- Degree of protection — Reg 703.512.2
- Equipment shall have a degree of protection of at least IPX4. Where cleaning by use of water jets may reasonably be expected, at least IPX5.
- Wiring systems — Reg 703.52
- The wiring system should preferably be installed outside the zones, on the cold side of the thermal insulation. Where it is on the warm side of the thermal insulation in Zone 1 or Zone 3 it shall be heat-resisting. Metallic sheaths and metallic conduits shall not be accessible in normal use.
- Switchgear and socket-outlets — Reg 703.537.5
- Switchgear and controlgear forming part of the sauna heater equipment, or of other fixed equipment installed in Zone 2, may be installed within the sauna room or cabin in accordance with the manufacturer instructions. Other switchgear and controlgear, for example for lighting, shall be placed outside the room or cabin. Socket-outlets shall not be installed within the location containing the sauna heater.
- Protective measures ruled out — Regs 703.410.3.5/.3.6
- Obstacles and placing out of reach (Section 417) shall not be used. Non-conducting location (Reg 418.1) and earth-free local equipotential bonding (Reg 418.2) shall not be used.
- SELV and PELV — Regs 703.414.3 and 703.414.4.5
- Regulation 703.414.3 was introduced at A4:2026: where SELV or PELV is used in Zones 1, 2 and/or 3, a source described in Regulation 414.3(d) shall not be used. Whatever the nominal voltage, basic protection shall be provided by basic insulation complying with Regulation 416.1 or by barriers or enclosures complying with Regulation 416.2.
- Heating appliances — Reg 703.55
- Sauna heating appliances shall comply with BS EN 60335-2-53 and be installed in accordance with the manufacturer instructions.