBO protection.

08 · Regulation Deep-Dive

Common ADS Failures and How to Resolve Them

During inspection and testing, these are the most common reasons circuits fail ADS compliance:

  • High Ze on TN-S supplies — older TN-S supplies with deteriorating lead sheath can have Ze values above 0.8 ohms. Combined with long circuit cable runs, Zs can exceed the limit. Solution: contact the DNO to check the supply earth, or add RCD protection to circuits at risk.
  • Long cable runs — each metre of cable adds to R1+R2. Very long radial circuits (particularly in larger properties, outbuildings, or agricultural installations) can result in high Zs. Solution: increase cable size (lower resistance per metre), reduce circuit length, or protect with an RCD.
  • Wrong MCB type — Type C or D MCBs used where Type B is appropriate. This is common in older commercial installations where Type C MCBs were fitted as standard. Solution: replace with Type B MCBs where the load characteristics permit.
  • Loose or corroded connections — poor connections in the protective conductor path increase impedance. This often manifests as inconsistent Zs readings between test points. Solution: inspect and tighten all connections in the circuit, particularly at accessories and junction boxes.
  • Broken ring continuity — if a ring final circuit has a break in the ring (either line or CPC), the circuit operates as two radials. The Zs at the break point can be significantly higher than expected. Solution: carry out ring circuit continuity tests (R1, Rn, R2) to confirm the ring is intact.

On an EICR, a circuit that fails ADS is typically coded C2 (potentially dangerous) — the protective measure is impaired and may not operate in the event of a fault. If the touch voltage exceeds 50V AC and disconnection will not occur, a C1 code (danger present) may be appropriate.

Frequently Asked Questions About Regulation 411 and ADS

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Test, Record and Verify ADS Compliance on Site

Join 1,000+ UK electricians using Elec-Mate for loop impedance recording, automatic Zs validation, and on-site EIC/EICR certificates. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy