1 of 8 Elec-AI Specialist Agents

AI Circuit DesignerBS 7671 Compliant Design

Design complete electrical circuits with AI tailored and trained specifically for UK electrical work. Automatic cable sizing, protection device selection, voltage drop verification, and earth fault loop impedance checks — all to BS 7671:2018+A4:2026.

BS 7671:2018+A4:20261,000+ electriciansPart of 8 Elec-AI agents
The AI Circuit Designer generates fully verified BS 7671:2018+A4:2026-compliant circuit designs from a plain-English description of your installation. It produces a complete consumer unit schedule — including cable sizes, protective device types and ratings, voltage drop figures (verified against Appendix 4, Section 6.4 limits of 3% for lighting and 5% for other circuits), and earth fault loop impedance values — ready to transfer directly onto an Electrical Installation Certificate. All A4:2026 requirements are applied automatically, including RCD protection on domestic lighting circuits (Reg 411.3.4) and bidirectional device selection for installations with solar PV or battery storage (Reg 530.3.201).

What Is the AI Circuit Designer?

The AI Circuit Designer is one of eight specialist Elec-AI agents built into the Elec-Mate platform. It is tailored and trained specifically for UK electrical work, with deep knowledge of BS 7671:2018+A4:2026, the IET On-Site Guide, IET Guidance Notes 1 through 8, and thousands of real-world installation scenarios. Unlike generic AI tools, this agent understands the specific requirements of UK electrical installations and produces designs that comply with the current edition of the Wiring Regulations.

You describe an installation in plain English — for example, "four-bedroom detached house with an EV charger in the garage, 10.8 kW electric shower, induction hob, gas boiler, LED downlights throughout, and a garden office with its own distribution board" — and the Circuit Designer generates a complete electrical design. This includes a full consumer unit schedule with circuit-by-circuit details, cable sizing calculations with all correction factors applied, protection device selections with type ratings and breaking capacities, voltage drop verification for every circuit, and earth fault loop impedance checks against the maximum permitted values for the chosen protective devices.

The designer handles the full range of UK domestic, commercial, and light industrial installations. For domestic work, it designs consumer unit layouts with the correct split-load or dual-RCD configurations, specifies RCBO protection where required, and includes surge protection device (SPD) requirements under BS 7671 Section 443. For commercial work, it produces distribution board schedules with three-phase load balancing, submain calculations, and diversity assessments. For all installation types, it accounts for the earthing system (TN-S, TN-C-S, or TT) and applies the correct disconnection times from BS 7671 Table 41.1.

What distinguishes this tool from a simple cable sizing calculator is that it designs the complete circuit, not just one parameter in isolation. It considers how cable size, protection device rating, circuit length, installation method, and earthing arrangement all interact. If a change to one parameter affects another — for example, if upsizing a cable for voltage drop compliance changes the (R1+R2) value and therefore the maximum Zs — the designer recalculates everything automatically and presents a fully verified design.

How the Circuit Designer Works

1

Describe Your Installation

Enter the property type, circuits needed, earthing system, and any specific requirements in plain English. The AI asks clarifying questions if it needs more detail — for example, the cable route lengths for critical circuits, the ambient temperature conditions, or whether cables will pass through thermal insulation.

2

AI Designs the Complete Circuit

The designer calculates design currents, selects protective devices (MCBs, RCBOs, or MCCBs with correct type ratings), sizes cables using the full adiabatic method from BS 7671 Appendix 4, and verifies voltage drop, earth fault loop impedance, and prospective fault current for every circuit.

3

Review with Regulation References

Every design decision is explained with references to specific BS 7671 regulations. If the designer chose a 6mm cable instead of 4mm, it shows the calculation step by step, citing the specific tables and correction factors used. You can verify every decision independently.

4

Export the Consumer Unit Schedule

Download the complete consumer unit schedule in a format that maps directly onto the Electrical Installation Certificate (EIC). Circuit numbers, descriptions, device ratings, cable sizes, and test parameters are all ready to transfer to your certification documentation.

Cable Sizing to BS 7671 Appendix 4

Cable sizing is the foundation of safe circuit design, and the AI Circuit Designer follows the complete BS 7671 method rather than taking shortcuts. The process begins with determining the design current (Ib) based on the connected load. For a 10.8 kW electric shower on a 230V single-phase supply, this is 10,800 / 230 = 47A. The designer then selects the next standard protective device rating (In) above the design current — in this case, a 50A device.

The required current-carrying capacity of the cable (It) is then calculated by dividing the protective device rating by the product of all applicable correction factors: It = In / (Ca x Cg x Ci x Cc). For a cable installed in a loft space with thermal insulation on one side only (Ci = 0.75), in an ambient temperature of 30 degrees Celsius (Ca = 0.94 from Table 4B1), grouped with two other circuits (Cg = 0.79 from Table 4C1), the required It would be 50 / (0.94 x 0.79 x 0.75) = 89.7A. The designer then selects the smallest cable from the appropriate table whose tabulated current-carrying capacity (Iz) exceeds this value.

After selecting the cable, the designer verifies three additional requirements. First, the voltage drop from the origin of the installation to the load must not exceed 3% for lighting circuits or 5% for other circuits. Second, the earth fault loop impedance at the furthest point of the circuit must be low enough for the protective device to disconnect within the required time (0.4 seconds for final circuits not exceeding 32A, 5 seconds for distribution circuits). Third, the cable must satisfy the adiabatic equation (k squared S squared greater than or equal to I squared t) to ensure it can withstand the thermal effects of a fault current for the duration of the protective device operating time. If any of these checks fails, the designer automatically upsizes the cable and recalculates.

Protection Device Selection

The Circuit Designer selects the correct type and rating of protective device for every circuit based on the load characteristics and BS 7671 requirements. It understands the different operating characteristics of Type B, Type C, and Type D MCBs and selects the appropriate type for each application. Type B devices (tripping at 3 to 5 times rated current) are used for resistive and lightly inductive loads such as socket outlets, lighting, and electric showers. Type C devices (tripping at 5 to 10 times rated current) are selected for circuits with moderate inrush currents such as small motors, fluorescent lighting banks, and IT equipment. Type D devices (tripping at 10 to 20 times rated current) are specified for circuits with high inrush currents such as large motors, transformers, and X-ray equipment.

The designer also applies the RCD protection requirements of BS 7671. Under Regulation 411.3.3 (revised in A4:2026), additional protection by an RCD with a rated residual operating current not exceeding 30 mA is required for socket outlets with a rated current not exceeding 32A. For mobile equipment with a rated current not exceeding 32A for use outdoors, RCD protection is similarly required (Regulation 411.3.3 and OSG Regulation 830.3.201). In non-dwelling premises the requirement may be omitted where a documented risk assessment determines RCD protection is not necessary; in dwellings, no such exception applies. The designer specifies RCBO protection (combined MCB and RCD in a single device) where individual circuit RCD protection is needed, or recommends a split-load consumer unit configuration with appropriate RCD coverage.

For installations with battery storage systems, solar PV, or EV chargers with DC fault current capability, the designer specifies the appropriate RCD type. Standard Type AC RCDs detect only AC residual currents, Type A RCDs detect AC and pulsating DC residual currents, and Type B RCDs detect AC, pulsating DC, and smooth DC residual currents. The designer selects the correct type based on the equipment connected, in accordance with BS 7671 Regulation 531.3 and Regulation 530.3.201 introduced by A4:2026, which requires selection and erection of protective devices to take account of whether a device is unidirectional or bidirectional — essential for installations with reverse power flow such as battery storage and solar PV arrays.

Why Electricians Choose Elec-Mate for Circuit Design

Tailored and trained specifically for UK electrical work. The AI Circuit Designer handles the calculations so you can focus on the installation. Part of 70+ calculators, 8 AI agents, and 46+ training courses.

Adiabatic Cable Sizing

Full BS 7671 Appendix 4 cable sizing with all correction factors: ambient temperature (Ca), grouping (Cg), thermal insulation (Ci)…

Protection Device Selection

Automatic selection of MCBs, RCBOs, and RCDs with correct type ratings. Type B for resistive loads, Type C for small motors…

Voltage Drop Verification

Automatic voltage drop calculation against BS 7671 limits: 3% for lighting circuits, 5% for power circuits. Calculates cumulative drop for submains.

Earth Fault Loop Impedance

Verifies Zs at the furthest point of every circuit against BS 7671 Tables 41.2-41.6. Accounts for conductor temperature and cable length.

Consumer Unit Schedules

Generates complete consumer unit schedules ready for EIC documentation. Circuit numbers, device ratings, cable sizes, and Zs values all included.

TN-S, TN-C-S & TT Systems

Full support for all UK earthing arrangements. Correct disconnection times, earth fault loop values, and RCD requirements for each system type.

Trained on BS 7671:2018+A4:2026

The AI Circuit Designer is tailored and trained specifically for UK electrical work. Its knowledge base covers the complete scope of BS 7671:2018+A4:2026 (the 18th Edition of the IET Wiring Regulations including Amendment 4, issued July 2024), the IET On-Site Guide, all eight IET Guidance Notes, and a curated library of real-world installation case studies and worked examples.

Amendment 4:2024 (A4:2026) is particularly relevant for the Circuit Designer because it introduces several new requirements. Regulation 530.3.201 requires that the selection and erection of protective devices shall take account of whether a device is unidirectional or bidirectional — critical for installations with battery energy storage, solar PV arrays, and other sources of reverse power flow. Regulation 411.3.4 introduces a mandatory requirement for RCD protection (rated residual operating current not exceeding 30 mA) on all domestic lighting circuits. Regulation 411.3.3 has been revised to apply to all socket outlets rated not exceeding 32A, with the exception to omit RCD protection limited to non-dwelling premises where a documented risk assessment supports it. The Circuit Designer automatically applies all of these requirements.

BS 7671:2018+A4:2026 (18th Edition)
Amendment 4:2024 — Regs 411.3.3, 411.3.4, 530.3.201
IET On-Site Guide
IET Guidance Notes 1-8
GN3: Inspection & Testing (9th Edition)
Appendix 4 Cable Sizing Tables
Real-world installation case studies
TN-S, TN-C-S, and TT system design

Frequently Asked Questions

How does the AI Circuit Designer select cable sizes?

The AI Circuit Designer follows the full adiabatic cable sizing method from BS 7671 Appendix 4. It starts with the design current (Ib) for the circuit, selects a protective device rating (In) that is greater than or equal to Ib, then determines the required current-carrying capacity (It) by applying all relevant correction factors. These include the ambient temperature factor (Ca) from Table 4B1, the grouping factor (Cg) from Tables 4C1 to 4C6, the thermal insulation factor (Ci) from Table 52.2, and where applicable the semi-enclosed fuse factor (Cc) of 0.725. The designer then selects the smallest cable size from the appropriate table in Appendix 4 (for example, Table 4D5 for thermoplastic flat cable) whose tabulated current-carrying capacity (Iz) exceeds the required value of It. It then verifies the cable meets the voltage drop limits, earth fault loop impedance requirements, and adiabatic equation for fault protection. If any check fails, the designer automatically upsizes the cable and recalculates.

Can the AI handle three-phase circuit design?

Yes. The AI Circuit Designer handles single-phase and three-phase circuit design. For three-phase installations, it calculates line currents, selects appropriate three-pole and four-pole protective devices (MCCBs, TP MCBs, TP+N RCBOs), sizes three-phase cables using the correct current-carrying capacity tables, and verifies voltage drop across all three phases. It understands the differences between balanced and unbalanced three-phase loads, calculates neutral current in unbalanced systems, and selects neutral conductor sizes accordingly. For commercial and industrial installations, it produces distribution board schedules showing phase allocation to achieve balanced loading across the three phases, and calculates diversity factors appropriate to the type of installation.

Does the Circuit Designer verify earth fault loop impedance?

Yes. For every circuit, the designer verifies that the earth fault loop impedance (Zs) at the furthest point of the circuit does not exceed the maximum value permitted for the selected protective device. It uses the formula Zs = Ze + (R1+R2), where Ze is the external earth fault loop impedance of the supply and (R1+R2) is the resistance of the line conductor plus the circuit protective conductor, corrected for conductor operating temperature. The designer references the maximum Zs values from BS 7671 Tables 41.2 to 41.6 for different protective device types and ratings. If the calculated Zs exceeds the maximum, the designer either increases the cable size to reduce (R1+R2), selects a larger protective device rating where the design current permits, or recommends the use of an RCBO for additional fault protection.

How does the AI handle EV charger circuit design?

EV charger circuits have specific requirements under BS 7671 Section 722 that the Circuit Designer addresses automatically. For a typical 7.4 kW single-phase charger drawing 32A, the designer applies a continuous load factor (the charger operates at rated current for extended periods, so the cable must be rated for sustained loading). It specifies Type A RCD protection as a minimum, or Type B where required by the charger manufacturer for DC fault current protection. The cable sizing accounts for the full route from the consumer unit to the charging point, including any derating for thermal insulation where the cable passes through insulated walls or loft spaces. For installations requiring a dedicated supply (such as a 22 kW three-phase charger), the designer includes the supply assessment and any upgrades needed to the main incoming supply. BS 7671 Section 722 also includes specific requirements for TN-C-S (PME) earthing systems: outdoor EV charging equipment on a PME supply requires particular consideration of the earthing arrangement and protective measures, as the PME earth may not be suitable without additional precautions. The designer flags this when the earthing system is identified as TN-C-S and the charger is located outdoors.

What earthing systems does the Circuit Designer support?

The Circuit Designer supports all earthing systems defined in BS 7671: TN-S (separate neutral and earth, typically older PME supplies with a lead-sheathed cable earth), TN-C-S (combined neutral and earth at the supply transformer, separated at the intake position — the most common arrangement for modern UK domestic supplies), and TT (no earth provided by the distributor, requiring a local earth electrode). For each earthing system, the designer applies the correct maximum disconnection times from BS 7671 Table 41.1 (0.4 seconds for final circuits not exceeding 32A, 5 seconds for distribution circuits), selects appropriate protective devices, and verifies earth fault loop impedance values. For TT systems, it accounts for the typically higher Ze values and recommends RCD protection where the earth fault loop impedance would otherwise be too high for overcurrent devices alone to provide disconnection within the required time.

Can the designer produce a complete consumer unit schedule for an EIC?

Yes. When you describe an installation, the Circuit Designer generates a complete consumer unit schedule that maps directly onto the schedule of circuits section of the Electrical Installation Certificate (EIC). For each circuit, the schedule includes: circuit number, circuit description, protective device type and rating (MCB Type B/C/D or RCBO), cable type and reference (for example, 6242Y for twin and earth flat cable), cable size, design current (Ib), protective device rating (In), maximum permitted Zs, voltage drop in volts and as a percentage, and whether the circuit requires RCD protection. The schedule also specifies the recommended consumer unit make and model, the main switch rating, and SPD (Surge Protection Device) requirements under BS 7671 Section 443. The output is formatted so you can transfer the values directly onto the EIC without additional calculation.

How does voltage drop verification work?

The Circuit Designer automatically verifies voltage drop for every circuit against the limits set by BS 7671. The statutory requirement is in Regulation 525, and the numeric limits — 3% for lighting circuits and 5% for all other circuits — are stated in Appendix 4, Section 6.4 of BS 7671:2018+A4:2026. The designer calculates voltage drop using the millivolt-per-ampere-per-metre (mV/A/m) values from the cable data tables in Appendix 4, multiplied by the design current and the cable route length. For longer cable runs — such as an outbuilding supply or a submain to a separate distribution board — the designer accounts for the cumulative voltage drop across all sections of the circuit. If the calculated voltage drop exceeds the permitted limit, the designer automatically upsizes the cable to bring the voltage drop within limits and recalculates all other parameters to confirm compliance.

Does the circuit designer apply the A4:2026 requirement for RCD protection on lighting circuits?

Yes. Regulation 411.3.4 of BS 7671:2018+A4:2026 introduces a mandatory requirement that, within domestic (household) premises, additional protection by an RCD with a rated residual operating current not exceeding 30 mA shall be provided for AC final circuits supplying luminaires. This is a new A4:2026 obligation — not present in earlier editions — and the Circuit Designer applies it automatically when designing a domestic installation. When producing the consumer unit schedule, the designer specifies RCBO protection (or RCD coverage from a split-load board) for every lighting circuit in a domestic property, not only for socket-outlet circuits. The requirement uses "shall" and is not subject to a risk-assessment exception; it applies to all domestic lighting circuits regardless of installation method.

When does the designer specify AFDDs, and does it need to be recorded on the EIC?

Regulation 421.1.7 of BS 7671:2018+A4:2026 recommends the installation of arc fault detection devices (AFDDs) in AC final circuits of a fixed installation to mitigate the risk of fire due to arc fault currents. The regulation uses recommendatory rather than mandatory language, but many network operators and insurers treat it as a practical requirement for high-risk premises (houses in multiple occupation, care homes, and similar). Where the Circuit Designer recommends or specifies AFDDs for socket-outlet final circuits, this must be recorded on the Electrical Installation Certificate: Regulation 133.1.3 of BS 7671:2018+A4:2026 requires that certain equipment usages — including AFDD installation — shall be recorded on the appropriate Part 6 electrical certification. The consumer unit schedule output from the Circuit Designer flags AFDD-protected circuits and reminds you to declare this on the EIC.

Design Circuits + Create Certificates in One App

Use the AI Circuit Designer alongside Elec-Mate's EIC certificate tool. Design the circuit, verify compliance, then document it — all from your phone.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Need to complete an installation certificate? Use the EICR and EIC certificate tool to record your design parameters and test results digitally.

7-Day Free Trial — Cancel Anytime, No Hassle

Design your first circuit in 60 seconds

Join 1,000+ UK electricians using AI for BS 7671 compliant circuit design. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy