COMMERCIAL GUIDE

Restaurant Electrical Requirements: Commercial Kitchen Electrics Guide

From three-phase supply sizing to gas interlocks, emergency switching to EICR intervals — every electrical requirement for restaurants and commercial kitchens in the UK, referenced to BS 7671:2018+A4:2026.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,600+ UK electricians

16 min readUpdated 2026-08-07Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

The short answer

What are the electrical requirements for a commercial kitchen?

Most commercial kitchens need a three-phase supply: 100A three-phase gives roughly 69 kW against a typical post-diversity demand of 40-80 kW. Each fixed appliance takes its own circuit (Reg 314.2) with a local means of isolation (Reg 462.2). Socket-outlets up to 32A need 30 mA RCD protection (Reg 411.3.3), emergency switching off must be red on a contrasting background and latch off (Reg 537.3.3), and gas cooking equipment must be interlocked with the extract ventilation.

1,600+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5

Key takeaways

  1. 01Most commercial kitchens need a three-phase supply. A 100A three-phase supply delivers roughly 69 kW against a typical post-diversity demand of 40-80 kW for a 40-60 cover restaurant — a 100A single-phase supply delivers about 23 kW and is rarely enough.
  2. 02Socket-outlets rated up to 32A need 30 mA RCD additional protection under BS 7671 Reg 411.3.3. The documented risk-assessment exception applies only to indent (b) — it is not available for outlets liable to be used by ordinary persons, which covers almost every socket in a restaurant.
  3. 03Commercial cooking and dishwashing equipment often has a protective conductor current above 10 mA. Reg 543.7.1.203 then requires a high integrity protective conductor connection, and Reg 543.7.1.205 requires the affected circuits to be indicated at the distribution board.
  4. 04Where gas cooking equipment is used, an interlock between the gas supply and the mechanical extract ventilation is required — the gas shuts off if the extract stops. This is a Gas Safe and BS 6173 requirement, not a BS 7671 one, but the electrician installs and maintains the electrical side.
  5. 05BS 7671 sets no fixed EICR interval. Reg 652.1 requires the frequency to be determined from the type of installation, its use, the quality of maintenance, external influences and previous reports; Reg 653.4 requires the report to state a recommended interval with an explanation. For commercial kitchens 1-3 years is typical.

01 · Commercial Guide

Restaurant Electrical Requirements: What You Need to Know

Restaurants, cafes, and commercial food establishments have some of the most demanding electrical installations in the commercial sector. High-power cooking equipment, mechanical extract ventilation, emergency lighting, fire alarm systems, refrigeration, EPOS tills and ambient lighting combine into a load that needs careful design, correct circuit division, and ongoing maintenance in a genuinely hostile environment.

The regulations that actually apply

InstrumentWhat it covers here
BS 7671:2018+A4:2026Design, installation, inspection and testing of the fixed electrical installation.
Electricity at Work Regulations 1989Duty on the duty holder to maintain systems so as to prevent danger.
Health and Safety at Work Act 1974Overarching duty of care to employees and members of the public.
Fire Safety Order 2005Fire risk assessment, escape route lighting, fire detection and alarm provision.
Building Regulations Part B and Part FFire safety, and ventilation of the food preparation area.
Building Regulations Part PElectrical safety in dwellings only. It bites on a restaurant fit-out only where the premises include or adjoin a dwelling, such as a flat above.
Gas Safety (Installation and Use) Regs 1998Gas side of the extract interlock, with BS 6173 for catering appliances.

Part P is the one most commonly cited in error. Approved Document P applies to electrical installations in dwellings — a standalone restaurant unit is not notifiable work under Part P, though a mixed-use building with flats above may well be. The rest of the fixed installation is governed by BS 7671:2018+A4:2026 and the Electricity at Work Regulations 1989.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Commercial Guide

Three-Phase Supply for Commercial Kitchens

The first question for any restaurant installation is whether the existing supply is adequate. Reg 311.1 requires maximum demand to be determined so the installation is designed within thermal limits and admissible voltage drop, and permits diversity to be taken into account. Start with what the supply can actually deliver:

SupplyApproximate capacityRealistic for
100A single-phase~23 kWCafe, sandwich bar, takeaway with domestic-grade equipment
100A three-phase~69 kWMost mid-size sit-down restaurants
200A three-phase~138 kWLarge restaurant, two combi ovens, full extract plant
400A three-phase~276 kWHotel kitchen, central production unit, multi-unit site

Capacities are the arithmetic product of the supply voltage and current at unity power factor (three-phase: 3 × 230V × I). Treat them as a sanity check, not a design figure — confirm the agreed capacity in kVA with the DNO.

Typical connected loads, 40-60 covers

EquipmentTypical loadSupply and notes
Combi oven15-40 kWThree-phase, hardwired. The single largest load in most kitchens — and some kitchens have two.
Commercial dishwasher6-18 kWPass-through types typically 32A; rack conveyor types usually three-phase.
Extract ventilation system2-7 kWCanopy extract plus make-up air. Often three-phase on larger systems.
Walk-in cold room and freezer1-3 kW eachDedicated circuits; condensing unit usually external.
Power, lighting, EPOS, CCTV5-15 kWFront and back of house power, ambient and feature lighting, tills, security.

Total connected load commonly reaches 60-120 kW before diversity. After diversity, maximum demand typically falls to 40-80 kW — which is why a 100A three-phase supply suits many mid-size restaurants and a single-phase supply rarely does. If the premises are single-phase, a three-phase upgrade must be arranged through the Distribution Network Operator, involving a formal application, a connection quotation, and a lead time of 6-12 weeks.

What to ask before you take a unit

How many phases, and what is the main switch rated at?
Ask for a photograph of the intake, the cut-out fuse rating, and the main switch. Three brown tails is not the same as an agreed three-phase capacity.
What is the DNO agreed capacity in kVA?
Get it in writing. The fuse rating is what is fitted; the agreed capacity is what you are allowed to draw, and the two often differ.
Can I see the last EICR and the board schedules?
A current report tells you the earthing arrangement, the outcome, any C1/C2 codes outstanding, and how many spare ways you have to work with.
Is the meter whole-current or CT-metered?
CT metering usually indicates a substantial supply. A whole-current single-phase meter is a strong signal that heavy electric cooking will not fit.
Is the supply shared with flats or another unit?
A shared intake constrains what you can add and complicates any upgrade application.

03 · Commercial Guide

Extract Fans and Ventilation Systems

Mechanical extract ventilation is not optional in a commercial kitchen. Building Regulations Part F covers ventilation of the food preparation area, and the detailed specification is set out in DW/172 (the BESA Specification for Kitchen Ventilation Systems).

Dedicated circuit
The extract fan takes its own circuit, sized for the full load current of the motor with the appropriate rating factors applied. Reg 314.2 requires separate circuits for parts of an installation that need to be separately controlled.
Gas interlock
Where gas cooking equipment is used, an interlock between the gas supply and the extract is required under BS 6173. A current-sensing relay or air pressure switch proves the extract is running; if it stops, the gas solenoid valve closes and shuts off the supply to all cooking equipment.
Make-up air
The supply air fan providing replacement air is interlocked with the extract, so the supply system cannot run without the extract running.
Speed control
Variable speed drives are common on extract motors. Install to minimise electromagnetic disturbance and use screened cable between drive and motor. Reg 314.1(e) explicitly lists mitigating the effects of electromagnetic disturbances as a reason to divide an installation into circuits.

The gas interlock is the most safety-critical element of the electrical installation in a gas kitchen. It must be tested at commissioning and at every subsequent gas safety inspection. The electrician installs and maintains the electrical components — current sensor, relay, control panel and wiring — while the Gas Safe registered engineer installs the solenoid valve and certifies the gas side.

04 · Commercial Guide

Commercial Kitchen Equipment: Electrical Requirements

Every piece of commercial kitchen equipment has specific electrical requirements that must be settled at fit-out. Get the manufacturer data sheets before you design the board schedule — power rating, number of phases, connection type and protective conductor current all vary between models.

Combi ovens

The most power-hungry item in most kitchens, commonly 15-40 kW on a three-phase supply, hardwired on a dedicated circuit with a local means of isolation. Water and drain connections are also required, and the position must allow clearance for ventilation and servicing.

Commercial dishwashers

Pass-through (hood-type) models typically need a 32A supply. Rack conveyor models need three-phase, often 32A or 63A depending on the model, and flight-type machines for high-volume operations can exceed 50 kW. Each takes a dedicated circuit with a means of isolation adjacent to the machine.

Walk-in cold rooms and freezers

Dedicated circuits, typically 16A or 20A, with the condensing unit usually sited externally or in a plant area. An internal emergency door release must be fitted, and an internal alarm is recommended. Luminaires inside must be rated for the temperature and humidity — IP65 LED fittings are standard.

Deep fat fryers

Electric fryers range from about 3 kW (single-tank countertop) to 25 kW (double-tank floor-standing, three-phase). They sit under the extract canopy on dedicated circuits, with a means of emergency switching off within reach of the operator — see the section below for what BS 7671 actually requires of that control.

High protective conductor current (Reg 543.7)

This is the requirement most often missed on commercial kitchen fit-outs. Combi ovens, dishwashers, induction ranges and variable speed drives all carry EMC filters, and their protective conductor current in normal service is frequently above 10 mA. BS 7671 then imposes three separate obligations:

Reg 543.7.1.202 — how the equipment may be connected
Equipment with a protective conductor current exceeding 10 mA must be permanently connected to the fixed wiring, or connected by a flexible cable with a BS EN IEC 60309-2 plug and socket-outlet whose protective conductor is at least 2.5mm² for 16A plugs and at least 4mm² above 16A, or protected by a BS 4444 earth monitoring system that disconnects on a protective conductor continuity fault.
Reg 543.7.1.203 — high integrity protective connection
Where the total protective conductor current on a circuit is likely to exceed 10 mA, the wiring needs a high integrity protective connection: a single 10mm² protective conductor, or a single 4mm² copper protective conductor with additional mechanical protection, or two individual protective conductors, or a BS 4444 monitoring system, or supply via a double-wound transformer.
Reg 543.7.1.205 — label the board
Information must be provided at the distribution board indicating which circuits have a high protective conductor current, positioned so it is visible to anyone modifying or extending the circuit.

The same accumulation of filter current is the usual cause of nuisance RCD tripping in kitchens. Reg 314.1(d) lists reducing unwanted tripping of RCDs due to excessive protective conductor currents as an explicit reason to divide the installation into more circuits — which is a better answer than uprating the RCD.

RCD protection for kitchen socket-outlets (Reg 411.3.3)

In AC systems, 30 mA RCD additional protection is required for socket-outlets rated up to 32A in locations where they are liable to be used by ordinary persons (BA1) or children (BA2), for socket-outlets up to 32A in other locations, and for mobile equipment up to 32A used outdoors. The documented risk-assessment exception applies to the second of those only. In a restaurant, kitchen and front-of-house sockets are used by ordinary persons, so the exception is not available for them — and the regulation's own note is explicit that an ordinary person instructed in the use of the installation does not stop being an ordinary person. Training the kitchen brigade does not buy you out of the requirement.

Before starting any fit-out, collect the manufacturer data sheets, calculate the total connected load, apply diversity, and design the board schedule around it. Use Elec-Mate's max demand calculator to confirm the supply is adequate before you commit.

05 · Commercial Guide

Isolation and Emergency Switching in the Kitchen

Isolation and emergency switching off are two different functions with two different sets of requirements, and commercial kitchens need both. Confusing them is a common EICR observation.

Isolation

Reg 462.2 requires every circuit to be provided with a means of isolation for all live conductors, and Reg 462.3 requires isolation devices to be designed or installed so as to prevent unintentional or inadvertent closure — by being within a lockable enclosure, by padlocking, or by being located adjacent to the associated equipment. For fixed kitchen equipment, a local isolator beside the machine is the practical answer: it matches the third of those examples and lets an engineer work on a fryer without shutting the whole kitchen down.

Emergency switching off

Reg 465.1 requires a means of emergency switching off for any part of an installation where it may be necessary to control the supply to remove an unexpected danger — a fryer, a mixer, a slicer. Reg 465.3 requires it to act as directly as possible on the supply conductors, with a single action interrupting the supply. Section 537 sets out what the device itself has to do:

Red, on a contrasting background (Reg 537.3.3.5)
The means of operating must be clearly identified, preferably by colour. Where colour is used it shall be red with a contrasting background — yellow is the example given in the regulation. A bare red mushroom head on a stainless splashback does not meet this.
It must latch off (Reg 537.3.3.7)
The means of operation must be capable of latching in the OFF position, unless both the emergency switching off and the re-energising are under the control of the same person. A momentary pushbutton is not acceptable.
A plug is not an emergency stop (Reg 537.3.3.3)
Plugs and socket-outlets shall not be provided for use as a means for emergency switching off. “Just pull the plug out” is not a compliant arrangement.
Readily accessible where the danger is (Reg 537.3.3.6)
The control must be readily accessible at places where a danger might occur, and where appropriate at a remote position from which the danger can be removed. Behind the fryer is not readily accessible.
It must break the full load (Reg 537.3.3.2)
Devices for emergency switching off must be capable of breaking the full load current of the relevant parts of the installation, taking stalled motor currents into account where appropriate.

Cables in protected escape routes (Reg 422.2)

Restaurants nearly always have a protected escape route, and Reg 422.2.201 restricts what may run through a firefighting shaft or a protected stairway: only an essential fire safety or related safety system, general needs lighting, or socket-outlets provided for cleaning or maintenance. Reg 422.2.1 further restricts which cables may be installed in protected escape routes to fire-resistant cables meeting Reg 560.8.1, or cables with resistance to flame propagation to the relevant part of the BS EN 60332-3 series, among the listed options. Reg 422.2.202 deems cables to be outside the escape route where they are installed in a fire-resisting enclosure of the same fire resistance as the compartment they pass through. Routing a general power circuit up a protected stairway to save a few metres of cable is a straightforward non-compliance.

06 · Commercial Guide

Emergency Lighting in Restaurants

Emergency lighting is a legal requirement for restaurants and commercial food premises under the Regulatory Reform (Fire Safety) Order 2005. The system must comply with BS 5266-1:2016 and illuminate escape routes, exit doors, and high-risk areas including the kitchen, on failure of the normal supply.

AreaMinimum illuminanceNotes
Escape routes1 lux across the full widthUniformity ratio no worse than 40:1 between brightest and darkest points.
Open areas (anti-panic)0.5 luxApplies to open areas larger than 60m², such as the main dining room.
High-risk task areas10% of the normal maintained illuminance, or 15 lux, whichever is greaterThe commercial kitchen is a high-risk task area — staff need enough light to shut equipment down safely.
Duration3 hours1 hour is only acceptable where premises are evacuated immediately and not reoccupied until the supply is restored.

Illuminated exit signs, maintained or non-maintained, go above every final exit door and at any point where the direction of escape is not immediately obvious; signs comply with BS 5499.

Testing and records

Testing is mandatory: a monthly functional test (simulate supply failure and confirm every luminaire illuminates) and an annual full-duration test (run the system for its full rated duration on battery and confirm illumination is maintained throughout). Every result goes in the log book, which the Fire and Rescue Service may ask to see. For more on test procedure and order, see our testing sequence guide.

In the app

Try Elec-Mate free for 7 days

19 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

07 · Commercial Guide

Fire Alarm Systems for Restaurants

The Regulatory Reform (Fire Safety) Order 2005 requires the responsible person — typically the restaurant owner or operator — to ensure appropriate fire detection and alarm systems are in place. The system is designed, installed and maintained to BS 5839-1:2025, with the category set by the fire risk assessment.

Category M

Manual system only — call points at exit doors, no automatic detection. Suitable for smaller premises with simple layouts and a low fire risk, where occupants would discover a fire quickly.

Category L2

Automatic detection in defined high-risk areas (kitchen, store rooms, plant rooms) plus all escape routes and rooms opening onto them. The most common category for mid-size restaurants.

Cooking produces heat and airborne particles that trigger false alarms, so heat detectors — rate-of-rise or fixed-temperature, rated for the environment — are used in cooking areas rather than smoke detectors. Multi-sensor detectors are increasingly used in transitional areas such as the pass between kitchen and dining room.

Systems the alarm has to talk to

Electromagnetic door holders
Fire doors held open on electromagnetic retainers must release automatically on alarm activation.
Kitchen suppression system
Where a wet chemical canopy suppression system is fitted, it interfaces with the fire alarm panel so activation is signalled and logged.
Gas shut-off
The fire alarm can be arranged to drop the gas solenoid valve, cutting the gas supply on activation.

Maintenance is weekly user testing of the alarm, plus periodic inspection and servicing by a competent fire alarm engineer at the frequency set by BS 5839-1 and the fire risk assessment. Keep every record.

08 · Commercial Guide

EICR Intervals for Restaurants and Commercial Kitchens

There is no fixed BS 7671 maximum interval for commercial premises. Reg 652.1 requires the frequency of periodic inspection and testing to be determined having regard to the type of installation and equipment, its use and operation, the frequency and quality of maintenance, and the external influences to which it may be subjected — and the results and recommendations of previous certificates and condition reports must also be taken into account. Reg 653.4 then requires the report to indicate a recommended interval until the next inspection, supported by an explanation for the recommendation.

Read those two together and a commercial kitchen argues itself into a short interval. Heat, steam, grease, water, aggressive cleaning chemicals and heavy daily use are exactly the “external influences” and “use and operation” factors Reg 652.1 puts in front of the inspector. IET Guidance Note 3 gives the same steer for periodic inspection of commercial installations.

The interval is the inspector's judgement, not a table lookup
Reg 653.4 requires the recommendation and the explanation behind it to appear on the report. “5 years” with no reasoning does not satisfy it.
1-3 years is typical for a restaurant kitchen
Shorter where the installation is older, heavily loaded, or regularly exposed to moisture and cleaning chemicals. Many insurers, local authorities and fire and rescue services independently specify 3 years as a condition of cover or licensing.
Mobile catering units are a different job
A transportable catering unit falls under BS 7671 Section 717 (mobile or transportable units), which brings its own requirements — including the Reg 717.514 permanent notice at the supply inlet stating the supply types accepted, voltage rating, number of supplies and phases, on-board earthing arrangement, and maximum power requirement.
A maintenance regime can replace periodic inspection
Reg 652.2 allows periodic inspection and testing to be replaced by an adequate regime of continuous monitoring and maintenance by skilled persons, under an effective management system for preventative maintenance, with appropriate records kept. Few independent restaurants will meet that bar; larger groups sometimes do.

Under the Health and Safety at Work Act 1974 and the Electricity at Work Regulations 1989 (Regulation 4 in particular), the duty holder must ensure electrical installations are maintained so as to prevent danger. A current EICR is the standard evidence of that. Failing to hold one can lead to enforcement action from the HSE, invalidated insurance, and difficulty renewing a premises licence.

In the app

Commercial kitchen electrical requirements

BS 7671:2018+A4:2026 compliance for restaurant kitchens. Calculate load demands, design circuits, and issue certificates. Free guide for electricians.

09 · Commercial Guide

Restaurant Electrical Compliance Checklist

Work through this before signing off a restaurant installation or closing out an EICR. Regulation references are to BS 7671:2018+A4:2026.

  • Supply adequacy (Reg 311.1) — Maximum demand determined and checked against the DNO agreed capacity, with diversity applied. Three-phase supply in place where required.
  • Circuit division (Regs 314.1, 314.2, 314.4) — Installation divided into circuits to avoid danger, facilitate testing and maintenance, and reduce unwanted RCD tripping from protective conductor currents. Each final circuit on its own way in the board.
  • Distribution board schedule — All circuits clearly labelled with correct ratings, and adequate spare ways for future equipment.
  • RCD protection (Reg 411.3.3) — 30 mA RCD additional protection on socket-outlets rated up to 32A. Remember the documented risk-assessment exception covers indent (b) only, and does not reach outlets liable to be used by ordinary persons.
  • High protective conductor current (Reg 543.7) — Equipment above 10 mA connected by a permitted method (543.7.1.202), circuits given a high integrity protective connection (543.7.1.203), and the affected circuits indicated at the board (543.7.1.205).
  • Isolation (Regs 462.2, 462.3) — Every circuit has a means of isolating all live conductors, and isolators for fixed kitchen equipment are located adjacent to the equipment or otherwise secured against inadvertent closure.
  • Emergency switching off (Regs 465.1, 537.3.3) — Provided where needed to remove an unexpected danger; red on a contrasting background, latching in the OFF position, readily accessible, and able to break the full load current. Not a plug and socket.
  • AFDDs (Regs 421.1.7, 532.6) — Required in high rise residential buildings, HMOs, purpose-built student accommodation and care homes for single-phase AC final circuits supplying socket-outlets up to 32A; recommended for all other premises on the same circuit type. Where fitted, at the origin of the circuit.
  • Escape route wiring (Reg 422.2) — Nothing in a firefighting shaft or protected stairway beyond essential safety systems, general needs lighting, and cleaning or maintenance socket-outlets. Cables in protected escape routes meet Reg 422.2.1.
  • Gas interlock — Extract-to-gas-solenoid interlock installed, commissioned and tested. Current sensing or air pressure proving confirmed operational.
  • Emergency lighting — BS 5266-1 compliant system installed. Exit signs, escape route lighting, open-area lighting and high-risk task area lighting all verified, with the test schedule established.
  • Fire alarm — BS 5839-1 system installed to the category set by the fire risk assessment. Heat detection in cooking areas. Integration with door holders, suppression and gas shut-off proven.
  • Cable adequacy (Section 523) — Cables confirmed adequate for current-carrying capacity for the type and nature of the installation, with rating factors for ambient temperature, grouping and installation method applied.
  • Cable support (Regs 521.10.202, 522.8.5) — Cables correctly supported throughout their run, and wiring systems supported such that they are not liable to premature collapse in the event of a fire.
  • EICR (Regs 653.1, 653.4) — Current report in place with a Satisfactory outcome, and a recommended interval to the next inspection recorded with the reasoning behind it.
  • Portable appliances — In-service inspection and testing carried out and recorded for all portable equipment.

10 · Commercial Guide

For Electricians: Restaurant Work as a Revenue Stream

Restaurant and commercial kitchen work is a strong specialism. Periodic EICRs, emergency lighting testing, fire alarm servicing, in-service appliance testing and reactive maintenance together produce a recurring income from every restaurant client — and the barrier to entry is knowing Section 543, Chapter 46 and Section 537 well enough to specify properly.

Periodic EICR
At the interval recommended on the previous report — commonly 1-3 years for a commercial kitchen. Thirty to fifty circuits is a full day on site. Price accordingly.
Emergency lighting testing
Monthly functional tests and the annual full-duration test, usually sold as a maintenance contract.
Fire alarm servicing
Scheduled servicing visits at the frequency set by BS 5839-1 and the fire risk assessment. Another contract opportunity.
Reactive maintenance
Restaurants trade long hours and cannot serve without a working kitchen. Being on call generates premium-rate callout work.

Elec-Mate covers the full range of certificates restaurant work needs — EICR, EIC, Minor Works, fire alarm, emergency lighting and appliance testing. Complete each one on your phone, generate a professional PDF, and send it to the owner before you leave the premises.

In the app

All restaurant certificates in one app

EICR, EIC, Fire Alarm, Emergency Lighting, PAT Testing — complete every certificate a restaurant needs on your phone.

Frequently Asked Questions About Restaurant Electrical Requirements

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-day free trial

Complete Restaurant Certificates on Your Phone

EICR, Fire Alarm, Emergency Lighting, PAT Testing — every certificate a restaurant needs, completed on site with AI-powered tools. Join 1,600+ UK electricians using Elec-Mate. 7-day free trial.

Start your free trial

From £6.99/mo after the trial — no charge until day 8.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in one tap — no calls, no hassle
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play
Certificate types
19Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists

1,600+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy