HIGH VALUE GUIDE

Solar Panel Installation UK
Guide, Requirements & Costs 2026

Solar PV is one of the fastest-growing areas of domestic electrical work in the UK. This guide covers everything an electrician needs to know — system sizing, MCS certification, DNO notification, earthing considerations, inverter selection, battery storage, costs, and the certificates required to commission a compliant installation.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

20 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1A typical domestic solar PV system is 3-4 kW (8-10 panels), costs £5,000-£8,000 installed, and pays back in 6-10 years through electricity savings and Smart Export Guarantee payments.
  • 2MCS certification is essential — without it the homeowner cannot receive Smart Export Guarantee payments, which can amount to several thousand pounds over the system lifetime.
  • 3DNO notification is mandatory: G98 (simple notification) for systems up to 3.68 kW single-phase, G99 (formal application) for larger systems.
  • 4On PME (TN-C-S) earthing systems, the PV array frame must not be connected to the PME earth — a separate earth electrode or double-insulated equipment is required (BS 7671 Section 712).
  • 5Two certificates are required for a domestic solar PV installation: an MCS certificate (covering the renewable energy system) and an Electrical Installation Certificate (EIC) to BS 7671 covering the AC and DC wiring.
01 · High Value Guide

Domestic Solar PV — Overview

A domestic solar photovoltaic (PV) system converts sunlight into electricity using semiconductor panels mounted on the roof. The typical UK domestic system is between 3 kW and 4 kW, consisting of 8 to 10 panels each rated at approximately 400-450 W. A south-facing roof at a pitch of 30-40 degrees provides the best energy yield, although east-west split arrays are increasingly common and can provide a more even generation profile throughout the day.

The PV panels generate direct current (DC) electricity, which is converted to alternating current (AC) by an inverter. The AC output is connected to the property's consumer unit, where it supplies the household loads. Any surplus electricity not used by the household is exported to the grid. The system operates automatically — generating electricity whenever there is sufficient daylight — and requires minimal maintenance beyond occasional panel cleaning and periodic inverter checks.

For electricians, solar PV installation involves both DC and AC electrical work, structural assessment of the roof, compliance with MCS standards, DNO notification, and Part P building regulations notification. It is a skilled job that requires specific training and, for SEG eligibility, MCS installer certification.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · High Value Guide

MCS Certification Requirements

The Microgeneration Certification Scheme (MCS) is the quality assurance framework for small-scale renewable energy installations in the UK. MCS certification covers both the products (panels and inverters must be MCS-listed) and the installers (who must be MCS-certified). An MCS-certified installation is eligible for payments under the Smart Export Guarantee (SEG), the scheme that pays generators for electricity exported to the grid.

To become an MCS-certified installer, you must hold a relevant qualification — typically the City and Guilds 2399 (Design and Installation of Solar Photovoltaic Systems) or equivalent. You must also be registered with a Competent Person Scheme for Part P notification, carry adequate public liability insurance, and meet the MCS quality management requirements, including documented procedures for system design, installation, commissioning, and handover.

MCS Certification Checklist

  • Product certification — All panels and inverters must be MCS-listed products. Check the MCS product directory before specifying equipment.
  • Installer certification — The installing company must hold a current MCS certificate for PV installations. Individual operatives must be qualified and competent.
  • Performance estimate — An MCS-compliant performance estimate (predicted annual generation in kWh) must be provided to the customer before installation.
  • Commissioning documentation — Full commissioning records including test results, system specification, photographs, and the MCS installation certificate.

Without MCS certification, the homeowner cannot register the installation for Smart Export Guarantee payments. This is a significant financial consideration — over a 25-year system lifetime, SEG payments can amount to several thousand pounds. MCS certification also provides consumer protection through the MCS Consumer Code.

03 · High Value Guide

DNO Notification — G98 and G99

Any electricity-generating installation connected to the public distribution network must comply with the relevant Engineering Recommendation published by the Energy Networks Association (ENA). For domestic solar PV, this means either G98 or G99, depending on the rated output of the system.

G98 (Up to 3.68 kW Single Phase)

G98 (formerly G83) applies to installations with a rated output up to 16A per phase — approximately 3.68 kW on a single-phase supply. G98 uses a simplified notification process: you notify the Distribution Network Operator (DNO) within 28 days of commissioning using the standard G98 form, and connection is permitted automatically provided the installation meets the technical requirements.

No prior approval is needed. The majority of domestic PV installations fall within the G98 threshold.

G99 (Above 3.68 kW Single Phase)

G99 (formerly G59) applies to installations exceeding the G98 threshold. This requires a formal application to the DNO before installation begins. The DNO carries out a network impact assessment to determine whether the local network can accommodate the generation.

The DNO may approve the connection as applied for, approve it with conditions (such as export limitation), or require network reinforcement. G99 applications can take 4-12 weeks.

For three-phase installations, the G98 limit is approximately 11.04 kW (3.68 kW per phase). Systems above this require a G99 application regardless of the number of phases.

04 · High Value Guide

Part P Building Regulations Notification

Installing a solar PV system involves adding new electrical circuits to the property, which is notifiable work under Part P of the Building Regulations. The work must be either self-certified through a Competent Person Scheme (such as NICEIC, NAPIT, or ELECSA) or notified to the local authority building control department before work commences.

Most MCS-certified installers are registered with a Competent Person Scheme, allowing them to self-certify the electrical work. A full Electrical Installation Certificate (EIC) is required for the new circuits — both the DC side (panels to inverter) and the AC side (inverter to consumer unit). A Minor Works Certificate is not appropriate because the work involves new circuits.

In addition to the electrical notification, the structural aspects of the installation may require consideration under the Building Regulations. In most cases, solar PV installations on existing domestic roofs are permitted development and do not require planning permission, provided the panels do not protrude more than 200mm from the roof surface and do not extend above the highest part of the roof. However, listed buildings, conservation areas, and certain other designations may require planning consent.

05 · High Value Guide

Earthing Considerations — PME vs TT

The earthing arrangement of the property is a critical consideration for solar PV installations. The majority of UK domestic properties have a TN-C-S (PME) earthing system, which creates specific safety considerations for PV arrays.

On a PME supply, the combined neutral-earth (PEN) conductor means that if an open PEN fault occurs, dangerous voltages can appear on the PME earth terminal. Because the PV array frame is typically mounted on the roof and connected via metallic mounting rails, any fault on the PME earth could energise the entire array frame structure — creating a hazard for anyone on the roof or in contact with the array.

PME Earthing — Critical Safety Point

On PME (TN-C-S) supplies, BS 7671 Section 712 requires that the PV array frame must not be connected to the PME earth. Options include: installing a separate TT earth electrode for the array frame, using Class II (double-insulated) equipment throughout the DC side so that no earthing of the array frame is required, or a combination of both approaches. The chosen method must be documented on the Electrical Installation Certificate.

For properties with a TN-S earthing system (earth provided by the cable sheath), the open PEN risk does not apply, and the array frame can be earthed to the main earthing terminal in the normal way. For properties with an existing TT earthing system, the earth electrode arrangements must be checked for adequacy.

Always verify the earthing arrangement by inspecting the supply and measuring Ze before designing the PV installation earthing scheme.

Cable Sizing Calculator for Solar PV

Elec-Mate's cable sizing calculator handles both DC and AC sides of a solar PV installation. Enter the string voltage, current…

Try it free for 7 days
Download on the App StoreGet it on Google Play
06 · High Value Guide

Inverter Types — String vs Micro

The inverter converts DC electricity from the PV panels into AC electricity compatible with the household supply and the grid. There are two main types of inverter used in domestic installations, each with distinct advantages and implications for the electrical design.

String Inverter

A string inverter is a single central unit, typically mounted near the consumer unit or in a garage. All PV panels are connected in series (a "string") and their combined DC output feeds into the inverter. This is the traditional and most cost-effective approach for simple roof layouts.

Advantages: Lower cost per kW, simpler wiring, easier access for maintenance. Disadvantages: If one panel is shaded, the output of the entire string is reduced. Not suitable for complex roof layouts with multiple orientations. Single point of failure.

Microinverters

Microinverters are small inverters mounted on the back of each individual panel. Each panel operates independently, converting DC to AC at the panel level. The AC output from all microinverters is then combined and fed to the consumer unit.

Advantages: Panel-level optimisation means shading on one panel does not affect others. Ideal for complex roofs with multiple orientations or partial shading. No high-voltage DC cabling in the property. Disadvantages: Higher cost per kW, more components on the roof, maintenance requires roof access.

A third option is power optimisers combined with a string inverter. Optimisers are fitted to each panel (like microinverters) but handle only DC-DC conversion and panel-level optimisation. The DC output still feeds into a central string inverter for DC-AC conversion. This provides many of the benefits of microinverters with a central inverter for easier maintenance and monitoring.

AI Circuit Designer for Solar PV Systems

Elec-Mate's AI Circuit Designer helps you plan the complete electrical design for a solar PV installation — string configuration, inverter selection…

Try it free for 7 days
Download on the App StoreGet it on Google Play

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
07 · High Value Guide

Battery Storage

Battery storage systems allow homeowners to store surplus solar electricity generated during the day for use in the evening and at night. A typical domestic battery stores 5-13 kWh of energy and costs £2,500-£6,000 installed. The addition of battery storage significantly increases the self-consumption ratio — the proportion of generated electricity used on site rather than exported — from typically 30-50% (without a battery) to 70-90% (with a battery).

For electricians, battery storage adds complexity to the installation. The battery system connects between the inverter and the consumer unit (AC-coupled) or between the PV array and the inverter (DC-coupled). Hybrid inverters that handle both PV input and battery charging/discharging are increasingly popular and simplify the wiring.

BS 7671:2018+A4:2026 Section 530 is particularly relevant to battery storage installations. Because a battery can supply fault current back through the consumer unit (bidirectional current flow), the protective devices must be suitable for operation in both directions. Standard unidirectional MCBs and RCBOs may not clear faults correctly when current flows in the reverse direction. Always check with the device manufacturer and the battery system designer that the protective devices are rated for bidirectional fault current.

Battery storage installations are notifiable under Part P and require appropriate certification. The consumer unit regulations apply in full, including the Amendment 4 requirements for bidirectional devices.

08 · High Value Guide

Smart Export Guarantee (SEG)

The Smart Export Guarantee (SEG) replaced the Feed-in Tariff (FiT) in January 2020 as the mechanism for paying domestic generators for electricity exported to the grid. Under the SEG, licensed electricity suppliers with more than 150,000 customers must offer at least one SEG tariff that pays a positive rate for exported electricity.

SEG tariff rates vary between suppliers and change regularly, but as of 2026, typical rates range from 4p to 15p per kWh exported, depending on the supplier and the tariff structure. Some suppliers offer fixed rates, while others offer variable rates that track wholesale electricity prices — these can be significantly higher during peak demand periods.

To register for the SEG, the installation must be MCS-certified and have a generation capacity up to 5 MW (for solar PV, practically all domestic installations qualify). A smart meter or export meter is required to measure the electricity exported. The homeowner applies to their chosen electricity supplier for a SEG tariff — they do not have to use the same supplier for their import tariff.

For a typical 4 kW domestic system generating approximately 3,400-3,800 kWh per year and exporting approximately 50% (1,700-1,900 kWh), the annual SEG income at current rates is approximately £100-£200. Over a 25-year system lifetime, this amounts to £2,500-£5,000 — a meaningful contribution to the payback calculation.

09 · High Value Guide

Installation Process — Roof Assessment to Commissioning

A domestic solar PV installation follows a structured process from the initial site survey through to commissioning and handover. Each stage involves specific technical considerations and documentation requirements.

Roof Assessment Checklist

  • Structural suitability — The roof must be able to support the additional weight of the panels and mounting system (typically 12-15 kg per panel). Most modern roofs can handle this, but older properties or lightweight roof structures may need a structural engineer's assessment.
  • Orientation and pitch — South-facing at 30-40 degrees is optimal, but east-west splits and pitches from 15-50 degrees are all viable. North-facing roofs are generally not suitable.
  • Shading — Trees, chimneys, neighbouring buildings, and dormer windows can all cause shading. Even partial shading on one panel can significantly reduce string output (unless microinverters or optimisers are used).
  • Available area — Each panel occupies approximately 1.7-2.0 m². A 4 kW system (10 panels) requires approximately 17-20 m² of unobstructed roof area.
  • Cable route — Plan the route for DC cables from the roof to the inverter location. Cables must be UV-resistant where exposed, protected from mechanical damage, and routed to minimise length and voltage drop.

Commissioning involves testing both the DC and AC sides of the installation. DC tests include open-circuit voltage (Voc) and short-circuit current (Isc) for each string, insulation resistance, earth continuity, and polarity. AC tests follow the standard BS 7671 requirements — earth fault loop impedance, prospective fault current, RCD operating times, insulation resistance, and continuity.

10 · High Value Guide

Certificates Required

A domestic solar PV installation requires several pieces of documentation to be fully compliant:

MCS Certificate

Issued by the MCS-certified installer upon completion. Documents the system specification, performance estimate, and confirms compliance with MCS standards. Required for SEG registration. Uploaded to the MCS database along with commissioning photographs and the performance estimate.

Electrical Installation Certificate (EIC)

Required under BS 7671 for the new electrical circuits. Covers both the DC side (panels to inverter) and the AC side (inverter to consumer unit). Must include full test results, system design details, and confirmation of compliance with Section 712 requirements.

G98/G99 Notification

The DNO notification form (G98 for systems up to 3.68 kW single-phase) or application and approval documentation (G99 for larger systems). Must be completed and submitted within the required timeframe.

Part P Certificate

Building Regulations compliance certificate issued through the Competent Person Scheme or local authority building control. Confirms the electrical work complies with the Building Regulations.

Solar PV Certificate in Elec-Mate

Elec-Mate has a dedicated Solar PV Certificate form covering both DC and AC side documentation, string configurations, inverter specifications…

Try it free for 7 days
Download on the App StoreGet it on Google Play
11 · High Value Guide

Cost and Payback Period

The total cost of a domestic solar PV installation depends on the system size, equipment specification, roof complexity, and the installer's pricing. As of 2026, typical costs for a standard domestic installation are:

Typical UK Solar PV Costs (2026)

3 kW system (8 panels)

Suitable for smaller properties or lower consumption

£4,000 - £6,000

4 kW system (10 panels)

Most common domestic size

£5,000 - £8,000

6 kW system (15 panels)

Larger properties or higher consumption

£7,000 - £10,000

Battery storage (add-on)

5-13 kWh capacity

£2,500 - £6,000

The payback period depends on electricity prices, self-consumption ratio, and SEG income. At current UK electricity prices (approximately 24-28p per kWh), a typical 4 kW system saves the homeowner £500-£800 per year through reduced electricity bills and SEG payments. This gives a payback period of approximately 6-10 years. With a system lifetime of 25-30 years, the total financial benefit over the system life is substantial.

Adding battery storage extends the payback period (due to the additional capital cost) but significantly increases the self-consumption ratio and therefore the annual savings. With an EV or heat pump, the case for battery storage becomes even stronger.

AI Cost Engineer for Solar PV Quoting

Elec-Mate's AI Cost Engineer generates accurate quotes for solar PV installations in seconds.

Try it free for 7 days
Download on the App StoreGet it on Google Play

How to Install Solar Panels — Step-by-Step

A step-by-step overview of the domestic solar PV installation process, from initial survey through to commissioning and handover.

1

Site survey and system design

Visit the property and assess the roof — orientation, pitch, available area, shading, and structural suitability. Check the existing electrical installation: earthing arrangement, consumer unit capacity, supply fuse rating. Design the PV system: panel layout, string configuration, inverter selection, cable routing, and earthing scheme. Prepare the MCS performance estimate.

2

DNO notification and permissions

Submit the G98 notification (or G99 application for systems above 3.68 kW single-phase) to the Distribution Network Operator. Check whether planning permission is required (conservation area, listed building, etc.). Order equipment: panels, inverter, mounting system, DC and AC cabling, protective devices.

3

Install the mounting system and panels

Install the roof mounting brackets, fixing through the tiles or slates into the rafters. Fit the mounting rails and attach the panels according to the planned layout. Ensure all fixings are watertight using appropriate flashing and sealant. Connect the panels in the designed string configuration using MC4 connectors.

4

Install DC and AC cabling

Route the DC cables from the roof to the inverter location using UV-resistant PV cable (H1Z2Z2-K). Install the DC isolator adjacent to the inverter. Mount and connect the inverter. Run the AC cable from the inverter to the consumer unit. Install the AC isolator and appropriate protective device (MCB or RCBO) in the consumer unit.

5

Commission and test

Carry out DC side tests: open-circuit voltage (Voc) and short-circuit current (Isc) for each string, insulation resistance, earth continuity, and polarity. Carry out AC side tests: earth fault loop impedance, prospective fault current, RCD operating time, insulation resistance, and continuity. Commission the inverter and verify correct grid connection operation. Record all test results.

6

Certify and hand over

Complete the Electrical Installation Certificate (EIC) covering both DC and AC sides. Submit the DNO notification (G98) or confirm G99 approval. Register the installation on the MCS database. Issue all documentation to the homeowner: MCS certificate, EIC, G98/G99 notification, inverter manual, and the performance estimate. Assist the homeowner with SEG tariff application if required.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Design and Certify Solar PV Installations With Confidence

Solar PV certificates, cable sizing calculator, voltage drop calculator, and AI Circuit Designer — all in Elec-Mate. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy