WIRING GUIDE

Types of Circuit Breakers UK: MCB, MCCB, RCCB and RCBO Explained

A complete practical guide to circuit breaker types used in UK electrical installations — MCB, MCCB, RCCB and RCBO explained with curve types, breaking capacity requirements, BS 7671 compliance, and guidance on selecting the right device for every application.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

11 min readUpdated 2026-05-18Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1MCBs (Miniature Circuit Breakers) provide overcurrent protection for individual circuits in domestic and light commercial consumer units — they do not provide earth-fault (RCD) protection.
  • 2MCCBs (Moulded Case Circuit Breakers) are used in larger commercial and industrial installations where higher fault current ratings and adjustable trip settings are required.
  • 3RCCBs (Residual Current Circuit Breakers) provide earth-fault protection only — they must always be used with separate MCBs for complete circuit protection.
  • 4RCBOs combine MCB and RCD functions in one device, providing both overcurrent and 30mA earth-fault protection for a single circuit.
  • 5MCB curve type (B, C or D) determines the instantaneous trip threshold — Type B for domestic, Type C for commercial/light industrial, Type D for high inrush loads.
  • 6Breaking capacity must exceed the prospective fault current at the point of installation — always measure with a PFC meter before specifying devices.
01 · Wiring Guide

What Is a Circuit Breaker?

A circuit breaker is an automatically operated electrical switch designed to protect a circuit from damage caused by excess current, typically resulting from an overload or a short circuit. Unlike a fuse, which must be replaced after it operates, a circuit breaker can be reset — either manually or automatically — to resume normal operation after the fault has been identified and cleared.

  • Overload protection — a circuit breaker will trip after a sustained period of overcurrent (e.g. too many appliances on one circuit), protecting cables from overheating. The thermal element of the breaker heats up proportionally to the excess current and trips when the temperature threshold is reached.
  • Short-circuit protection — the electromagnetic element of a circuit breaker trips almost instantaneously (within milliseconds) when a short-circuit current is detected, preventing damage to wiring and equipment.
  • Not RCD protection — standard circuit breakers (MCBs and MCCBs) do not detect earth-fault currents. RCD protection must be provided separately unless an RCBO is used. See the RCD types guide for full details.

In UK electrical installations governed by BS 7671, the main types of circuit breaker used are MCBs, MCCBs, RCCBs, and RCBOs. Each has specific applications and characteristics that determine where it should be used.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Wiring Guide

MCB — Miniature Circuit Breaker

The MCB (Miniature Circuit Breaker) is the standard protective device for individual final circuits in UK domestic and light commercial consumer units. MCBs are compact single-module devices that provide both overload and short-circuit protection for a single circuit.

  • Current ratings — MCBs for domestic use are typically available in 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A, and 100A. Standard final circuits use: 6A for lighting, 32A for ring final circuits (sockets), 32A to 40A for cookers, 16A or 20A for dedicated circuits.
  • Breaking capacity — standard domestic MCBs have a breaking capacity of 6kA, which is sufficient for most UK domestic supplies. Higher breaking capacity MCBs (10kA) are available for commercial applications or where prospective fault current is higher.
  • No RCD function — MCBs provide overcurrent protection only. For circuits requiring 30mA additional protection (socket outlets, bathrooms, outdoor circuits), either an RCBO must replace the MCB, or an upstream RCCB must be used.
  • BS EN 60898 — UK MCBs are manufactured to BS EN 60898, which defines the performance requirements, trip characteristics, and marking for miniature circuit breakers for household and similar installations.
03 · Wiring Guide

MCCB — Moulded Case Circuit Breaker

An MCCB (Moulded Case Circuit Breaker) is a larger, more powerful circuit breaker used in commercial, industrial, and large residential installations. MCCBs can handle higher current ratings, have greater breaking capacities, and often feature adjustable trip settings that make them suitable as main incoming protection or sub-main protection in large distribution systems.

  • Higher current ratings — MCCBs are available from around 16A up to 1,600A or more, making them suitable as main switches for commercial distribution boards, sub-main circuit protection for large loads, and incoming protection for industrial installations.
  • Adjustable trip settings — unlike fixed MCBs, MCCBs often have adjustable thermal and magnetic trip settings. This allows the protection characteristic to be tailored to the connected load, improving selectivity and reducing nuisance tripping.
  • Higher breaking capacity — MCCBs are available with breaking capacities from 16kA up to 150kA, essential for installations near transformer secondary sides where fault currents can be very high.
  • Three-phase versions — MCCBs are commonly available in three-pole (three-phase) and four-pole (three-phase plus neutral) configurations, making them essential for three-phase commercial and industrial distribution.
04 · Wiring Guide

RCCB — Residual Current Circuit Breaker

An RCCB (Residual Current Circuit Breaker) provides earth-fault protection for a group of circuits. It does not provide overcurrent protection and must always be used in conjunction with individual MCBs. In a split-load consumer unit, an RCCB typically protects half the board's circuits from earth faults while individual MCBs on each way provide overcurrent protection.

  • Earth-fault protection only — the RCCB detects residual current (the difference between live and neutral currents) and trips when the imbalance exceeds the rated threshold. It does not respond to overload or short-circuit conditions.
  • Nuisance tripping — because one RCCB may protect 8 or more circuits, a fault on any single circuit trips all protected circuits. This is a significant disadvantage compared to individual RCBOs.
  • Sensitivity ratings — RCCBs are available at 30mA (personal protection), 100mA, and 300mA (fire protection). For domestic socket-outlet circuits, 30mA is required by BS 7671 18th Edition.

For a detailed explanation of all RCD types including SRCDs and RCDMs, see the RCD types UK guide.

05 · Wiring Guide

RCBO — Combined MCB and RCD in One Device

An RCBO (Residual Current Breaker with Overcurrent protection) is a single-module device that combines the functions of an MCB and a 30mA RCD. Each RCBO provides both overcurrent protection and earth-fault protection for one individual circuit, eliminating the need for a separate upstream RCCB for that circuit.

  • Per-circuit isolation — a fault on one circuit trips only that RCBO, leaving all other circuits unaffected. This eliminates the nuisance tripping problem inherent in RCCB-based designs and is a major benefit for domestic properties.
  • Higher cost per device — an RCBO costs three to five times more than an equivalent MCB. However, when the cost of the RCCB is removed from the calculation, an all-RCBO board is typically only £150 to £300 more expensive than a split-load RCCB/MCB board for a typical domestic installation.
  • RCD type selection — RCBOs come in Type AC, Type A, and Type B variants. Type A is now recommended as standard for domestic installations. Type B is required for certain EV charging circuits and equipment with smooth DC residual current components.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · Wiring Guide

MCB Curve Types: B, C and D Explained

The MCB curve type defines the instantaneous magnetic trip threshold — the multiple of the rated current at which the device trips almost instantaneously to clear a short circuit. Choosing the correct curve type is essential: too sensitive and the breaker nuisance-trips on inrush currents; not sensitive enough and the breaker fails to provide adequate protection against shock and fire.

  • Type B — 3 to 5 × In — trips instantaneously at 3 to 5 times rated current. Used for domestic circuits with resistive and slightly inductive loads: lighting circuits, socket-outlet circuits, immersion heaters, electric showers. The standard choice for most domestic final circuits.
  • Type C — 5 to 10 × In — trips instantaneously at 5 to 10 times rated current. Used for commercial circuits with moderate inrush loads: fluorescent and LED lighting banks, small motors, power supplies, and HVAC equipment. Common in commercial and light industrial distribution boards.
  • Type D — 10 to 20 × In — trips instantaneously at 10 to 20 times rated current. Used for high inrush loads: large motors (star-delta starting), transformers, welding equipment, and UPS systems where the inrush current at switch-on would otherwise trip a Type B or C breaker.
  • Impact on earth loop impedance — higher curve types require a lower earth loop impedance (Zs) to ensure the breaker trips within the required disconnection time under fault conditions. Always verify that the measured Zs meets the maximum Zs value for the MCB type and rating in use.
07 · Wiring Guide

Breaking Capacity and Prospective Fault Current

Breaking capacity is the maximum fault current a circuit breaker can safely interrupt without damage, expressed in kiloamperes (kA). Selecting a device with insufficient breaking capacity can result in catastrophic failure during a fault — the device may be unable to clear the fault, leading to arc flash, fire, or explosion.

  • Measure before specifying — always measure the prospective fault current (PFC) at the supply origin before specifying protective devices. For domestic consumer units this is typically done at the meter tails / incoming terminals. Record the result on the Electrical Installation Certificate.
  • 6kA for most domestic — the vast majority of UK domestic supplies will have a PFC below 6kA, making standard 6kA MCBs adequate. However, properties close to a substation, on TN-S systems, or on large commercial developments may exceed this.
  • Commercial installations — 10kA MCBs are standard for commercial distribution boards. For installations at or near transformer secondaries, MCCBs with breaking capacities of 25kA, 36kA, or higher may be required. The network operator's technical standards and site measurements determine the requirement.
08 · Wiring Guide

Selecting the Right Circuit Breaker for Your Installation

Circuit breaker selection involves assessing the load current, the prospective fault current, the earth loop impedance, the circuit's disconnection time requirements, and any specific load characteristics such as inrush current. The following practical guidance covers the most common UK scenarios.

  • Domestic consumer unit replacement — specify an all-RCBO board with Type A, 30mA, 6kA RCBOs. Use Type B curve for all final circuits. This eliminates nuisance tripping, provides BS 7671 18th Edition compliant additional protection, and simplifies certification.
  • Commercial distribution board — specify MCCBs for incoming protection (with appropriate breaking capacity based on measured PFC), Type C MCBs for general circuits, and Type D for motor circuits. Add 30mA RCDs or RCBOs for socket-outlet circuits as required by BS 7671.
  • EV charging circuit — use a Type A or Type B RCBO (not Type AC). Check the charge point manufacturer's documentation — some units have built-in Type B RCD protection, in which case a Type A upstream RCBO is acceptable.
  • Retrofit where Zs is marginal — if measured Zs is close to the maximum for the existing MCB, consider replacing with an RCBO of the same rating and curve type to add RCD protection without changing the overcurrent characteristic. Do not use a lower-rated MCB to improve Zs compliance — always consult the tables in BS 7671.
09 · Wiring Guide

For Electricians: Certification and Testing

Consumer unit replacements and new circuit installations are notifiable work in England and Wales under Part P of the Building Regulations. Electricians registered with a competent person scheme (NICEIC, NAPIT, ELECSA, or similar) can self-certify without involving building control.

EIC and Test Results Required

Every consumer unit replacement requires an Electrical Installation Certificate (EIC) and a complete Schedule of Test Results including PFC measurement, Zs measurements for each circuit, and RCD test results where applicable. Use the Elec-Mate EIC app to complete certification on site with no evening admin.

EICR Assessment

During an EICR, circuit breaker type, rating, and breaking capacity must be verified against the installation's requirements. MCBs without RCD protection on circuits requiring 30mA additional protection are a C2 observation. Devices with insufficient breaking capacity relative to the measured PFC are a C2 or C1 finding depending on the severity.

Complete consumer unit certificates on your phone

Join 1,000+ UK electricians using Elec-Mate for on-site EIC and EICR completion with AI board scanning, test result recording, and instant PDF export.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions About Circuit Breaker Types

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Complete Circuit Certificates and EICRs on Your Phone

Join 1,000+ UK electricians using Elec-Mate for on-site EIC and EICR completion with AI board scanning, test result recording, and instant PDF export. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy