COMMERCIAL GUIDE

Restaurant Electrical Requirements: Commercial Kitchen Electrics Guide

From three-phase supply calculations to gas interlocks, emergency lighting to fire alarm systems — this guide covers every electrical requirement for restaurants and commercial kitchens in the UK. Whether you are fitting out new premises or maintaining an existing installation, this is the reference you need.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

14 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

What are the electrical requirements for a commercial kitchen?

A commercial kitchen usually needs a three-phase supply to handle high-load cooking equipment, with each fixed appliance on its own correctly-sized circuit. Key requirements include a clearly-labelled emergency shut-off, a gas-interlock system linking the ventilation to the gas supply, emergency lighting on escape routes, fire detection, and RCD protection — all installed and certified to BS 7671. A periodic EICR keeps the installation compliant and insurable.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Most commercial kitchens require a three-phase supply to support high-demand equipment such as combi ovens, commercial dishwashers, and extract systems — single-phase supply is rarely sufficient.
  • 2Extract ventilation in commercial kitchens must comply with Building Regulations Part F, Gas Safety (Installation and Use) Regulations 1998, and DW/172 (Specification for Kitchen Ventilation Systems) — an interlock between the gas supply and extract fan is mandatory.
  • 3Emergency lighting must comply with BS 5266-1:2016 and requires monthly functional testing, annual full-duration testing, and a 3-hour battery duration for most restaurant premises.
  • 4EICR inspection intervals for restaurants are not fixed by BS 7671 — per IET Guidance Note 3 (GN3 9th Ed, Reg 2.4), the inspector must determine and recommend the next interval based on the findings of each inspection. For harsh commercial kitchen environments, a 1–3 year interval is typically appropriate.
  • 5Elec-Mate lets electricians complete EICR certificates, fire alarm certificates, and emergency lighting certificates for restaurant clients on site — with AI defect coding, professional PDF export, and instant delivery.
01 · Commercial Guide

Restaurant Electrical Requirements: What You Need to Know

Restaurants, cafes, and commercial food establishments have some of the most demanding electrical installations in the commercial sector. The combination of high-power kitchen equipment, mechanical extract ventilation, emergency lighting, fire alarm systems, CCTV, EPOS tills, refrigeration, and ambient lighting creates a complex electrical load that requires careful design, installation, and ongoing maintenance.

The regulatory framework is equally complex. Restaurant electrical installations must comply with BS 7671:2018+A4:2026 (the IET Wiring Regulations), the Electricity at Work Regulations 1989, the Health and Safety at Work Act 1974, Building Regulations Part P (electrical safety), Part B (fire safety), Part F (ventilation), Part L (energy efficiency), the Regulatory Reform (Fire Safety) Order 2005, and food hygiene regulations that affect the design and placement of electrical equipment in food preparation areas.

This guide covers the key electrical requirements for restaurants in the UK — from three-phase supply calculations to extract fan interlocks, emergency lighting to fire alarm systems, and EICR inspection intervals. Whether you are an electrician working on restaurant fit-outs or a restaurant owner planning a new premises, this is the reference you need.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Commercial Guide

Three-Phase Supply for Commercial Kitchens

The first question for any restaurant electrical installation is whether the existing supply is adequate. Most commercial kitchens need a three-phase supply because the total connected load exceeds the capacity of a single-phase supply.

A typical sit-down restaurant with 40-60 covers might have the following electrical loads:

  • Combi oven — 15 to 40 kW (three-phase). The single largest electrical load in most commercial kitchens. Some kitchens have two.
  • Commercial dishwasher — 6 to 18 kW. Pass-through types are typically single-phase 32A; rack conveyor types are usually three-phase.
  • Extract ventilation system — 2 to 7 kW. Kitchen canopy extract with supply air. Often three-phase for larger systems.
  • Walk-in cold room and freezer — 1 to 3 kW each. Dedicated circuits with appropriate overcurrent and RCD protection.
  • General power, lighting, EPOS, CCTV — 5 to 15 kW combined. Front of house and back of house power circuits, ambient and feature lighting, tills, card machines, and security systems.

The total connected load can easily reach 60 to 120 kW before diversity is applied. After applying diversity (permitted under BS 7671 Reg 311.1 and the OSG notes on allowances for diversity), the maximum demand typically falls to 40 to 80 kW. A three-phase 100A supply provides approximately 69 kW, which is sufficient for many mid-size restaurants. Larger operations may require a 200A or even 400A three-phase supply.

If the premises currently has a single-phase supply, a three-phase upgrade must be arranged through the Distribution Network Operator (DNO). This involves a formal application, a quotation for the connection works, and a lead time of 6 to 12 weeks. Plan this well ahead of your fit-out programme.

03 · Commercial Guide

Extract Fans and Ventilation Systems

Mechanical extract ventilation is not optional in a commercial kitchen. Building Regulations Part F requires adequate ventilation in all commercial food preparation areas, and the specific requirements are set out in DW/172 (BESA Specification for Kitchen Ventilation Systems).

The electrical requirements for kitchen extract systems include:

  • Dedicated circuit — the extract fan must have its own dedicated circuit from the distribution board, sized for the full load current of the motor with appropriate correction factors.
  • Gas interlock — where gas cooking equipment is used, a gas interlock system is mandatory. A current-sensing relay monitors the extract fan motor. If the fan stops, the gas solenoid valve closes, shutting off the gas supply to all cooking equipment within seconds.
  • Make-up air — the supply air fan (providing replacement air to the kitchen) must be interlocked with the extract fan. The supply air system should not operate without the extract running.
  • Speed control — variable speed drives (VSDs) or inverters are increasingly used for extract fan motors to reduce energy consumption. The VSD must be installed to minimise electromagnetic interference and the cable between the VSD and motor should be screened (SY cable).

The gas interlock is one of the most safety-critical elements of the electrical installation. It must be tested at commissioning and at every subsequent gas safety inspection. The electrician installs and maintains the electrical components (current sensor, relay, control panel, and wiring), while the Gas Safe engineer commissions and certifies the gas side including the solenoid valve.

04 · Commercial Guide

Commercial Kitchen Equipment: Electrical Requirements

Every piece of commercial kitchen equipment has specific electrical requirements that must be met during the fit-out. Getting these wrong causes delays, additional costs, and potential safety issues.

Combi Ovens

The most power-hungry item in most kitchens. A single Rational iCombi Pro 10-1/1 draws approximately 19 kW on a three-phase supply. Larger models (20-2/1) can draw over 40 kW. They require hardwired connections on dedicated circuits with appropriate isolators. Always check the manufacturer data sheet — power ratings vary significantly between models. Water and drain connections are also required, and the installation position must allow adequate clearance for ventilation and servicing.

Commercial Dishwashers

Pass-through (hood-type) models typically need a 32A single-phase or three-phase supply. Rack conveyor models need a three-phase supply, often 32A or 63A depending on the model. Flight-type (conveyor) machines for high-volume operations can exceed 50 kW. A dedicated circuit with RCD protection is essential. The dishwasher should also have a local isolator within reach of the operator for emergency shutdown.

Walk-In Cold Rooms and Freezers

Walk-in cold rooms and freezer rooms require dedicated circuits, typically 16A or 20A. The compressor unit is usually sited externally or in a plant area. An emergency door-release mechanism (often a manual push bar) must be fitted inside the cold room, and an internal alarm system is recommended. The lighting circuit inside the cold room must use fittings rated for the temperature and humidity conditions. IP65 rated LED fittings are standard.

Deep Fat Fryers

Electric fryers range from 3 kW (single-tank countertop) to 25 kW (double-tank floor-standing, three-phase). They must be positioned under the extract canopy and connected on dedicated circuits. A red emergency stop button (mushroom head, latching type) should be installed within easy reach of the fryer operator. The fryer circuit must be protected by an appropriate overcurrent device and, where required, an RCD.

Reg 730.55.1.4 — One Socket-Outlet Per Vessel

Where cooking vessels (such as electric fryers, induction hobs, or heated holding units) are connected via plug-and-socket, BS 7671:2018+A4:2026 Reg 730.55.1.4 requires that each socket-outlet shall supply only one vessel. Multi-way adaptors, socket bars, and Y-leads feeding multiple cooking vessels from a single outlet are non-compliant. In practice this means the kitchen socket layout must provide a dedicated outlet for each plug-connected cooking appliance — a common deficiency found on EICR inspections of older commercial kitchen installations.

Before starting any commercial kitchen fit-out, obtain the manufacturer data sheets for every piece of equipment. Calculate the total connected load, apply diversity, and design the distribution board schedule accordingly. Use Elec-Mate's max demand calculator to verify the supply capacity is adequate.

05 · Commercial Guide

Emergency Lighting in Restaurants

Emergency lighting is a legal requirement for all restaurants and commercial food premises under the Regulatory Reform (Fire Safety) Order 2005. The system must comply with BS 5266-1:2016 and provide illumination along all escape routes, at exit doors, and in high-risk areas (including the commercial kitchen) in the event of a mains power failure.

  • Exit signs — illuminated exit signs (maintained or non-maintained) must be installed above all final exit doors and at any point where the direction of escape is not immediately obvious. Signs must comply with BS 5499.
  • Escape route lighting — minimum 1 lux on the centre line of escape routes, with a uniformity ratio of no more than 40:1 between the brightest and darkest points.
  • Open-area lighting — minimum 0.5 lux in open areas larger than 60 square metres, such as the main dining room, to prevent panic.
  • High-risk task area lighting — the commercial kitchen is classified as a high-risk area. Emergency lighting must provide sufficient illumination for the operator to shut down equipment safely (minimum 10% of the normal maintained illuminance or 15 lux, whichever is greater).
  • Duration — 3-hour battery backup for most restaurant premises (1 hour is only acceptable for premises that are evacuated immediately and not reoccupied during a power failure).

Testing is mandatory: a monthly functional test (simulate mains failure, confirm all luminaires illuminate), a quarterly brief inspection, and an annual full-duration test (run the system for the full 3 hours on battery and verify illumination is maintained). All test results must be recorded in a log book. For more on the testing sequence, see our testing sequence guide.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · Commercial Guide

Fire Alarm Systems for Restaurants

The Regulatory Reform (Fire Safety) Order 2005 requires the responsible person (typically the restaurant owner or operator) to ensure that appropriate fire detection and alarm systems are in place. The fire alarm system must be designed, installed, and maintained to BS 5839-1:2025.

The system category depends on the fire risk assessment. Common categories for restaurants include:

Category M

Manual system only — call points at exit doors. Suitable for smaller premises with simple layouts, minimal fire risk, and where the occupants are likely to discover a fire quickly. No automatic detection.

Category L2

Automatic detection in defined areas of high risk (kitchen, store rooms, plant rooms) plus all escape routes and rooms opening onto escape routes. Most common category for medium-sized restaurants. Heat detectors in the kitchen, smoke detectors in escape routes and storage areas.

Commercial kitchens present a unique challenge for fire detection because cooking produces heat and airborne particles that can trigger false alarms. Heat detectors (rate-of-rise type or fixed-temperature type rated for the kitchen environment) are used in cooking areas instead of smoke detectors. Multi-sensor detectors are increasingly used in transitional areas (for example, the pass between kitchen and dining room).

The fire alarm system must integrate with:

  • Electromagnetic door holders — fire doors held open by electromagnetic retainers release automatically when the fire alarm activates.
  • Kitchen suppression system — if an Ansul or similar kitchen suppression system is fitted, it should interface with the fire alarm panel.
  • Gas shut-off — the fire alarm can trigger the gas solenoid valve to close, shutting off the gas supply in the event of a fire alarm activation.
07 · Commercial Guide

EICR Intervals for Restaurants and Commercial Kitchens

IET Guidance Note 3 (9th Edition, Reg 2.4) is clear: there is no fixed BS 7671 maximum interval for commercial premises. The subsequent inspection period must be determined during each periodic inspection and test, based on the inspector's assessment of the installation's condition, the risk environment, and the findings of the current inspection. The inspector's recommended interval must be recorded on the EICR and the duty holder is bound by it.

In practice, the harsh environment of a commercial kitchen — heat, steam, grease, water, aggressive cleaning chemicals, and heavy daily use — accelerates deterioration. Inspectors will typically recommend a shorter interval than for a low-risk commercial premises. Many insurers, local authorities, and fire and rescue services also specify 3-year intervals for restaurants as a condition of cover or premises licensing.

  • Inspector-determined interval — per GN3 9th Ed Reg 2.4, the recommended interval must be based on the findings of each inspection, not a generic table. The inspector's reasoning must be recorded on the EICR.
  • 1–3 years typical for restaurants — appropriate for most restaurant kitchens given the harsh operating environment, particularly where the installation is older, heavily loaded, or regularly exposed to moisture and cleaning chemicals.
  • 1 year for food vans and temporary structures — pop-up restaurants and temporary food stalls should be inspected annually due to the portable nature of the installation and exposure to weather.

Under the Health and Safety at Work Act 1974 and the Electricity at Work Regulations 1989 (specifically Regulation 4), the duty holder must ensure that electrical installations are maintained so as to prevent danger. A current EICR is the standard evidence of compliance. Failing to maintain a valid EICR can result in enforcement action from the Health and Safety Executive (HSE), invalidation of insurance, and difficulty renewing a premises licence.

Commercial kitchen electrical requirements

BS 7671:2018+A4:2026 compliance for restaurant kitchens. Calculate load demands, design circuits, and issue certificates. Free guide for electricians.

Try it free for 7 days
Download on the App StoreGet it on Google Play
08 · Commercial Guide

Restaurant Electrical Compliance Checklist

Use this checklist to verify that a restaurant electrical installation meets the key compliance requirements:

  • Supply adequacy — supply capacity verified against maximum demand calculation. Three-phase supply in place where required.
  • Distribution board schedule — all circuits clearly labelled with correct ratings. Adequate spare ways for future expansion.
  • RCD protection — appropriate RCD protection on all final circuits as required by BS 7671 Reg 551.4.4.2. Socket circuits, circuits supplying equipment in zones of increased risk.
  • AFDD consideration (Reg 421.1.7, A4:2026) — BS 7671:2018+A4:2026 recommends arc fault detection devices (AFDDs) on AC final circuits to mitigate fire risk from arc fault currents. For mixed-use buildings with residential flats above a restaurant, the residential floors may be within scope. Electricians quoting restaurant fit-outs in these buildings should discuss AFDD provision with the client.
  • Gas interlock — extract fan to gas solenoid interlock installed, commissioned, and tested. Current sensing relay confirmed operational.
  • Emergency lighting — BS 5266-1 compliant system installed. Exit signs, escape route lighting, open-area lighting, and high-risk area lighting all verified. Test schedule established.
  • Fire alarm — BS 5839-1 compliant system installed to the appropriate category. Heat detectors in kitchen areas. Integration with door holders, suppression system, and gas shut-off verified.
  • EICR — current EICR in place with Satisfactory outcome. Next inspection date recorded and tracked.
  • Dedicated socket per cooking vessel (Reg 730.55.1.4) — each plug-connected cooking appliance has its own dedicated socket-outlet. No multi-way adaptors feeding multiple cooking vessels from a single outlet.
  • Cable adequacy verified (Reg 622.85) — at EICR, cables confirmed adequate for current-carrying capacity with correction factors for ambient temperature, grouping, and installation method checked against Section 523.
  • PAT testing — all portable appliances tested and labelled. Records maintained.
09 · Commercial Guide

For Electricians: Restaurant Work as a Revenue Stream

Restaurant and commercial kitchen electrical work is a lucrative specialism for electricians. The combination of regular EICR inspections (every 3-5 years), emergency lighting testing (monthly and annually), fire alarm maintenance (quarterly and annually), PAT testing, and ongoing reactive maintenance creates a recurring revenue stream from each restaurant client.

A single restaurant contract might include:

  • EICR every 3 years — commercial premises with 30-50+ circuits. A thorough commercial EICR can take a full day on site. Price accordingly.
  • Emergency lighting testing — monthly functional tests and annual full-duration test. Many electricians offer this as a maintenance contract.
  • Fire alarm maintenance — quarterly inspections and annual service. Another maintenance contract opportunity.
  • Reactive maintenance — restaurants operate long hours and equipment failures need fast response. Being on call for a restaurant generates premium-rate callout work.

Elec-Mate supports the full range of certificates needed for restaurant work — EICR, EIC, Minor Works, Fire Alarm, Emergency Lighting, and PAT Testing. Complete every certificate on your phone, generate professional PDFs, and deliver them to the restaurant owner before you leave the premises.

All restaurant certificates in one app

EICR, EIC, Fire Alarm, Emergency Lighting, PAT Testing — complete every certificate a restaurant needs on your phone.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions About Restaurant Electrical Requirements

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Complete Restaurant Certificates on Your Phone

EICR, Fire Alarm, Emergency Lighting, PAT Testing — every certificate a restaurant needs, completed on site with AI-powered tools. Join 1,000+ UK electricians using Elec-Mate. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy